Addition: an extension or increase in floor area or height of a building outside of the existing building envelope
Alteration: any change, rearrangement, replacement, or addition to a building or its systems and equipment; any modification in construction or building equipment
Annual fuel utilization efficiency (AFUE): an efficiency description of the ratio of annual output energy to annual input energy as developed in accordance with requirements of U.S.Department of Energy (DOE) 10CFR Part 430
Area: see roof and wall, conditioned floor, day lighted, façade, fenestration, lighted floor
Astronomical time switch: an automatic time switch that makes an adjustment for the length of the day as it varies over the year
Authority having jurisdiction: the agency or agent responsible for enforcing this standard
Automatic: self-acting, operating by its own mechanism when actuated by some non-manual influence, such as a change in current strength, pressure, temperature, or mechanical configuration.
Automatic control device: a device capable of automatically turning loads off and on without manual intervention
Balancing, air system: adjusting airflow rates through air distribution system devices, such as fans and diffusers, by manually adjusting the position of dampers, splitters vanes, extractors, etc., or by using automatic control devices, such as constant air volume or variable air volume boxes
Balancing, hydronic system: adjusting water flow rates through hydronic distribution system devices, such as pumps and coils, by manually adjusting the position valves, or by using automatic control devices, such as automatic flow control valves
Ballast: a device used in conjunction with an electric-discharge lamp to cause the lamp to start and operate under proper circuit conations of voltage, current, waveform, electrode heat, etc.
Boiler: a self- contained low-pressure appliance for supplying steam or hot water
Boiler, packaged: a boiler that is shipped complete with heating equipment mechanical draft equipment, and automatic controls; usually shipped in one or more sections. A packaged boiler includes factory-built boilers manufactured as a unit or system, disassembled for shipment, and reassembled at the site.
Building: a structure wholly or partially enclosed within exterior walls, or within exterior and party walls, and a roof, affording shelter to persons, animals, or property.
Building, existing: a building or portion thereof that was previously occupied or approved for occupancy by the authority having jurisdiction
Building complex: a group of buildings in a contiguous area under single ownership
Building entrance: any doorway set of doors, turnstiles, or other form of portal that is ordinarily used to gain access to the building by its users and occupants
Building envelope: the exterior plus the semi-exterior portions of a building. For the purposes of determining building envelope requirements, the classifications are defined as follows:
(a) Building envelope, exterior: the elements of a building that separate conditioned spaces from the exterior
(b) Building envelope, semi-exterior: the elements of a building that separate conditioned space from unconditioned space or that enclose semi-heated spaces through which thermal energy may be transferred to or from the exterior, or to or form unconditioned spaces, or to or form conditioned spaces
Building exit: any doorway, set of doors, or other form of portal that is ordinarily used only for emergency egress or convenience exit
Building grounds lighting: lighting provided through a building's electrical service for parking lot, site, roadway, pedestrian pathway, loading dock, and security applications
Building material: any element of the building envelope through which heat flows and that heat is included in the component U-factor calculations other than air films and insulation
Circuit breaker: a device designed to open and close a circuit by non-automatic means and to open the circuit automatically at a predetermined over-current without damage to itself when properly applied with its rating
Class of construction: for the building envelope, a subcategory of roof, wall, floor, slab-on-grade floor, opaque door, vertical fenestration, or skylight
Coefficient of performance (COP)-cooling: the ratio of the rate of heat removal to the rate of energy input, in consistent units, for a complete refrigerating system or some specific portion of that system under designated operating conditions
Coefficient of performance (COP)-heating: the ratio of the rate of heat delivered to the rate of energy input, in consistent units, for a complete heat pump system. Including the compressor and, if applicable, auxiliary heat, under designated operating conditions
Commercial building: all building except for multi-family buildings of three stories or fewer above grade and single-family buildings
Construction documents: drawings and specifications used to construct a building, building systems, or portions thereof
Control: to regulate the operation of equipment
Control device: a specialized device used to regulate the operation of equipment
Cool roof: a property of a surface that describes its ability to reflect and reject heat. Cool roof surfaces have both a light color (high solar reflectance) and a high emittance (can reject heat back to the environment)
Day lighted area: the daylight illuminated floor area under horizontal fenestration (skylight) or adjacent to vertical fenestration (window), described as follows
(a) Horizontal Fenestration: the under a skylight, monitor, or saw tooth configuration with an effective aperture greater than 0.001 (0.1%). The day lighted area is calculated as the horizontal dimension in each direction equal to the top aperture dimension in that direction plus either the floor-to-ceiling height (H) for skylights, or 1.5 H for monitors, or H or 2H for the saw tooth configuration, or the distance to the nearest 1000mm (42 in) or higher opaque partition, or one-half the distance to an adjacent skylight or vertical glazing, whichever is least, as shown in the plan and section figures below:

PLAN

SECTION

SECTION

SECTION
(d) Vertical Fenestration: the floor area to adjacent to side apertures (vertical fenestration in walls) with an effective aperture greater than 0.06 (6%). The day lighted area extends into the space perpendicular to the side aperture a distance either two times the head height of the side aperture or to the nearest 1.35m (54 in) or higher opaque partition, whichever is less. In the direction parallel to the window, the day lighted area extends a horizontal dimension equal to the width of the window plus either 1 m (3.3 ft) on each side of the aperture, the distance to an opaque partition, or one-half the distance to an adjacent skylight or window, whichever is least.

