a) Calculate the thermal resistance of each uniform material layer, which constitutes the building component, as follows:
where,
R i is the thermal resistance of material layer i, m2.K/W
t i is the thickness of material layer i, m
k i is the thermal conductivity of material layer i, W/(m.K)
b) Find the total thermal resistance, R π as follows:
where,
R τ is the total thermal resistance, m2.K/W
Rsi is the interior surface film thermal resistance, m2.K/W
Rse is the exterior surface film thermal resistance, m2.K/W
R j is the thermal resistance of material layer 1, m 2 . K / W
R z is the thermal resistance of material layer 2, m2.K/W
R z is the thermal resistance of material layer 3, m 2 . K / W
Use these default values for calculation,
| Wall | Roof | ||
| All Climatic Zones | Composite Climate, Hot-Dry Climate, Warm-Humid Climate, and Temperate Climate | Cold Climate | |
| Rsi (m².K/W) | 0.13 | 0.17 | 0.10 |
| Rse (m².K/W) | 0.04 | 0.04 | 0.04 |
Source Adapted from Bureau of Energy Efficiency (BEE), 2009. Energy Conservation Building Code User Guide, New Delhi
The thermal conductivity of commonly used building materials is given in Table 7, which can be used to calculate the thermal resistance (R value).
Bureau of Energy Efficiency (BEE)
22 |
ANNEXURE 5
c) Calculate the thermal transmittance (or the overall heat transfer coefficient or U value) of a wall or roof assembly, as follows:
where,
U is the overall heat transfer coefficient, W/(m2.K)
Table 7 gives typical thermal properties of commonly used building and insulating materials. This is not an all-inclusive list. In case, thermal conductivity values, measured using the appropriate IS codes, are available; those can also be used for calculations.
| Sl no. | Type of material | Density (kg/m3) | Thermal conductivity (W/m.K) | Specific heat capacity (kJ/kg.K) | Source |
| 1. Building materials | |||||
| 1 | Solid burnt clay brick | 1920 | 0.980 | 0.80 | (1) |
| 2 | Solid burnt clay brick | 1760 | 0.850 | NA | (1) |
| 3 | Solid burnt clay brick | 1600 | 0.740 | NA | (1) |
| 4 | Solid burnt clay brick | 1440 | 0.620 | NA | (1) |
| 5 | Resource efficient (hollow) brick | 1520 | 0.631 | 0.65 | (4) |
| 6 | Fly ash brick | 1650 | 0.856 | 0.93 | (2) |
| 7 | Solid concrete block 25/50 | 2427 | 1.396 | 0.20 | (4) |
| 8 | Solid concrete block 30/60 | 2349 | 1.411 | 0.30 | (4) |
| 9 | Aerated autoclaved concrete (AAC) block | 642 | 0.184 | 1.24 | (4) |
| 10 | Cement stabilized soil block (CSEB) | 1700 | 1.026 | 1.03 | (5) |
| 11 | Cement stabilized soil block (CSEB) | 1800 | 1.201 | 1.07 | (5) |
| 12 | Cement stabilized soil block (CSEB) | 1900 | 1.303 | 1.07 | (5) |
| 13 | Dense concrete | 2410 | 1.740 | 0.88 | (3) |
| 14 | Reinforced concrete cement (RCC) | 2288 | 1.580 | 0.88 | (3) |
| 15 | Brick tile | 1892 | 0.798 | 0.88 | (3) |
| 16 | Lime concrete | 1646 | 0.730 | 0.88 | (3) |
| 17 | Mud Phuska | 1622 | 0.519 | 0.88 | (3) |
| 18 | Cement mortar | 1648 | 0.719 | 0.92 | |
Bureau of Energy Efficiency (BEE)
| 23 |
ANNEXURE 5
| Sl no. | Type of material | Density (kg/m3) | Thermal conductivity (W/m.K) | Specific heat capacity (kJ/kg.K) | Source |
| 23 | Gl sheet | 7520 | 61.060 | 0.50 | (3) |
| 24 | Timber | 480 | 0.072 | 1.68 | (3) |
| 25 | Timber | 720 | 0.144 | 1.68 | (3) |
| 26 | Plywood | 640 | 0.174 | 1.76 | (3) |
| 27 | Glass | 2350 | 0.814 | 0.88 | (3) |
| 28 | Tar felt (2.3 kg/m2) | 0.479 | 0.88 | (3) | |
| II. Insulating materials | |||||
| 1 | Expanded polystyrene | 16.0 | 0.038 | 1.34 | (3) |
| 2 | Expanded polystyrene | 24.0 | 0.035 | 1.34 | (3) |
| 3 | Expanded polystyrene | 34.0 | 0.035 | 1.34 | (3) |
| 4 | Foam glass | 127.0 | 0.056 | 0.75 | (3) |
| 5 | Foam glass | 160.0 | 0.055 | 0.75 | (3) |
| 6 | Foam concrete | 320.0 | 0.070 | 0.92 | (3) |
| 7 | Foam concrete | 400.0 | 0.084 | 0.92 | (3) |
| 8 | Foam concrete | 704.0 | 0.149 | 0.92 | (3) |
| 9 | Cork slab | 164.0 | 0.043 | 0.96 | (3) |
| 10 | Cork slab | 192.0 | 0.044 | 0.96 | (3) |
| 11 | Cork slab | 304.0 | 0.055 | 0.96 | (3) |
| 12 | Rock wool (unbonded) | 92.0 | 0.047 | 0.84 | (3) |
| 13 | Rock wool (unbonded) | 150.0 | 0.043 | 0.84 | (3) |
| 14 | Mineral wool (unbonded) | 73.5 | |||
Table 7 contd...
