15.1 Envelope Summary
| Envelope SummaryThe Punjab Energy Conservation Building Code 2013 Compliance Forms | |||
| Project Info | Project Address | Date | |
| For Building Department Use | |||
| Applicant Name: | |||
| Applicant Address: | |||
| Applicant Phone: | |||
| Project Description | ☐ New Building ☐ Addition ☐ Alteration ☐ Change of Use | ||
| Compliance Option | ☐ Prescriptive ☐ Envelope Trade-Off ☐ Whole Building (Appendix D) Performance | ||
| ☐ Hospital, hotel, call center (24 hour) ☐ Other building types (daytime) | |||
| Vertical Fenestration Area CalculationNote: Vertical fenestration area can not exceed 60% of the gross wall area for prescriptive option | Total Vertical divided by Gross Exterior times 100 Fenestration Wall Area equals % Vertical Area (rough opening) | ||
| ÷ | X 100 = | ||
| Skylight Area CalculationNote: Skylight area can not exceed 5% of the gross roof area for prescriptive compliance. | Total Skylight divided by Gross Exterior times 100 Fenestration Wall Area equals % Vertical Area (rough opening) | ||
| ÷ | X 100 = | ||
Appendix F: PECBC Compliance Forms
Hospital, hotel, call center (24 hour)
OPAQUE ASSEMBLY
FENESTRATION
| Roof Minimum Insulation R-value | |
|---|---|
| Wall Minimum Insulation R-value |
| Vertical | |
|---|---|
| Maximum U-factor | |
| Maximum SHGC (or SC) | |
| Overhang (yes or no) | |
| If yes, enter Projection Factor | |
| Side fins (yes or no) | |
| If yes, enter Projection Factor | |
| Skylight | |
| Maximum U-factor | |
| Maximum SHGC (or SC) |
Other Building type (daytime)
OPAQUE ASSEMBLY
| Roof MinimumInsulation R-value | |
|---|---|
| Wall MinimumInsulation R-value |
FENESTRATION
| Vertical | |
|---|---|
| Maximum U-factor | |
| Maximum SHGC (or SC) | |
| Overhang (yes or no) | |
| If yes, enter Projection Factor | |
| Side fins (yes or no) | |
| If yes, enter Projection Factor | |
| Skylight | |
| Maximum U-factor | |
| Maximum SHGC (or SC) |
Appendix F: PECBC Compliance Forms
15.2 Building Permit Plans Checklist
| Building Permit Plans ChecklistENVELOPE ChecklistThe Punjab Energy Conservation Building Code 2013 Compliance Forms | |||||||
| Project Address | Date | ||||||
| The following information is necessary to check a building permit application for compliance with the building envelope requirements in The Punjab Energy Conservation Building Code 2013. | |||||||
| Applicability(yes, no, n.a.) | Code Section | Component | Information Required | Location on Plans | Building Department Notes | ||
| MANDATORY PROVISIONS (Section 4.2) | |||||||
| 4.2.1 | Fenestration rating | ||||||
| 4.2.1.1 | U-factor | Specify whether per 4.2.1.1 or default in Appendix C | |||||
| 4.2.1.2 | SHGC | Specify whether per 4.2.1.2 or default in Appendix C | |||||
| 4.2.1.3 | Air leakage | Specify leakage rates | |||||
| 4.2.2 | Opaque U-factors | Specify whether per default in Appendix C or ASHRAE | |||||
| 4.2.3 | Bldg. envelope sealing | Indicate sealing, caulking, gasketing, and weather stripping | |||||
| PRESCRIPTIVE COMPLIANCE OPTION (Section 4.3) | |||||||
| 4.3.1 | Roof | Indicate R-values on roof sections | |||||
| 4.3.2 | Cool roof | Indicate minimum reflectance and emittance on plans | |||||
| 4.3.3 | Opaque walls | Indicate R-values on wall sections | |||||
| 4.3.4 | Vertical fenestration | (1) Indicate U-factors on fenestration schedule. Indicate if values are rated or default. If values are default, then specify frame type, glazing layers, gap width, low-e.(2) Indicate SHGC or SC on fenestration schedule. Indicate if values are rated or default. | |||||
| 4.3.5 | Skylights | (3) Indicate if overhangs or side fins are used for compliance purposes. If so, provide projection factor calculation.(1) Indicate U-factors on fenestration schedule. Indicate if values are rated or default. If values are default, then specify frame type, glazing layers, gap width, low-e.(2) Indicate SHGC or SC on fenestration schedule. Indicate if values are rated or default. | |||||