Dead band: the range of values within which a sensed variable can vary without initiating a change in the controlled process
Demand: the highest amount of power (average Btu/h over an interval) recorded for a building or facility in a selected time frame.
Design capacity: output capacity of a system or piece of equipment at design conditions
Design conditions: specified environmental conditions, such as temperature and light intensity, required to be produced and maintained by a system and under which the system must operate.
Distribution system: a device or group of devices or other means by which the conductors of a circuit can be disconnected from their source of supply.
Door: all operable opening areas ( which are not fenestration) in the building envelope, including swinging and roll-up doors, fire doors, and access hatches. Doors that are more than one- half glass are considered fenestration. For the purposes of determining building envelope requirements, the classifications are defined as follows:
(a) Door, non-swinging: roll-up sliding, and all other doors that are not swinging doors.
(b) Door, swinging: all operable opaque panels with hinges on one side and opaque revolving doors.
Door area: total area of the door measured using the rough opening and including the door slab and the frame.
Dwelling unit: a single unit providing complete independent living facilities for one or more persons, including permanent provisions for living, sleeping, eating, coking, and sanitation.
Economizer, air: a duct and damper arrangement and automatic control system that together allow a cooling system to supply outdoor air to reduce or eliminate the need for mechanical cooling during mild or cold weather.
Economizer, water: a system by which the supply air of a cooling system is cooled indirectly with water that is itself cooled by heat or mass transfer to the environment without the use of mechanical cooling
Effective aperture: visible light Transmittance x window-to-wall Ratio. (EA=VLT X WWR)
Effective aperture, horizontal fenestration: a measure of the amount of daylight that enters a space through horizontal fenestration (skylights). It is the ratio of the skylight area times the visible light transmission divided by the gross roof area above the day lighted area. See also day lighted area.
Effective aperture, vertical fenestration: a measure of the amount of daylight that enters a space through vertical fenestration. It is the ratio of the daylight window area times its visible light transmission plus half the vision glass area times its visible light transmission and the sum is divided by the gross wall area. Day lighted window area is located 202 m (7 ft) or more above the floor and vision window area is located above 1 m (3 ft) but below 2.2 m (7 ft). The window area, for the purposes of determining effective aperture shall not include windows located in light wells when the angle of obstruction (a) of objects obscuring the sky dome is greater than 70º, measured from the horizontal, nor shall it include window area located below a height of 1 m (3 ft). See also day lighted area.

