5. Procedure for obtaining fire safety plan approval
5.1. Any applicant seeking the development permission under the Gujarat Town Planning and Urban Development Act, 1976 in any Fire Region, with regard to any building or premises mentioned in Third Schedule of the Rules, shall make an application as per ANNEXURE 1 to the Regional Fire Officer or the Chief Fire Officer, as the case may be, for obtaining the Fire Safety Plan Approval with requisite fees as may be prescribed, the required documents and building plans showing the minimum requirement, capacity and location of fire prevention, life safety and fire protection measures. The application shall be countersigned by the owner / builder/ developer and the Licensed Agency/ architect on record / engineer on record / structural engineer on record.
5.2. On receipt of the application made under regulation No. 5.1, the Regional Fire Officer or the Chief Fire Officer as the case may be shall, within a period of 21 days, scrutinize the same and on being satisfied that for the development proposed, the minimum requirement and location of fire prevention, life safety and fire protection measures as required under these regulations are shown in the fire safety plans, shall issue "Fire Safety Plan Approval" (FSPA) letter as per ANNEXURE 2. The fire safety plan may be rejected as per ANNEXURE 3 mentioning the reasons thereof. On the basis of this "Fire Safety Plan Approval" letter, the competent authority may grant the development permission under the provisions of the Gujarat Town Planning and Urban Development Act, 1976.
5.3. Prior to occupancy or use of any building specified in regulation No. 5.1, the owner / builder/ developer and the Licensed Agency / architect on record / engineer on record / structural engineer on record shall make an application for obtaining fire safety certificate to the Regional Fire Officer or the Chief Fire Officer, as the case may be, in "FORM-B14" of the Rules, along with the requisite fees as may be prescribed, for certifying that the completed construction complies with the minimum requirement and location of fire prevention, life safety and fire protection measures as required under these regulations and as shown in the fire safety plans on basis of which the "Fire Safety Plan Approval" certificate was issued.
Following self-certifications shall be submitted along with the application for Fire Safety Certificate Approval;
a) Self-certification by the Owner/ Occupier/ Builder/ Developer for maintaining fire prevention, life safety and fire protection measures as per approved fire safety certificate and doing no alteration of any part of the building without approval of the competent authority (ANNEXURE 13)
b) Self-certification by the Owner/ Occupier/ Builder/ Developer having done Annual Maintenance Contract (AMC) for fire protection equipment and system installed in the building/ premise (ANNEXURE 14)
c) Self-certification by owner/ occupier/ builder/developer regarding safe electrical installations inside building or premise (ANNEXURE 15)
When applying for fire safety certificate, in case there is a deviation from approved fire safety plan with regard to requirement and locations of fire prevention, life safety and fire protection measures, the fire safety plan has to be approved again as per the fire prevention, life safety and fire protection measures actually provided in the building / premises, after paying prescribed fee for fire safety plan approval (ANNEXURE 8), and then only application can be processed for the fire safety certificate.
348-5
5.4. On receipt of the application made under clause 5.3, the Regional Fire Officer or the Chief Fire Officer as the case may be shall, within a period of 21 days, scrutinize the same and after making such inquiry as it may deem fit, including the site visit, inspection, testing and on being satisfied that the construction completed fulfills the minimum requirements for fire prevention, life safety and fire protection measures, as required under these regulations, shall issue the fire safety certificate(FSC) in the prescribed "FORM-B13" of the Rules.
5.5. The Regional Fire Officer or the Chief Fire Officer as the case may be, may reject the application for issuance of fire safety certificate and inform the owner / builder/ developer and the Licensed Agency / architect on record / engineer on record / structural engineer on record as per ANNEXURE 4 by mentioning the reasons thereof.
5.6. In case of rejection of application for grant of fire safety certificate under regulation No. 5.5, a fresh application shall be made by the owner or occupier under regulation No. 5.3 duly complying with the requirements as communicated under regulation No. 5.5.
5.7. This fire safety certificate shall be valid for a period of three years from the date of issue unless cancelled by the Regional Fire Officer or the Chief Fire Officer after recording the reasons thereof.
5.8. The buildings or premises that have already been issued ‘No Objection Certificate’ for the occupancy of the building or premises shall deemed to have been issued Fire Safety Certificate under Rule 23 subject to verification of compliance of fire prevention, life safety and fire protection measures on which the ‘No Objection Certificate’ was issued on the last occasion.
