4th Floor, Sewa Bhawan, R K Puram, New Delhi, India
No portion (graphics or text) of this Code may be reproduced, translated, or transmitted in any form or manner by any means – including but not limited to electronic copy, photocopy, or any other information storage and retrieval system without explicit written consent from Bureau of Energy Efficiency, New Delhi.
All rights reserved
Printed in New Delhi, India
ISBN No.: 978-81-936846-3-4
1st Printed: December 2018
Printed on 100% recycled paper.
CONTENTS
List of tables ..............iv
List of figures ..............v
Committees and Working Groups ..............vii
CHAPTER 1 - INTRODUCTION ............1
CHAPTER 2 - SCOPE ............4
CHAPTER 3 - CODE PROVISIONS ............6
3.1 Openable Window-to-Floor Area Ratio (WFRop) ............6
3.3 Thermal Transmittance of Roof (Uroof) ............7
3.4 Residential envelope transmittance value (RETV) for building envelope (except roof) for four climate zones, namely, Composite Climate, Hot-Dry Climate, Warm-Humid Climate, and Temperate Climate ............8
3.5 Thermal transmittance of building envelope (except roof) for cold climate (Uenvelope,cold) ............10
CHAPTER 4 - CODE COMPLIANCE ............12
ANNEXURES
Annexure 1 Terminology and Definitions............14
Annexure 2 Climatic zone and classification of cities ............18
Annexure 3 Calculation of openable window-to-floor area ratio (WFRop) ............20
Annexure 4 Calculation of window-to-wall ratio (WWR) ............21
Annexure 5 Calculation of thermal transmittance (U value) of roof and wall............22
Annexure 6 Orientation Factor............27
Annexure 7 Calculation of Equivalent SHGC ............28
Annexure 8 Examples of Code Compliance ............37
Annexure 9 Guidelines for Design for Natural Ventilation............51
Annexure 10 Cool Roof and Roof Gardens ............56
Bureau of Energy Efficiency (BEE)
iii
Committees and Working Groups
Steering Committee
Abhay Bakre, Director General, Bureau of Energy Efficiency (Chair)
Saurabh Diddi, Director, Bureau of Energy Efficiency (Convenor)
Arijit Sengupta, Director, Bureau of Energy Efficiency (BEE)
Madhurima Madhav, Bureau of Indian Standards (BIS)
Amor Kool, Bureau of Indian Standards (BIS)
Vijay Garg, Council of Architecture (COA)
V P Singh, Ministry of Housing and Urban Affairs (MoHUA), Government of India
B K Bhatt, Ministry of New and Renewable Energy (MNRE), Government of India
R Srinivas, Town and Country Planning Organisation (TCPO)
S Surendra, Town and Country Planning Organisation (TCPO)
Pawan Kumar, Town and Country Planning Organisation (TCPO)
Anand Shukla, Swiss Agency for Development and Cooperation (SDC)
Abdullah Nisar Siddiqui, Bureau of Energy Efficiency (BEE)
Shatakshi Suman, Bureau of Energy Efficiency (BEE)
Anju Singh, Bureau of Energy Efficiency (BEE)
Karl May, Deutsche Gesellschaft für Internationale Zusammenarbeit (GIZ)
S Vikash Ranjan, Deutsche Gesellschaft für Internationale Zusammenarbeit (GIZ)
Govinda Somani, Deutsche Gesellschaft für Internationale Zusammenarbeit (GIZ)
Wesley Wojtas, Deutsche Gesellschaft für Internationale Zusammenarbeit (GIZ)
Apurva Chaturvedi, United States Agency for International Development (USAID)
Naveen Akkina, Indian Green Building Council (IGBC)
Punit Agarwal, Indian Green Building Council (IGBC)
Mili Majumdar, Green Building Certification Inc. (GBCI)
Apoorv Vij, Green Building Certification Inc. (GBCI)
Suhaas Mathur, Green Building Certification Inc. (GBCI)
Bureau of Energy Efficiency (BEE)
vii
Yatin Choudhary, The Energy and Resources Institute (TERI)
Pardeep Chauhan, The Energy and Resources Institute (TERI)
Disha Sharma, The Energy and Resources Institute (TERI)
Sonia Rani, The Energy and Resources Institute (TERI)
Alok K Modi, Gujarat Guardian Ltd (GGL)
Sourabh Kankar, Gujarat Guardian Ltd (GGL)
R Subramanian, Glazing Society of India (GSI)
Gopal Ganatra, Glazing Society of India (GSI)
G N Gohul Deepak, Glazing Society of India (GSI)
3.2Visible Light Transmittance (VLT)
3.2.1 Visible light transmittance (VLT) of non-opaque building envelope components (transparent/translucent panels in windows, doors, ventilators, etc.), indicates the potential of using daylight. Ensuring minimum VLT helps in improving daylighting, thereby reducing the energy required for artificial lighting.
