14.1 Basic Requirements:
(a) If a temporary structure and pandal is constructed then it shall be of fire resistant material and be open from two sides or provide two emergency exits marked "EMERGENCY EXIT".
(b) Minimum height of the ceiling of the temporary structure and pandal should not be less than 3.00 meters.
(c) No structure shall be erected under any live electrical line. It shall be minimum 15 mts away from the railway lines, electrical sub stations, furnaces and other hazardous places. If required, the distance may be increased as directed by the Regional fire Officer or the Chief Fire Officer.
(d) 4.5 mts margins shall be kept on all sides. Minimum width of the exits of the temporary structure and pandal shall be 2.5 mts.
(e) All the space used in and outside the public gathering place shall be made into a flat surface and entry/exit shall have a leveled surface without obstruction.
(f) Kitchens, if any shall be constructed 15 meters away from the temporary structure or pandal and be built by using tin sheets.
348-15
(g) No combustible material like wood shavings, straw, highly inflammable and explosive chemicals and similar materials should be permitted to be stored in the vicinity or inside the temporary structure and pandal.
(h) No fireworks display with open flames of any kind should be permitted close to the temporary structure and pandal.
(i) Every security guard and other supporting staff shall have a torch and shall ready all the time during dark hours of operation.
14.2 First-aid firefighting arrangements:
(a) A 200 liter water barrel along with water buckets/sand buckets shall be placed not more than 50 mts distance.
(b) Water type, Dry chemical powder and C02 type fire extinguishers shall be placed in required numbers at strategic locations.
14.3 Electrical Wiring:
(a) Electrical wires should pass through PVC conduits and not contact any flammable material. No loose wiring shall be allowed and all ends shall be properly taped and insulated.
(b) Big lights (halogen/halides) shall be at least 60cms, away from the rides or any metal structure temporarily constructed.
(c) Heavy cable connections shall be connected by ceramic connectors and then insulated along with the fuses. Power control switches, MCB or ELCB shall be installed for each specific use.
(d) All light fittings and lamps installed shall not be in contact with cloth or any other flammable material.
Standby generators of appropriate capacities shall be kept ready at the site in case of pandal having size more than 500sq.mt
14.4. Code of Practice for fire precautionary measures in construction of temporary structures and pandals shall be followed as provided in the IS No. 8758:2013
14.5. Maintaining the minimum standards and to follow the measures to be taken for fire prevention, life safety and fire protection in temporary structures and pandals shall be the liability of every owner or occupier of temporary premises or erectors of pandals.