19.1 Staircase:
19.1.1 For more than 45 meters (excluding parapet wall, lift and stair cabin, OH tank) & each floor area more than 3000 sq. meters- ventilated from two sides/cross ventilated/external staircases connected through a lobby-travel distance not to exceed 25 meters.
19.1.2 If a centrally located staircase is provided with pressurization and fire-resistant doors, the central staircase shall be in addition to the ventilated staircases require for the floor area, maintaining the travel distance.
19.1.3 Width of staircase shall be 2 meters width for all buildings.
19.1.4 The staircase shall be of RCC construction & ventilated and shall be kept open except the parapet wall, all the space above the parapet wall shall be kept open.
19.1.5 The staircase shall be designed/ located at the exterior part of the building. If the staircase is in the center of the building and is not ventilated then a fire escape staircase (fire tower) has to be installed on either side of the building with travel distance not more than 30 meters.
19.2 Lift
If the lift and staircase from higher floors go directly to the basements then this area shall be protected by 2 hours fire resistant construction including fire doors.
19.3 Fire lift
19.3.1 One fire lift for each 1200 sq. meter area of floor area on each level (Fire lift otherwise can be used as a common passenger lift).
19.3.2 All lifts of the building shall be Fire lifts and shall have a provision to ground in case of electrical failure and shall be installed with a panic button and a talk-back system. The lift shall not be installed in the center of the building and the lift shaft shall be ventilated from the top with smoke extractors. The lift for the higher floors shall end at the ground level and not go to the basement
348-31
19.4 Electrical duct
Electrical duct should have sealed metal doors with metal frame or fire rated doors at each floor level. Opening of the duct shall be from basement to terrace level.
19.5 Hollow plinth
Hollow plinth parking shall be protected with sprinklers as per Indian standard IS 15105.
19.6 Margins
All margins shall be as per CGDCR.
19.7 Ramp
Ramps shall be provided as per CGDCR.
19.8 Refuge area
Refuge area shall be provided as per CGDCR.
19.9 Electric supply
19.9.1 Electric supply to the Fire pumps, fire lift all shall be supplied parallel (standalone) to the building supply and should not get cut- off if the supply to the building is switched off.
19.9.2 All the electric wiring used shall be of 900 volt grading and connected to each enclosure through a MCB for a particular load.
19.10 Auto glow signage
All exits, corridors and staircase shall have auto glow signs for people to escape in case of fires in darkness. Even the floors shall have guide marks guiding towards the staircase.
19.11 Ventilation
19.11.1 Ventilation of stair-cases:
Every stair case provided under the foregoing clauses shall be lighted and ventilated to the satisfaction of the Authority from an open-air space not less than 1 sq.mt.
19.11.2 Windows in stair-case Bay:
There shall be provided a window or windows of an aggregate area of at least 1.2 sq. meters on each storey in such of the wall of the stair-case room which abuts on such 1 sq.mt. open air space to right and ventilate such staircase.
19.12 Skip floor/Refuge area
Skip floor/Refuge area shall be provided as per CGDCR.
20. Buildings of Height more than 100 meters (From ground level to top floor ceiling height):
The Fire prevention, Life safety and Fire protection measures shall be provided as per this regulation and CGDCR 2017 along with the subsequent notifications.
21. Mixed Occupancy:
CGDCR shall be followed for the provisions related to Fire prevention and life safety measures in addition to the provisions under the regulations.
22. Institutional buildings:
22.1 CGDCR shall be followed for the provisions related to Fire prevention and life safety measures in addition to the provisions under the regulations.
22.2 In case of standalone institutional buildings/ premises minimum two staircases with width not less than 2 m shall be provided.
348-32
[ PART IV-B
23. Storage Buildings:
23.1 These shall conform to those given in Part 4 of National Building Code of India.
23.2 Storage Buildings beyond 15 meters height shall not be permitted. However, building used for Car Park may be permitted beyond 15 meters.
24. Hazardous Building:
24.1 These shall conform to those given in Part 4 of National Building Code of India.
24.2 Hazardous Buildings beyond 15 meters height shall not be permitted. However, building used for Car Park may be permitted beyond 15 meters.
25. Assembly Building:
25.1 Railway station including Metro stations buildings, bus stations building, sea port building, Airport building and other public gathering buildings shall be considered as an assembly building according to the national building code of India and provisions related to fire prevention, life safety and fire protection, shall follow as per this regulation, CGDCR, their respective govt. norms.
25.2 Beam smoke detectors installed across the assembly building.
25.3 The material used for seats and lining shall be of Fire-resistant material.
25.4 The foyer and the halls shall have emergency lights operating automatically in case of electricity failure.
25.5 The projection room shall have suitable Fire extinguishers and shall have doors on two extreme sides.