3.2.2 The glass used in non-opaque building envelope components (transparent/translucent panels in windows, doors, etc.) shall comply with the requirements given in Table 2. The VLT requirement is applicable as per the window-to-wall ratio (WWR) of the building. WWR is the ratio of the area of non-opaque building envelope components of dwelling units to the envelope area (excluding roof) of dwelling units.
WWR=A
N Murali, Glazing Society of India (GSI)
Aditi Salway, The All India Glass Manufacturers' Federation (AIGMF)
Ragini Goswami, International Finance Corporation (IFC)
Ashok Lall, Ashok B. Lall Architects
Prashant Bhanware, Indo-Swiss Building Energy Efficiency Project (BEEP)
Saswati Chetia, Indo-Swiss Building Energy Efficiency Project (BEEP)
Vernica Prakash Kapoor, Indo-Swiss Building Energy Efficiency Project (BEEP)
Sameer Maithel, Indo-Swiss Building Energy Efficiency Project (BEEP)
Technical Committee
Saurabh Diddi, Director, Bureau of Energy Efficiency (Chair and Convenor)
Arijit Sengupta, Director, Bureau of Energy Efficiency (BEE)
Anju Singh, Bureau of Energy Efficiency (BEE)
Madhurima Madhav, Bureau of Indian Standards (BIS)
Ujjwal Mitra, Central Public Works Department (CPWD)
Rajeev Sharma, Central Public Works Department (CPWD)
R Srinivas, Town and Country Planning Organisation (TCPO)
Harpal Dave, Town and Country Planning Organisation (TCPO)
Anand Shukla, Swiss Agency for Development and Cooperation (SDC)
Tanmay Tathagat, Environmental Design Solutions (EDS) Global (P) Ltd
Piyush Varma, EDS Global (P) Ltd
viii
Ashok Lall, Ashok B. Lall Architects
Salil Mohan, Ashok B. Lall Architects
Rajan Rawal, Centre for Environmental Planning and Technology (CEPT)
Vishal Garg, International Institute of Information Technology (IIIT)
Jyotirmay Mathur, Malaviya National Institute of Technology (MNIT)
Shweta Manchanda, School of Planning and Architecture (SPA)
Abdullah Nisar Siddiqui, Bureau of Energy Efficiency (BEE)
Meenal Anand, Bureau of Energy Efficiency (BEE)
Karl May, Deutsche Gesellschaft für Internationale Zusammenarbeit (GIZ)
S Vikash Ranjan, Deutsche Gesellschaft für Internationale Zusammenarbeit (GIZ)
Govinda Somani, Deutsche Gesellschaft für Internationale Zusammenarbeit (GIZ)
Naveen Akkina, Indian Green Building Council (IGBC)
Shivraj Dhaka, Indian Green Building Council (IGBC)
Praveen Soma, Indian Green Building Council (IGBC)
Apoorv Vij, Green Building Certification Inc. (GBCI)
Suhaas Mathur, Green Building Certification Inc. (GBCI
Yatin Choudhary, The Energy and Resources Institute (TERI)
Pradeep Kumar, The Energy and Resources Institute (TERI)
G N Gohul Deepak, Glazing Society of India (GSI)
R Subramanian, Glazing Society of India (GSI)
N Murali, Glazing Society of India (GSI)
S Senthil Kumar, The All India Glass Manufacturers’ Federation (AIGMF)
Aditi Salway, The All India Glass Manufacturers’ Federation (AIGMF)
Isaac Emmanuel, Indian Insulation Forum (IIF)
Rohit Jain, Indian Institute of Architects (IIA)
Pierre Jaboyedoff, Indo-Swiss Building Energy Efficiency Project (BEEP)
Prashant Bhanware, Indo-Swiss Building Energy Efficiency Project (BEEP)
Saswati Chetia, Indo-Swiss Building Energy Efficiency Project (BEEP)
Vernica Prakash Kapoor, Indo-Swiss Building Energy Efficiency Project (BEEP)
Sameer Maithel, Indo-Swiss Building Energy Efficiency Project (BEEP)
1.1. India’s Intended Nationally Determined Contributions (INDCs) aim to reduce the emissions intensity of its gross domestic product (GDP) by 33 to 35 percent by 2030 from 2005 level.1 Any effort to achieve this target is contingent upon the increase in efficiency of energy use across all sectors, especially in the building sector. The building sector in India consumes over 30% of the total electricity2 consumed in the country annually and is second only to the industrial sector as the largest emitter of greenhouse gases (GHGs).
