18.1 Staircase
18.1.1 For Buildings up to 45 meters (excluding parapet wall, lift and stair cabin, OH tank) & each floor area more than 3000 sq. meters- ventilated from two sides/cross ventilated/external staircases connected through a lobby-travel distance not to exceed 25 meters.
348-30
[ PART IV-B
18.1.2 If a centrally located staircase is provided with pressurization and fire-resistant doors, the central staircase shall be in addition to the ventilated staircases require for the floor area, maintaining the travel distance.
18.1.3 Width of staircase shall be 2 meters width for all buildings.
18.1.4 If the lift and staircase from higher floors go directly to the basements then this area shall be protected by 2 hours fire resistant construction including fire doors.
18.2 Lift
One Fire lift for each 1200 Sq. meters of floor area on each level.
18.3 Electrical duct
Electrical duct should have sealed metal doors with metal frame or fire rated doors at each floor level. Opening of the duct shall be from basement to terrace level.
18.4 Hollow plinth
Hollow plinth parking shall be protected with sprinklers as per Indian standard IS 15105.
18.5 Margins
All margins shall be as per CGDCR.
18.6 Ramp
Ramps shall be provided as per CGDCR.
18.7 Refuge area
Refuge area shall be provided as per CGDCR.