(See Regulation 8.5) INSPECTION CHECKLIST FOR FSO
| Sr. No. | Description | Details cum Compliance | FSO Inspection Remarks (if any) | Instructions for FSO |
| IN1. Fire Inspection Preparation | ||||
| IN1.1 | Name of FSO designated for the premises/ building | Mr./ Ms. / Mrs. | ||
| IN1.2 | Fire Inspection Date | DD.MM.YYYY | ||
| IN1.3 | Names of Persons who joined with FSO for inspection | Persons can be - fire officer of same premises, habitants of building/ premises etc., but should not be outsiders | ||
| IN1.4 | Name of person - 1 | Mr./ Ms. / Mrs. | ||
| Contact Details | mobile number | |||
| IN1.5 | Name of person - 2 | Mr./ Ms. / Mrs. | ||
| Contact Details | mobile number | |||
| IN2. Fire Prevention | ||||
| IN2.1 | Are surrounding roads of the buildings or premise observed free from obstruction during inspection and occupier made aware about such surrounding details and their significance for fire and emergency operation? | Yes/No | If "no" then, write in remarks about basic details about such obstruction with exact location and nature of obstruction and the owner/occupier should be instructed to remove the obstruction | |
| IN2.2 | Is there any noticeable new construction or expansion of existing construction at building/ premises? | Yes/No | If "Yes" then, write in remarks about the basic details of new construction, like - location/ dimensions/type of use etc. | |
| IN2.3 | Are HVWS / N2 system/ other system(s) for transformers, heating and cooling units etc. working effectively in auto operation condition? | Yes/No / Not Applicable | Write observation in remarks if any deficiency is found in the systems. Observations like - For HVWS: Water leak in pipelines, deluge valve in manual mode, valves in close conditions, any part found damaged or missing from the system etc.. For N2 system: Hydro test due date over for N2 cylinders, any valve in closed condition, N2 cylinder having low weight, any part found damaged or missing from the system, system in manual mode etc.. | |
| IN2.4 | Are Electrical MV main distribution panel (s) and lift panel(s) provided with CO2/inert gas flooding or equivalent fire protection system and working in auto operation condition? | Yes/No/ Not applicable | Enter details in case non-compliance is there | |
348-67
| Sr. No. | Description | Details cum Compliance | FSO Inspection Remarks (if any) | Instructions for FSO |
| IN2.5 | If a generator is there in the premise, is the generator in good operational health? | Yes/No / Not Applicable | Please check other parameters like - Is fuel level in the generator close to 100 % and is cooling water level in radiator filled with 100 % or healthy levels, engine oil in the engine filled till appropriate level? And is battery is good health and if wet type, filled with full water? Are emergency inter-connection operations functioning properly? If they are not in proper functional condition, write in remarks about non-compliance of particular point. It is not allowed and filled immediately if level law | |
| IN2.6 | Are the ventilation systems, including mechanical ventilation system, AHUs etc. working effectively? | Yes/No/ Not applicable | If "no", then write in remarks about non-compliance of particular point and ensure that necessary repairs/corrections are carried out | |
| IN2.7 | Whether a connecting cable from lightning arrestor to ground level earth pit is found healthy (check physical condition layout of cable) or not? Also, Is Lightning arrestor earth pit's periodic inspection did or not (check record)? | Yes/No/ Not applicable | If"no", then write in remarks about non-compliance and ensure that necessary repairs/corrections are carried out | |
| IN3. Life Safety | ||||
| IN3.1 | Are proper signage there for identification of exits, stairs, floor number and lifts apart from emergency lights, floor plan placed at relevant locations and adequate illumination with alternate power supply provided for safe movement of persons towards and through the exits (as applicable as per Fire Safety Certificate)? | Yes/No | See emergency evacuation floor plan and drawing for actual declared signages in approval copy of fire safety certificate issued by CFO/RFO. If compliance not there, then, write in remarks about location details with missing of signages and immediate compliance should be ensured | |
| IN3.2 | Is any exit or staircase or passage (lobby) location observed different at location as mentioned in original drawings at building/ premise? | Yes/No | See building GA/ floor plan drawing for actual declared EXIT/staircase/passage (lobby) in approval copy of fire safety certificate issued by CFO/RFO. If "yes" than, write in remarks about location details which has changes. Instruct for immediate compliance if non-compliance is there | |
348-68
[ PART IV-B
| Sr. No. | Description | Details cum Compliance | FSO Inspection Remarks (if any) | Instructions for FSO |
| IN3.3 | Is any exit, exit door, egress path or staircase or passage (lobby) location found temporarily or permanently closed or obstructed at building/ premises? | Yes/No | If "yes" than, write in remarks about location details which has changes and details of temporarily or permanently closed or obstructed stairs, doors, egress paths etc.. Instruct for immediate compliance to be passed if non-compliance is there | |