1.2. Out of the total electricity consumed in the building sector, about 75% is used in residential buildings. The gross electricity consumption in residential buildings has been rising sharply over the years. For instance, the consumption figure rose to about 260 TWh in 2016-17 from about 55 TWh in 1996-97.3 That is an increase by more than four times in 20 years. Projections show it rising to anywhere between 630 and 940 TWh by 2032.4 Among various reasons, increased use of decentralized roombased air-conditioning units in homes for thermal comfort is an important reason contributing to this rapid increase in the electricity use in residential buildings. The demand for air-conditioning will continue its exponential growth with improvement in household incomes and will become the dominant contributor of GHG emissions nation-wide owing to increased electricity consumption. This situation calls for an immediate energy conservation action plan.
1.3. Energy codes for new buildings are an important regulatory measure for ushering energy efficiency in the building sector. They are particularly relevant for countries like India where the building stock is growing rapidly. The commercial sector among buildings has been addressed by the Energy Conservation Building Code (ECBC) for Commercial Buildings. Given the current and anticipated rapid growth in the residential building stock across India and the consequent opportunities as well as the necessity for energy conservation in this sector, the Energy Conservation Code for Residential Buildings is established by the Ministry of Power.
Ministry of Statistics and Programme Implementation (MoSPI). 2018. Energy Statistics 2018. New Delhi: MoSPI, Government of India.
3 Central Electricity Authority (CEA). 2017. Growth of Electricity Sector in India from 1947-2017. New Delhi: CEA, Government of India.
4 NITI Aayog. India Energy Security Scenario, 2047. New Delhi: NITI Aayog, Government of India. Available at http://indiaenergy.gov.in/iess/default.php (accessed on 1 May 2018).
CHAPTER 1
INTRODUCTION
1.4. Building envelope consists of walls, roof, and fenestration (openings including windows, doors, vents, etc.). Design of building envelope influences heat gain/loss, natural ventilation, and daylighting,5 which, in turn, determines indoor temperatures, thermal comfort, and sensible cooling/heating demand.
1.5. Most parts of India have cooling-dominated climates.6 Consideration of heat gain is often not given sufficient importance during residential building design. It is seen that current practices of residential building design and construction show a large variation in heat gains and hence in the sensible cooling demand. Depending on the envelope design and construction adopted for residential buildings located in a particular climate zone, the minimum and maximum sensible cooling demand can vary by as much as 1:3.7
1.6. Energy Conservation Building Code – Residential (ECBC-R) (Part I: Building Envelope) has been prepared to set minimum building envelope performance standards to limit heat gains (for cooling dominated climates) and to limit heat loss (for heating dominated climates8), as well as for ensuring adequate natural ventilation and daylighting potential. The code provides design flexibility to innovate and vary important envelope components such as wall type, window size, type of glazing, and external shading to windows to meet the compliance.