Efficacy: the lumens produced by a lamp/ballast system divided by the total watts of input power (including the ballast), expressed in lumens per watt
Efficiency: performance at a specified rating condition
Remittance: the ratio of the radiant heat flux emitted by a specimen to that emitted by blackbody at the same temperature and under the same condition.
Enclosed building: a building that is totally enclosed by walls, floors, and openable devices such as doors and operable windows.
Energy: the capacity for doing work. It takes a number of forms that may be transformed form one into another such as thermal (heat), mechanical (work) electrical, and chemical. Customary measurements are watts (W)
Energy Efficiency Ratio (EER): the ratio of net cooling capacity in Btu/h to total rate of electric input in watts under designated operating conditions
Energy Factor (EF): a measure of water heater overall efficiency
Envelope performance factor: the trade-off value for the building envelope performance compliance option calculated using the procedures specified in Appendix D 12. For the purposes of determining building envelope requirements the classifications are defined as follows:
(a) Base envelope performance factor: the building envelope performance factor for the base design
(b) Proposed envelope performance factor: the building envelope performance factor for the proposed design
Equipment: devices for comfort conditioned, electric power, lighting, transportation, or service water heating including, but not limited to, furnaces, boilers, air conditioners, heat pumps, chillers, water heaters, lamps, luminaries, ballasts, elevators, escalators, or other devices or installations
Equipment, existing: equipment previously installed in an existing building
Façade area: area of the façade, including overhanging soffits, cornices, and protruding columns, measured in elevation in a vertical plane, parallel to the plane of the face of the building. Non-horizontal roof surfaces shall be included in the calculations of vertical façade area by measuring the area in a plane parallel to the surface.
Fan system power: the sum of the nominal power demand (nameplate W or HP) of motors of all fans that are required to operate at design conditions to supply air from the heating or cooling source to the conditioned space(s) and return it to the source of exhaust it to the outdoors.
Fenestration: all areas (including the frames) in the building envelope that let in light, including windows, plastic panels, clerestories, skylights, glass doors that are more than one-half glass, and glass block walls.
a) Skylight: a fenestration surface having a slope of less than 60 degrees from the horizontal plane. Other fenestration, even if mounted on the roof of a building, is considered vertical fenestration.
b) Vertical fenestration: all fenestration other than skylights. Trombe wall assemblies, where glazing is installed within 300mm (12 in) of a mass wall, are considered walls, not fenestration.
Fenestration area: total area of the fenestration measured using the rough opening and including the glazing, sash, and frame. For doors where the glazed vision area is less than 50% of the door area, the fenestration area is the glazed vision area. For all other doors, the fenestration area is the door area.
Floor area gross: the sum of the floor areas of the spaces within the building including basements, mezzanine and intermediate-floored tiers, and penthouses with headroom height of 2.5 m (7.5 ft) or greater. It is measured from the exterior faces of exterior walls or from the centerline of walls separating buildings, but excluding covered walkways, open roofed-over areas, porches and similar spaces, pipe trenches, exterior terraces or steps, chimneys, roof overhangs, and similar features.
(a) Gross building envelope floor area: the gross floor area of the building envelope, but excluding slab-on grade floors.
(b) Gross conditioned floor area: the gross floor area of conditioned spaces.
(c) Gross lighted floor area: the gross floor area of lighted spaces.
(d) Gross semi heated floor area: the gross floor area of semi heated spaces.
Flue damper: a device in the flue outlet or in the inlet of or upstream of the draft control device of an individual, automatically operated, fossil fuel-fired appliance that is designed to automatically open the flue outlet during appliance operation and to automatically close the flue outlet when then appliance is in standby condition.
Fossil fuel: fuel derived from a hydrocarbon deposit such as petroleum, coal, or natural gas derived from living matter of a previous geologic time.
Fuel: a material that may be used to produce heat or generate power by combustion.
Generally accepted engineer standard: a specification, rule, guide, or procedure in the field of engineering or related thereto, recognized and accepted as authoritative.
Grade: the finished ground level adjoining building at all exterior walls.
Guest room: any room or rooms used or intended to be used by a guest for sleeping purposes.
Heat capacity: the amount of heat necessary to raise the temperature of a given mass 1°C (1°F). Numerically, the heat capacity per unit area of surface (W/m²-ºC [Btu/ft²-°F]) is the sum of the products of the mass per unit area of each individual material in the roof, wall, or floor surface multiplied by its individual specific heat.
Heating Seasonal Performance Factor (HSPF): the total heating output of a heat pump during its normal annual usage period for heating (in Btu) divided by the total electric energy input during the same period.
Historic: a building or space that has been specifically designed as historically significant.
HVAC system: the equipment, distribution systems, and terminals that provide, either collectively or individually, the processes of heating, ventilating, or air conditioned to a building or portion of a building.
Infiltration: the uncontrolled inward air leakage through cracks and crevices in any building element and around windows and doors of a building caused by pressure differences across these elements due to factors such as wind, inside and outside temperature differences (stack effect), and imbalance between supply and exhaust air systems.
Installed interior lighting power: the power in watts of all permanently installed general, task, and furniture lighting systems and luminaires.
Integrated part-load value (IPLV): a single number figure of merit based on partload EER, COP, or kW/ton expressing part-load efficiency for air-conditioning and heat pump equipment on the basis of weighted operation at various load capacities for the equipment.
Kilovolt-ampere: where the term “kilovolt-ampere” (kVA) is used in this Code, it is the product of the line current (amperes) times the nominal system voltage (kilovolts) times 1.732 for three-phase currents. For single-phase applications, kVA is the product of the line current (amperes) times the nominal system voltage (kilovolts).
Kilowatt: the basic unit of electric power, equal to 1000 W.
Labeled: equipment or materials to which a symbol or other identifying mark has been attached by the manufacturer indicating compliance with specified standard or performance in a specified manner.
Lamp: a generic term for man-made light source often called bulb or tube.
Lighted floor area, gross: the gross floor area of lighted spaces.
Lighting, decorative: lighting that is purely ornamental and installed for aesthetic effect. Decorative lighting shall not include general lighting.
Lighting, emergency: lighting that provides illumination only when there is a general lighting failure.
Lighting, general: lighting that provides a substantially uniform level of illumination throughout an area. General lighting shall not include decorative lighting or lighting that provides a dissimilar level of illumination to serve a specialized application or feature within such area.
Lighting Efficacy (LE): the quotient of the total lumens emitted from a lamp or lamp/ballast combination divided by the watts of input power, expressed in lumens per watt.
Lighting system: a group of luminaires circuited or controlled to perform a specific function.