5.9. The procedure of obtaining fire safety plan approval, issuance of fire safety certificate, uploading the required documents and plans, payment of requisite fees as may be prescribed, etc. need to be done on the Web portal https://gujfiresafetycop.in.
6. Enrolment of fire safety officer (FSO)
6.1. The Director shall issue the enrolment certificate to the fire safety officer in "Form-B12" of the Rules, after their successful completion of the training prescribed in the Rules and shall upload their details on the Web portal https://gujfiresafetycop.in.
6.2. The fire safety officer so enrolled can work anywhere in the State of Gujarat.
6.3. Any company wishing to enroll as fire safety officer must have a minimum of three fire safety officers which include at least one fire safety officer of Specialist grade.
6.4. The duties of fire safety officer shall be as prescribed in the FOURTH SCHEDULE of the Rules.
6.5. Fire safety certificate renewal shall be processed by the fire safety officers of different Grade for the type of buildings or premises, as specified in the FOURTH SCHEDULE of the Rules.
6.6. The owner or occupier shall appoint a fire safety officer who has no conflict of interest i.e., the appointed fire safety officer shall not have been involved in installation of fire protection and life safety measures in the same building/ premise for which he/ she has been appointed as fire safety officer. He/she shall not, in any case, issue fire safety certificate renewal for the building/ premises where he/she is employed/ engaged.
6.7. Licensed Agency cannot work as fire safety officer for the building/ premises for which owner or occupier has engaged it as a Licensed Agency.
7. Procedure for renewal of fire safety certificate
7.1. To get the fire safety certificate renewed (FSCR), every owner or occupier of the building or premises mentioned in THIRD SCHEDULE of the Rules and has been issued the fire safety certificate, shall appoint a fire safety officer from the list of fire safety officer enrolled by the Director, the details of which, shall be available on the Web portalhttps://gujfiresafetycop.in.
7.2. The owner or occupier shall appoint fire safety officer within two months prior to expiry of the validity of fire safety certificate issued under regulation No. 5.4 and upload the details on the Web portal https://gujfiresafetycop.in.
348-6
[ PART IV-B
7.3. However, in case where validity of the fire safety certificate of the existing building or premises mentioned in THIRD SCHEDULE of the Rules has expired on the date of coming into force of these regulations, the owner or occupier shall appoint fire safety officer as per regulation No. 6.0 and get the fire safety certificate renewed (FSCRe) for such existing building or premises through such appointed fire safety officer but not later than 90 days from coming into force of these regulations. In case fire safety certificate is not renewed within the said time limit, the fire safety certificate shall be treated as null and void; renewal shall not be permitted and In case, Fire Safety certificates is not obtained within the timelines defined above, the owner or occupier shall apply for the fire safety certificate again with penalty charges in the online system.
7.4. In case of a vacancy of the fire safety officer appointed under regulation No. 6.2 or 6.3, either on resignation or otherwise, the owner or occupier individually or jointly, as the case may be, shall immediately appoint the fire safety officer. In case of failure to do so, the Regional Fire Officer or the Chief Fire Officer may issue the notice for appointment of fire safety officer as per ANNEXURE 5.
7.5. The fire safety officer so appointed, shall inspect the building or premises for which he or she is appointed, to verify the compliance of relevant Rules and these regulations and on satisfaction that fire prevention, life safety and fire protection measures are in good repair and efficient operational condition and self-certifications as mentioned in Regulations No. 5.3 have been submitted, may issue a Fire Safety Certificate Renewal (FSCR) in "Form-B13.3" of the Rules, valid for a period of two years from the date of issue and for the same period thereafter.
7.6. After inspection of the building or premises, the appointed fire safety officer on being satisfied that owner or occupier has failed to ensure the compliance of relevant Rules and regulations and the provisions as laid down in the fire safety certificate or has change the use of building or premises or its part, shall reject the fire safety certificate renewal as per ANNEXURE 6 and inform the owner / occupier and the concerned Regional Fire Officer or the Chief Fire Officer as the case may be.