1.7. The code is applicable to all residential buildings and residential parts of ‘mixed land-use projects’, both built on a plot area of ≥500 m2. However, states and municipal bodies may reduce the plot area based on the prevalence in their area of juris diction. This provision is kept to take into account the prevalent plot sizes and housing types in different states, enabling the inclusion of a greater percentage of new multi-dwelling unit residential buildings within the scope of this code. (Please refer paragraph 2.4.)
1.8. Building envelope has the highest impact on thermal comfort, and consequently on the energy use in residential buildings. The envelope is also a permanent component of the building with the longest life cycle. An early introduction of this code would improve the design and construction of new residential building stock being built currently and in the near future, thus significantly curtailing the anticipated
5 Bureau of Indian Standards (BIS). 1987 and 2016. Handbook on Functional Requirements of Buildings (Other than Industrial Buildings) SP: 41 (S & T) - 1987, and National Building Code (NBC) of India 2016. New Delhi: BIS.
These are climates where the ambient temperatures are high during major part of the year and mechanical space cooling is required for thermal comfort.
7 Bureau of Energy Efficiency (BEE). 2014. Design Guidelines for Energy-Efficient Multi-Storey Residential Buildings (Warm-Humid Climate). New Delhi: BEE.
8 These are climates where the ambient temperatures are low during major part of the year and mechanical space heating is required for thermal comfort.
| 2 |
INTRODUCTION
CHAPTER 1
energy demand for comfort cooling in times to come. This critical investment in envelope design and construction made today will reap benefits of reduced GHG emissions for the lifetime of the buildings.
1.9. Part I – Building Envelope of ECBC-R is designed in a simple-to-apply format, requiring only simple calculations based on inputs from the architectural design drawings of buildings. This can be used by architects and engineers and will not require any simulation software. This also enables the code to be readily adopted in the building bye-laws. A compliance tool is also available on BEE website to aid in the calculations and compliance check.
1.10. Part I – Building Envelope is the first part of ECBC-R. It is envisaged that new parts will be added to address other aspects, such as energy efficiency in electro-mechanical equipment for building operation, renewable energy generation, and embodied energy of building materials and structural systems.
Bureau of Energy Efficiency (BEE)
| 3 |
CHAPTER 2
Chapter 2
SCOPE
2.1 The code sets minimum performance standards for building envelope to limit heat gains (for cooling dominated climates) and limit heat loss (for heating dominated climates) through it. The code gives the following provisions to this effect:
l Building Envelope (except roof)
£ Maximum value of residential envelope transmittance value (RETV) for building envelope (except roof) applicable for four climate zones9, namely, Composite Climate, Hot-Dry Climate, Warm-Humid Climate, and Temperate Climate.
£ Maximum value of thermal transmittance of building envelope (except roof) for Cold Climate zone ( U e n v e l o p e , c o l d ) °
Roof: Maximum value of thermal transmittance of roof ( U r o o f ) for all climate zones.
2.2 The code sets minimum building envelope performance standard for adequate natural ventilation potential by specifying minimum openable window-to-floor area ratio (WFR ).
2.3 The code sets minimum building envelope performance standard for adequate daylight potential by specifying minimum visible light transmittance (VLT) for the non-opaque building envelope components.
2.4 The code applies to (a) ‘Residential buildings’ built on a plot area ≥500 m2 and (b) Residential part of ‘Mixed land-use building projects’,10 built on a plot area11 of ≥500 m2.
‘Residential building’12 includes any building in which sleeping accommodation is provided for normal residential purposes with or without cooking or dining or both facilities. This definition includes:
One or two family private dwellings: These shall include any private dwelling, which is occupied by members of one or two families and has a total sleeping accommodation for not more than 20 persons.
