(a) The service lift machine controller and all other apparatus and equipment of the same, excepting such apparatus and equipment as function in the lift well or other positions shall be placed in the motor room which shall be adequately lighted and rendered fireproof and weatherproof.
(b) The secondary sheaves pulleys, floor selecting equipment may be placed in a place other than the motor room but such position shall be adequately lighted and rendered fireproof and weatherproof.
(c) The machine room floor shall be designed and constructed to carry safely at any point the heaviest portion or unit of equipment both during erection and for maintenance purpose.
(d) The machine room shall be kept closed except to those concerned with the operation and maintenance of machinery or equipment.
(e) The machine room shall be equipped with an insulated portable hand lamp provided with flexible cord for examining the machinery.
(f) If any machine room floor or platform does not extend to the enclosing walls, the open sides shall be provided with hand rails or otherwise suitably guarded.
(g) The machine room shall be provided with access doors opening outwards.
(h) The machine room shall not be used as a store room or for any purpose other than housing the lift machinery and its associated apparatus and equipment.
(i) All machines, pulleys, ;and similar units shall be so supported and held as to prevent any of these machines or parts thereof becoming loose or displaced affecting their safe working. Supporting beam shall be of steel or reinforced concrete.
(j) There shall be direct access to the service lift machine room.
(k) The height of the machine room shall be sufficient to allow any portion of equipment to be accessible and removable for repair and replacement, and shall be not less than 1.2m clear from the floor.
(l) The total load on the overhead beams shall be assumed as equal to all equipment resting on the beams plus twice the maximum load suspended from the beams.
(m) The factor of safety for all overhead beams and supports based on ultimate strength of the material and load in accordance with clause (l) shall not be less than the following:
For Steel 5
For reinforced concrete 7.
(n) Housing of Overhead Pulleys:- The penthouse or other space in which overhead pulleys, are housed shall have a clear height of at least 1.0 m and shall allow safe and convenient access and where practicable, have a substantial platform or floor and be provided with permanent and adequate artificial illumination.
- LIFT MACHINES .—(i) No friction gearing, belt, chain, clutch or chain driven mechanism shall be used for connecting the main driving gear to the traction sheaves.
(ii) The motor of each lift machine or the worm shaft shall be arranged so as to provide hand-winding facilities and shall be suitable marked for the direction of up and down travel of the lift car.
(iii) Use of Overhung Pulleys.- In the case of the use of overhung traction sheaves, effective precautions shall be taken to avoid the following:—
(a) The ropes leaving their grooves, and
(b) Objects lodging between the grooves and the ropes in the case where the machine is not above the well. These precautions shall not present examination and servicing of traction sheaves and sprockets.
(iv) Protection of Machinery .- Effective protection shall be provided for accessible rotating parts, which may be dangerous, in particular ,—
(a) Keys and screws in the shafts, and
(b) Projecting motor shafts.
Exception is made for traction sheaves, hand-winding wheels, brake drums and any similar smooth round parts. Such items shall be painted yellow at least in part.
(v) A fillet shall be provided at any point of change in the diameter of driving machine shafts and sheave shafts to prevent excessive stress concentrations in the shafts.
(vi) Shafts which support sheaves, gear, couplings and other members, which transmit torque, shall be provided with tight-fitting keys.