(a) All wiring in connection with the lift installation shall be installed in accordance with the rules and regulations made under the Indian Electricity Act, 1910 and the rules and regulations of the Bombay Fire Insurance Association, and metallic covering shall be used to protect all cables wherever possible.
(b) Circuits which supply current to the motor shall not be included in any twin or multicore trailing cable used in connection with the control and safety devices.
(c) A trailing cable which incorporates conductors for the control circuit shall be separate and distinct from that which incorporates conductors for lighting and signaling circuits.
(d) The electric supply for the lifts shall be on separate circuits from the main switch rooms and shall be taken through armored cable separately through respective lift shafts. The route of the armored cable shall be safe from fir.
(e) A trailing cable which incorporates conductors for the control circuit shall be separate and distinct from that which incorporates lighting and signaling circuits in the case of buildings less than 30m in height. In the case of building more than 30m in height or where high speed lift (1.52m/s or more) are employed, use of single traveling cable for lighting and control circuits is permitted. Provide that all conductors are insulated for the maximum voltage found in the cable.