| IN3.4 | Are basement(s), if any as per the FSCA, provided with obstruction free approach, has adequate ventilations, sprinklers etc. and no changes have been made in overall fire-safety requirements since the issue of Fire Safety Certificate or last renewal? | Yes/No/ Not applicable | Enter details in case non-compliance is there | |
| IN4. Fire Protection | ||||
| IN4.1 | Are the fire extinguishers, fire alarms and other fire equipment, as applicable, in place in building/premise as declared (quantity and technical specifications, capacity) in the Fire Safety Certificate Approval and they are all in good working condition? | Yes/No | Check for hydro testing of fire protection equipment wherever applicable, take note of condition of hydrant points, valves, hose reels, pipes, nozzles, fire pumps, voice evacuation system, intercom, fire detectors, MCP system, visual warning systems, auto operation wherever required. Note pressure gauge of fire hydrant system and see if it is appropriate. Hydro test has to be done once in 5 years for Co2 type and once in 3 years for DCP/Foam/ Water type extinguishers. Any issues related to main fire line valve closing, electrical motor problem, diesel engine problem, jockey pump issues, pipeline leakage or choking, water sump empty, pump house suction or delivery valve failure in closed condition etc. should be mentioned in remarks if "no" option is selected | |
| IN4.2 | Test sample fire equipment and write their tag numbers or serial numbers with other details | Write the tag number of fire pump, fire hydrant / hose reel / monitor, extinguishers, etc. in remarks | ||
348-69
| Sr. No. | Description | Details cum Compliance | FSO Inspection Remarks (if any) | Instructions for FSO |
| IN4.3 | Are all delivery lines, suction line and main header valve of hydrant and sprinkler system in open and working condition? (if applicable) (Except valves of sprinkler testing line and bypass line/circular line at fire pump house) | Yes/No | If appropriate lines are found closed, they should be opened and the owner/occupier be instructed to keep them open. Write the tag number of valve with reason of closing, if found closed, in remarks | |
| IN4.4 | Is sprinkler system, if any as per Fire Safety Certificate, in the building/ premise in healthy condition and pressure gauge showing proper readings? | Yes/No /Not Applicable | Immediate attention needs to be paid if sprinkler systems have faults. Also check alarm valve/ deluge valve installed in sprinkler system and whether it is kept in auto mode. Check missing sprinkler heads if any and inspect sprinkler pump condition also. Details to be noted in remarks column | |
| IN5. Other Inspection Points | ||||
| IN5.1 | Are all electrical points, equipment in good condition, regularly serviced and does the building complies with various requirements of electrical safety as mentioned in GFP&LSM, regulations 2023 and as required by the Central Electricity Authority regulations and their amendments? | Yes/No/NotApplicable | If "no" then, write in remarks about non-compliance of particular points and direct the owner/occupiers for immediate action. Inspection and service record of the electrical equipment to be checked along the self-certification as required by the Central Electricity Authority regulations. Electrical panels to be checked and should not be found exposed and in hazardous condition | |
| IN5.2 | Is organization chart for emergency response and evacuation assignment designating employees and their assignments prepared and posted in a conspicuous place at each floor in premise/ building? | If it is not there, FSO to help the owner occupier to get it prepared and keep a sample handy with him or her and provide it to owner occupier in editable soft copy | ||
| IN5.3 | Is latest approved Fire Safety Plan available with premise/ building and distributed to all tenants/employees/owners of premises? | If it is not there, FSO to help the owner occupier to get it prepared and keep a sample handy with him or her and provide it to owner occupier in editable soft copy | ||
348-70
[ PART IV-B
| Sr. No. | Description | Details cum Compliance | FSO Inspection Remarks (if any) | Instructions for FSO |
| IN5.4 | Are building staff / residents, selected as sample, found to be given firefighting training, as per conditions of the Fire Safety Certificate? Were they found conversant in the basic fire safety drills including operation of fire safety instruments like fire extinguishers? | Yes/No | Basic fire safety training record to be checked and owner/occupier should be guided how to maintain it. If no such training given till date, one to be organized and details to be entered in remarks | |
| IN5.5 | Was a closing meeting organized to discuss on fire inspection's overall compliance status details, observations and recommendations with key persons of building/ premise? | Yes/No | Participants to be also be informed regarding other emergency situations (like earthquake, electrocution and preventive and protective and post-event measures) and be given basic demonstration of equipment like fire extinguishers, operation of alarms, valves and so on | |
| IN5.6 | Concluding remarks and recommendations | |||
| IN6. Attachment (if any) | ||||
| IN7. Inspection Completion | ||||
| Next Inspection due Date: | ||||