15.4.1 Lift shall be provided in all buildings as prescribed hereunder
15.4.2 The planning and design of lifts including their number, type and capacity depending on the occupancy of the building, the population on each floor based on the occupant load and the building height shall be in accordance with the National building code of India.
15.4.3 In case of Building having height more than 13.0 mts from ground level, lift shall be provided. Lift shall have all the provision of fire life as specified in the National building code of India.
15.4.4 In case of building with 21 meters or more in height, at least two lifts shall be provided. From these lifts at least one of them shall be designed as fire lift as specified in National building code of India.
15.4.5 Lift shall be provided at the rate of one lift for 30 dwelling units of all the floors, or part thereof for residential buildings and at the rate of one lift per 1200.00 Sq.mts. or part thereof of builtup area for non-residential buildings.
15.4.6 The tenement and built-up area on ground floor and two upper floors shall be excluded in computing the above requirement.
15.4.7 Lift shall be provided from ground floor or lower level and shall have minimum capacity of six persons. On the basis of detailed calculations based on the relevant provisions of National Building Code, the number of lifts can be varied.
15.4.8 Minimum internal dimensions for passenger lifts shall be 1500 mm x 1500mm. A clear landing area in front of the lift doors shall be 1800mm x 1800mm and clear opening width of the doors shall be of minimum 900 mm. A handrail of 600 mm length at 1000 mm height from the floor shall be provided.
348-17
15.4.9
The time of an automatically closing door should be minimum 5 seconds and the closing speed should not exceed 0.25 m/sec. The interior of the cage shall be provided with a device that audibly indicates the floor the cage has reached and indicates that the door of the cage for entrance/exit is either open or closed.
15.4.10 Maintenance:
a) The lift installation should receive regular cleaning, lubrication adjustment and adequate servicing by authorized competent persons at such intervals as the type of equipment and frequency of service demand. In order that the lift installation is maintained at all times in a safe condition, a proper maintenance schedule shall be drawn up in consultation with the lift manufacturer and rigidly followed. A log book to record all items relating to general servicing and inspection shall be maintained.
b) The electrical circuit diagram of the lift with the sequence of operation of different components and parts shall be kept readily available for reference by persons responsible for the maintenance and replacement, where necessary, to the satisfaction of the competent authority.
c) Any accident arising out of operation of maintenance of the lifts shall be duly reported to the competent authority.