8. Annual and Bi-annual Declarations and Mock Drills
8.1. During the period of validity of the Fire Safety Certificate i.e. from the date of issuance till the first renewal of the same, the Licensed Agency shall give an annual declaration in "Form-B2" of the Rules, stating that the fire prevention, life safety and fire protection measures provided in the building or premises are operational, in good repair and efficient condition as specified in sub-section (2) of section 29 of the Act. This declaration shall be submitted to the Regional Fire officer or the Chief Fire officer not later than 15 days every year on completion of first and second year from the date of issue of fire safety certificate and it shall be uploaded on the Web portal https://gujfiresafetycop.in.
8.2. In case of Licensed Agency is not appointed, annual declarations in "Form-B2"of the rules, shall be given by the owner or occupier individually or jointly or by the developer as provided for in regulation No. 8.1.
8.3. The fire safety officer appointed as per regulation No. 6.2 or 6.3, after inspection of the building or premises shall declare every six months from the date of issue of fire safety certificate renewal (FSCR/FSCRe) in "Form-B15" of the Rules that fire prevention, life safety and fire protection measures provided in the building or premises are operational, in place and in best repairs.
8.4. The six-monthly declaration cum inspection report as per regulation No. 5.3 shall be uploaded on the Web portal https://gujfiresafetycop.in by the fire safety officer within stipulated time. Failure to do so may attract penalty as mentioned in regulation 11.
8.5. The fire safety officer shall also perform bi-annual emergency mock drills along with inspection of the fire safety measures and give declaration and maintain record of the same. Refer ANNEXURE 11 for checklist of mock fire and emergency drill and ANNEXURE 12 for the building/premise Inspection Checklist.
348-7
9. Check Lists
9.1. The details of Form Code of checklist, which is a part of the application form, specifying mandatory requirement for fire protection measures in the building/ premises based on building occupancies and categories, for Fire Safety Plan Approval (FSPA), Fire Safety Certificate Approval (FSCA) and Fire Safety Certificate Renewal (FSCR) are as mentioned in the TABLE-1 and for Fire Safety Certificate Renewal of the fire safety certificate issued prior to coming into force of these regulations (FSCRe) are as mentioned in TABLE-2.
Refer National building code of India- Part 4 for understanding the categorization of occupancy sub-type which is mentioned within brackets in Column 2 of the said TABLE 1
Irrespective of what is mentioned in FOURTH SECHEDULE of the amended Rules, 2021, for the purpose of FSCRe, the classification of buildings/ premises for appointment of FSOs for renewal of FSCRe, the grade of FSO shall be as mentioned in column 6 of TABLE 2 below.
9.2. The Checklists for various building categories are as per ANNEXURE 7.1 to 7.183of these regulations. The checklists are available on the web portal https://gujfiresafetycop.in. For convenience of citizens and users, commonly used nomenclature may have been used in the Checklists on the web portal.
| Occupancy Main Type | Occupancy Sub-Type (Refer NBC code Part 4) | Sr. No. | Building Categories | Form Code (FSPA) | Form Code (FSCA) | Form Code (FSCR) |
| 1 | 2 | 3 | 4 | 5 | 6 | 7 |
| Residential & Lodging | Dormitories, Flats, Hostels & Apartment Houses etc. (A-3) & (A-4) | 1 | 15 m and above but not exceeding 35 m in height | C1R1-P | C1R1-C | C1R1-R |
| 2 | Above 35 m but not exceeding 45 m in height | C1R2-P | C1R2-C | C1R2-R | ||
| 3 | Above 45 m but not exceeding 60 m in height | C1R3-P | C1R3-C | C1R3-R | ||
| 4 | Above 60 m but less than 100 m in height | C1R4-P | C1R4-C | C1R4-R | ||
| Hotels & Guest Houses etc. (Below 5 star) (A-5) | 5 | Less than 15 m in height Floor area exceeding 500 m2 but not more than 1000 m2 on any of the floor | C1R5-P | C1R5-C | C1R5-R |
10. Application fees
Application Fees for Fire Safety Plan Approval (FSPA), Fire Safety Certificate Approval (FSCA) and Fire Safety Certificate Renewal (FSCR) shall be paid to concerned Regional Fire Officer or the Chief Fire Officer as per ANNEXURE 8. Application Fees for Fire Safety Plan Renewal of existing building with FSC (FSCRe) shall be as per ANNEXURE 9.