9 For climate classification, see Annexure 2.
10 However, residential accommodation in a building, where the carpet area of the residential part is not more than 30 m2 for caretakers or persons employed in connection with the building, is exempted.
11 States and municipal bodies may reduce the plot area based on the prevalence in their area of jurisdiction.
12 Adapted from Bureau of Indian Standards (BIS). 2016. National Building Code of India 2016. New Delhi: BIS
| 4 |
SCOPE
CHAPTER 2
Apartment houses: These shall include any building or structure in which living quarters are provided for three or more families, living independently of each other and with independent cooking facilities. This also includes ‘Group Housing’.
The following are excluded from the definition of ‘residential building’ for the purpose of this code.
Lodging and rooming houses: These shall include any building or group of buildings under the same management in which separate sleeping accommodation on transient or permanent basis, with or without dining facilities but without cooking facilities for individuals, is provided. This includes inns, clubs, motels, and guest houses.
Dormitories: These shall include any building in which group sleeping accommodation is provided, with or without dining facilities for persons who are not members of the same family, in one room or a series of closely associated rooms under joint occupancy and single management. For example, school and college dormitories, students, and other hostels and military barracks.
Hotels: These shall include any building or group of buildings under single management, in which sleeping accommodation is provided, with or without dining facilities.
Source Adapted from Bureau of Indian Standards (BIS). 2016. National Building Code of India 2016. New Delhi: BIS.
CHAPTER 3
Chapter 3
CODE PROVISIONS
3.1 Openable Window-to-Floor Area Ratio ( WFR0p )
3.1.1 Openable window-to-floor area ratio ( WFRop ) indicates the potential of using external air for ventilation. Ensuring minimum WFRop helps in ventilation, improvement in thermal comfort, and reduction in cooling energy.
3.1.2 The openable window-to-floor area ratio ( WFRop ) is the ratio of openable area to the carpet area of dwelling units.
WFRop=AcarpetA
where,
WFRop : openable window-to-floor area ratio
A openable
: openable area ( m 2 ) ; it includes the openable area of all windows and ventilators, opening directly to the external air, an open balcony, ‘verandah’, corridor or shaft; and the openable area of the doors opening directly into an open balcony.
Exclusions: All doors opening into corridors. External doors on ground floor, for example, ground-floor entrance doors or back-yard doors.
A carpet
: carpet area of dwelling units (m2); it is the net usable floor area of a dwelling unit, excluding the area covered by the external walls, areas under services shafts, exclusive balcony or verandah area and exclusive open terrace area, but includes the area covered by the internal partition walls of the dwelling unit.13
3.1.3 The openable window-to-floor area ratio ( WFRop ) shall not be less than the values14 given in Table 1.
Table 1Minimum requirement of window-to-floor area ratio ( W F R o p )
Climatic zone
Minimum WFR<sub>op</sub> (%)
Composite
12.50
Hot-Dry
10.00
Warm-Humid
16.66
Temperate
12.50
Cold
8.33
WFR op
13 The Real Estate (Regulation and Development) Bill, 2016 (as passed by the Rajya Sabha on the 10 March 2016). Avail able at http://164.100.47.4/BillsTexts/RSBillTexts/PassedRajyaSabha/realest-238-RSP-E.pdf (accessed on 1 May 2018) 14 To comply with the Code, (%) values shall be rounded off to two decimal places in accordance with IS 2: 1960 ‘Rules for rounding off numerical values’.
CODE PROVISIONS
CHAPTER 3
3.3Thermal Transmittance of Roof
3.3 Thermal Transmittance of Roof (Uroof)
3.3.1 Thermal transmittance ( U r o o f ) characterizes the thermal performance of the roof of a building. Limiting the U r o o f helps in reducing heat gains or losses from the roof, thereby improving the thermal comfort and reducing the energy required for cooling or heating.
