13. GENERAL
13.1. Every owner or occupier of such temporary premises or erectors of pandals, to take such fire prevention, fire safety and fire protection measures as may be required under these regulations shall be deemed to be self-regulators for taking fire prevention, fire safety and fire protection measures.
13.2. The erector shall display a declaration to the effect that he or she has taken all the prescribed fire prevention, fire safety and fire protection measures in the “Form C1” of the Rules under his/her own signature at a prominent place in the premises, not less than 48 hours before starting to use the premises. The checklist as per ANNEXURE 10 needs to be filled in the https://gujfiresafetycop.in portal by paying the fee of Rs. 2000/- online.
13.3. The fire authority can enter and inspect any temporary structure or pandal about the correctness of the declaration, point out the shortcomings, if any, with directions to remove them within a specified time.
13.4. If the directions of the fire authority are not complied within the time so given, the fire authority may seal the temporary structure or pandal or dismantle such structure or pandal and costs incurred shall be recovered from such defaulter. If the owner or the occupier continues to disobey the directions, the fire authority, may fine the owner or occupier of such temporary premises or erector of pandal up to Rs. 1,00,000/- and for continuing the offence, further fine of Rs. 1,000/- per day.
13.5. Any false declaration filled in form of an online checklist shall be deemed to be a criminal offence punishable under the Indian Penal Code.
13.6. Minimum standards and the measures to be taken for fire prevention and life safety in temporary structures and pandals shall be as per Rules 27 and 31 and as per regulation No. 13 & 14.
13.7. In case where the use of the temporary structure or pandal is meant to attract public gathering, then the owner or the occupier of temporary structure or the erector of the pandal shall submit to the Regional fire Officer or the Chief Fire Officer:-
(a) a layout plan indicating access to the temporary structure or pandaI,
(b) the location, dimensions and area of stalls, sanitary facilities and other uses,
(c) the plans showing the construction at the sites, if any,
(d) a certificate with photograph from a registered electrical engineer to ensure proper load distribution and wiring in case of the temporary structure or pandal having size more than 500sq.mt.,
(e) any other plans or documents as may be directed by the Regional fire Officer or the Chief Fire Officer.