15.5.1 General Exit Requirements:
a) An exit may be a door way, corridor, passageway(s) to an internal staircase, or external staircase, or to a veranda or terrace(s), which have access to the street, or to roof of a building or a refuge area. An exit may also include a horizontal exit leading to an adjoining building at the same level.
b) Lifts and escalators shall not normally be considered as exits.
c) Every exit, exit access or exit discharge shall be continuously maintained free of all obstructions or impediments for full use in the case of fire or other emergency.
d) Every building meant for human occupancy shall be provided with exits sufficient to permit safe escape of occupants, in case of fire or other emergency.
e) In every building or structure, exits shall comply with the minimum requirements of this part, except those not accessible for general public use.
f) No building shall be so altered as to reduce the number, width or protection of less than that required.
g) Exits shall be clearly visible and the route to reach the exits shall be clearly marked and signs posted to guide the occupants of the floor concerned. Signs shall be illuminated and wired to an independent electrical circuit on an alternative Source of supply. The color of the exit signs shall be green.
h) The floors of area covered for the means of exit shall be illuminated to values not less than 1 ft candle (10 lux) at floor level. In auditoriums, theatres, concert halls and such other places of assembly, the illumination of floor exit/ access may be reduced during period of performances to value not less than 1/5 ft candle (2 lux)
i) Fire doors with 2-hour fire resistance shall be provided at appropriate places along the escape route and particularly at the entrance to lift lobby and stairwell where a funnel or flue effect may be created, inducing an upward spread of fire and smoke.
j) All exits shall provide continuous means of egress to the exterior of a building or to an exterior space leading to a street.
k) Exits shall be arranged that they may be reached without passing through another occupied unit.
348-18
[ PART IV-B
15.5.2 Illumination of means of Exit:
a) Staircase and corridor light shall confirm to the following:
b) The staircase and corridor lighting shall be the separate circuits and shall be independently connected so that they could be operated by one switch installation on the ground floor easily accessible to firefighting staff at any time irrespective of the position of the individual control of the light points, if any. It should be miniature circuit breaker type of switch so as to avoid replacement of fuse in case of crisis.
c) Staircase and corridor lighting shall also be connected to alternative supply. The alternative source of supply may be provided by battery continuously trickle charged from the electric mains; and
d) Suitable arrangement shall be made by installing double throw switches to ensure that the lighting installed in the staircase and the corridor does not get connected. Double throw switch shall be installed in the service room for tenanting the stand- by supply.
15.5.3 External Stairs:
a) An external staircase is desirable to be provided for high rise buildings and special buildings, if the safe travel distance for exit not maintained. External stairs, when provided shall comply with the following:
b) External stairs shall always be kept in sound operable conditions.
c) All external stairs shall be directly connected to the ground.
d) Care shall be taken to ensure that no wall opening or window opens on to an external stair.
e) The route to the external stairs shall be free of obstructions at all time.
f) The external stairs shall be constructed of non- combustible materials and any doorway leading to it shall have the required fire resistance.
g) No external staircase, used as a fire escape, shall be inclined at an angle greater than 45° from the horizontal.
h) External stairs shall have straight flight not less than 1250 mm wide with 250 mm treads and risers not more than 190 mm. The number of risers shall be limited to 15 per flight.
i) Handrail s shall be of height not less than 700 mm and not exceeding 850 - 900 mm. There shall be provisions of balusters with maximum gap of 150 mm.
15.5.4 Horizontal Exits:
a) The width of horizontal exit shall be same as for the exit doorways.
b) A horizontal exit shall be equipped with at least one fire/smoke door of minimum 2- hour fire resistance of self-closing type. Further, it should have direct connectivity to the fire escape staircase for evacuation.
c) Where there is a difference in level between connected areas for horizontal exits, ramps, not more than 1 to 10 slope shall be provided, steps shall not be used.
d) Doors in horizontal exits shall be open able at all times from both sided.
15.6 Fire Access Stair cases
15.6.1 Staircases to abut on outer wall or be external part of to the building are naturally cross ventilated.
15.6.2 The stairs should not have opening to any part of the building. At least one staircase shall be on external walls of building and shall open directly to the exterior, interior open space or to an open plan of safety. Further, the provision or otherwise of alternative staircases shall be subject to the requirements of travel distance being complied with. It shall be 20 mt. for hazardous use,25 mt for residential use and 25 mt. for non-residential use.