24
ANNEXURE 5
| Sl no. | Type of material | Density (kg/m3) | Thermal conductivity (W/m.K) | Specific heat capacity (kJ/kg.K) | Source |
|---|---|---|---|---|---|
| 28 | Wall board | 262.0 | 0.047 | 1.26 | (3) |
| 29 | Chip board | 432.0 | 0.067 | 1.26 | (3) |
| 30 | Chip board (perforated) | 352.0 | 0.066 | 1.26 | (3) |
| 31 | Particle board | 750.0 | 0.098 | 1.30 | (3) |
| 32 | Coconut pith insulation board | 520.0 | 0.060 | 1.09 | (3) |
| 33 | Jute fibre | 329.0 | 0.067 | 1.09 | (3) |
| 34 | Wood wool board (bonded with cement) | 398.0 | 0.081 | 1.13 | (3) |
| 35 | Wood wool board (bonded with cement) | 674.0 | 0.108 | 1.13 | (3) |
| 36 | Coir board | 97.0 | 0.038 | 1.00 | (3) |
| 37 | Saw dust | 188.0 | 0.051 | 1.00 | (3) |
| 38 | Rice husk | 120.0 | 0.051 | 1.00 | (3) |
| 39 | Jute felt | 291.0 | 0.042 | 0.88 | (3) |
| 40 | Closed cell flexible elastomeric foam - NBR | 40–55 | 0.043 | 1.20 | (3) |
NA: Not available
Sources
(1) American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). 2009. 2009 ASHRAE Handbook (Fundamentals). Atlanta, United States: ASHRAE
(2) Gourav K, et al. 2017. Studies into structural and thermal properties of building envelope materials. Energy Procedia 122: 104–108
(3) Bureau of Indian Standards (BIS). 1987. Handbook on Functional Requirements of Buildings (Other than Industrial Buildings) SP: 41 (S & T) -1987. New Delhi: BIS.
(4) Thermo-Physical-Optical Property Database of Construction Materials, U.S.- India Joint Center for Building Energy Research and Development (CBERD) and Ministry of New and Renewable Energy (MNRE). Available at http://www.carbse.org/wp-content/uploads/2017/10/Data-base-of-Construction-Materials\_Oct17.pdf (accessed on 1 May 2018).
(5) Balaji N C, et al. 2015. Influence of varying mix proportions on thermal performance of soil-cement blocks. Building Simulation Applications (BSA). 2nd IBPSA Italy Conference, Building Simulation Application - 2015 (BSA 2015). Available at http://www.ibpsa.org/proceedings/BSA2015/9788860460745\_10.pdf (accessed on 1 May 2018).
In case, the construction has air layer, use values of thermal resistance of air layer given in Table 8 for U value calculation.
Bureau of Energy Efficiency (BEE)
| 25 |
ANNEXURE 5
| Thickness of Air Layer (mm) | Thermal resistance( m².K/W ) | ||
| Wall in All Climatic Zones | Roof in Composite Climate, Hot-Dry Climate, Warm-Humid Climate, and Temperate Climate | Roof in Cold Climate | |
| 5 | 0.12 | 0.10 | 0.10 |
| 7 | 0.12 | 0.12 | 0.12 |
| 10 | 0.14 | 0.14 | 0.14 |
| 15 | 0.16 | 0.16 | 0.16 |
| 25 | 0.18 | 0.18 | 0.17 |
| 50 | 0.18 | 0.20 | 0.17 |
| 100 | 0.18 | 0.20 | 0.17 |
| 300 | 0.18 | 0.21 | 0.17 |
Source Adapted from Bureau of Energy Efficiency (BEE), 2009. Energy Conservation Building Code User Guide, New Delhi