(1) (a) The stopping of the lift machine or stopping the main circuit shall be controlled as detailed below:—
(i) Motor Supplied Directly from AC or DC mains.—The supply to the motor shall be interrupted by two independent contractors, the contract of which shall be in series in the motor circuit.
(ii) Drive Using a ‘Ward-Leonard’ System.—Two independent contactors shall interrupt the excitation of the generator.
(iii) A.C or DC Motor supplied and controlled by static elements. One of the following methods shall be used:—
(a) Two independent contactor shall interrupt the current to the motor.
(b) A System consisting of ,—
(1) A contactor interrupting the current in all the phases. The coil of the contactor shall be released at least before each change in direction. If the contactor shall be released at least before each change in direction. If the contactor does not release, any further movement of the lift shall be prevented.
(2) A control device blocking the flow of energy in the static elements.
(3) A monitoring device to verify the blocking of the flow of energy each time the lift is stationary. If during a normal stopping period, ;the blocking of the flow of energy by the static elements is not effective, the monitoring device shall cause the contractor to release and any further movement of the lift shall be prevented.
(2) The interruption of the electrical safety chain or safety circuit shall stop and shall prevent the movement of the car. In the event of an earth fault with any door open, the lift shall not operate.
(3) Operation of a spring or springs in tension or the completion of another electric circuit shall not be depended upon to break the circuit to stop; the lift at the terminal landings.
(4) Each lift machine operated by a polyphase AC motor shall be protected against phase reversal or failure. This shall not apply to an AC motor forming part of a motor generator. This protection shall be considered provided in the case of generator-field control having alternating current motor-generator driving motors, provided a reversal of phase does not cause the elevator driving machine motor to operate in the wrong direction. Controllers whose switches are operated by polyphase torque motors provide inherent protection against phase reversal or failure.
(5) No control system shall depend upon the completion or maintenance of an electrical circuit for the interruption of the power supply to the lift motor and the application of the machine brake to stop the lift car,—
(i) at the terminal floor, or
(ii) when the emergency stop switch or other safety device is operated.
Note.—This requirement does not apply to dynamic braking or to speed control.
(6) All control circuits should be protected by fuses or otherwise protected against faults or overloads, independently of the main circuits.
(7) The wiring of the controller shall conform to the latest provisions of Indian Electricity Rules and the voltage of any controller operating circuit shall not exceed the low voltage of 250 V as defined therein. The control circuit shall be suitably protected independently of the main circuit and it shall be so arranged that an earth fault or open circuit shall not create an unsafe condition.
(8) The high voltage test shall be performed as given in IS 14665(Part 3/Sec 1): 2001’Electric traction lifts: Part 3 Safety rules, Section 1 Passenger and goods lifts.