15.4 Mechanical Permit Checklist
| Mechanical Permit ChecklistMECHANICAL ChecklistThe Punjab Energy Conservation Building Code 2013 Compliance Forms | |||||
| Project Address: | Date: | ||||
| The following information is necessary to check a building permit application for compliance with the mechanical requirements in the Punjab Energy Conservation Building Code 2013. | |||||
| Applicability (yes, no, n.a.) | Code Section | Component | Information Required | Location on Plans | Building Dept. Notes |
| HEATING, VENTILATING, AND AIR CONDITIONING (Chapter 5) | |||||
| MANDATORY PROVISIONS (Section 5.2) | |||||
| 5.2.2 | Equipment efficiency | Provide equipment schedule with type, capacity, efficiency | |||
| 5.2.3 | Controls | ||||
| 5.2.3.1 | Timeclocks | Indicate thermostat with night setback, 3 different day types, and 2-hour manual override | |||
| 5.2.3.2 | Temp. & dead band | Indicate temperature control with 3°C deadband minimum | |||
| 5.2.3.3 | Cooling tower, fluid cooler | Indicate two-speed motor, pony motor, or variable speed drive to control the fans | |||
| 5.2.4.1 | Piping & ductwork | ||||
| 5.2.4.1 | Piping insulation | Indicate R-value of insulation | |||
| 5.2.4.1 | Ductwork insulation | Indicate R-value of insulation | |||
| 5.2.4.1 | Ductwork sealing | Specify sealing types and locations | |||
| 5.2.5 | System balancing | Specify system balancing | |||
| PRESCRIPTIVE COMPLIANCE OPTION (Section 5.3) | |||||
| 5.3 | Indicate whether project is complying with PECBC Prescriptive Option OR with ASHRAE Standard 90.1-2004 | ||||
| 5.3.1 | Economizer | ||||
| 5.3.1.1 | Air economizer | Indicate 100% capability on schedule | |||
| 5.3.1.2 | Integrated operation | Indicate capability for partial cooling | |||
| 5.3.1.3 | |||||
15.5 Lighting Summary
Appendix F: PECBC Compliance Forms
15.6 Lighting Permit Checklist
| Lighting Permit Checklist Lighting ChecklistThe Punjab Energy Conservation Building Code 2013 Compliance Forms | |||||
| Project Address Date: | |||||
| The following information is necessary to check a building permit application for compliance with the lighting requirements in the Punjab Energy Conservation Building Code 2013. | |||||
| Applicability (yes, no, n.a.) | Code Section | Component | Information Required | Location on Plans | Building Dept. Notes |
| LIGHTING (Chapter 7) | |||||
| MANDATORY PROVISIONS (Section 7.2) | |||||
| 7.2.1 | Lighting Controls | ||||
| 7.2.1.1 | Automatic shutoff | Indicate automatic shutoff locations or occupancy sensors | |||
| 7.2.1.2 | Space control | Provide schedule with type, indicate locations | |||
| 7.2.1.3 | Daylight zones | Provide schedule with type and features, indicate locations | |||
| 7.2.1.4 | Ext. lighting control | Indicate photosensor or astronomical time switch | |||
| 7.2.1.5 | Additional control | Provide schedule with type, indicate locations | |||
| 7.2.2 | Exit signs | Indicate 5 watts maximum | |||
| 7.2.3 | Exterior building grounds lighting | Indicate minimum efficacy of 60 lumens/Watt | |||
| PRESCRIPTIVE INTERIOR LIGHTING POWER COMPLIANCE OPTION (Section 7.3) | |||||
| 7.3 | Indicate whether project is complying with the Building Area Method (7.3.2) or the Space Function Method (7.3.3) | ||||
| 7.3.2 | Building area method | Provide lighting schedule with wattage of lamp and ballast and number of fixtures. Document all exceptions. | |||
| 7.3.3 | Space function method | Provide lighting schedule with wattage of lamp and ballast and number of fixtures. Document all exceptions. | |||
| 7.3.4.1 | Luminaire wattage | Indicate on plans | |||