3.3.2 Thermal transmittance of roof shall comply with the maximum U r o o f value of 1.2 W/m2.K.
WWR . ,
15 It is advised that a) the ≤ 015 minimum VLT should be 40% and b) the WWR in residential buildings may not exceed 0.40.
16 To comply with the Code, VLT values shall be rounded off to two decimal places in accordance with IS 2: 1960 ‘Rules for rounding off numerical values’.
17 To comply with the Code, WWR values shall be rounded off to two decimal places in accordance with IS 2: 1960 ‘Rules for rounding off numerical values’.
Bureau of Energy Efficiency (BEE)
| 7 |
CHAPTER 3
CODE PROVISIONS
3.3.3 The calculation18 shall be carried out, using Equation 3 as shown below.
Uroof=Aroof
where,
U r o o f : thermal transmittance of roof ( W / m 2 . K )
A r o o f : total area of the roof (m2)
U i : thermal transmittance values of different roof constructions ( W / m 2 . K )
A i : areas of different roof constructions (m2)
3.4 Residential envelope transmittance value (RETV) for building envelope (except roof) for four climate zones, namely, Composite Climate, Hot-Dry Climate, Warm-Humid Climate, and Temperate Climate
3.4.1 Residential envelope heat transmittance (RETV) is the net heat gain rate (over the cooling period) through the building envelope (excluding roof) of the dwelling units divided by the area of the building envelope (excluding roof) of the dwelling units. Its unit is W / m 2
RETV characterizes the thermal performance of the building envelope (except roof). Limiting the RETV value helps in reducing heat gains from the building envelope, thereby improving the thermal comfort and reducing the electricity required for cooling.
RETV formula takes into account the following:
l Heat conduction through opaque building envelope components (wall, opaque panels in doors, windows, ventilators, etc.),
l Heat conduction through non-opaque building envelope components (transparent/translucent panels of windows, doors, ventilators, etc.),
l Solar radiation through non-opaque building envelope components (transparent/translucent panels of windows, doors, ventilators, etc.)
3.4.2 The RETV for the building envelope (except roof) for four climate zones, namely, Composite Climate, Hot-Dry Climate, Warm-Humid Climate, and Temperate Climate, shall comply with the maximum RETV19 of 15 W / m 2 ,
18 To comply with the Code, U value shall be rounded off to one decimal places in accordance with IS 2: 1960 ‘Rules for rounding off numerical values’.
12 W/m²
19 BEE plans to improve the RETV norm to 12 W/m in the near future and the building industry and regulating agencies are encouraged to aim for it.
| 8 |
CODE PROVISIONS
CHAPTER 3
3.4.3 The RETV calculation20 of the building envelope (except roof) shall be carried out, using Equation 4 as shown below.
where,
A e n v e l o p e envelope area (excluding roof) of dwelling units ( m 2 ) . It is the gross external wall area (includes the area of the walls and the openings such as windows and doors).
A _ o p a q u e i areas of different opaque building envelope components (m2)
U _ o p a q u e i thermal transmittance values of different opaque building envelope components ( W / m 2 . K )
A n o n - o p a q u e i areas of different non-opaque building envelope components (m2)
| 9 |
U n o n - o p a q u e i thermal transmittance values of different non-opaque building envelope components ( W / m 2 . K )
SHGCeqi equivalent solar heat gain coefficient values of different non-opaque building envelope components (refer to Annexure 7)
ω _ i orientation factor of respective opaque and non-opaque building envelope components; it is a measure of the amount of direct and diffused solar radiation that is received on the vertical surface in a specific orientation (values are given in Annexure 6)
20 To comply with the Code, RETV value shall be rounded off to nearest integar value in accordance with IS 2: 1960 ‘Rules for rounding off numerical values’.
CHAPTER 3
CODE PROVISIONS
The coefficients of RETV formula, for different climate zones (for classification, refer to Annexure 2), are given in Table 3.
Table 3Coefficients (a, b, and c) for RETV formula