7.2.1 Lighting Control
7.2.1.1 Automatic Lighting Shutoff
2 2Interior lighting systems in buildings larger than 500m (5,000 ft ) shall be equipped with an automatic control device. Within these buildings, all office 2 2areas less than 30 m (300ft )enclosed by walls or ceiling-height partitions, all meeting and conference rooms, all school classrooms, and all storage spaces shall be equipped with occupancy sensors. For other spaces, this automatic control device shall function on either:
(a) Ascheduled basis at specific programmed times. An independent program 2 2schedule shall be provided for areas of no more than 2500 m (25000 ft ) and not more than one floor; or,
(b) Occupancy sensors that shall turn the lighting off within 10 minutes of an occupant leaving the space. Light fixtures controlled by occupancy sensors shall have a wall-mounted, manual switch capable of turning off lights when the space is occupied.
Exception to clause 7.2.1.1: Lighting systems designed for 24 hour use.
Lighting
7.2.1.2 Space Control
Each space enclosed by ceiling-height partitions shall have at least one control device to independently control the general lighting within the space. Each control device shall be activated either manually by an occupant or automatically by sensing an occupant. Each control device shall:
(a) Control a maximum of 2 5 0 m 2 2(2500 ft ) for a space less than or equal to 2 2 21000 m (10000 ft ), and a maximum of 1000 m (10000 ft2) for a space 2 2greater than 1000 m (10000 ft )
(b) Be capable of overriding the shutoff control required in clause 7.2.1.1 for no more than 2 hours.
(c) Be readily accessible and located so the occupant can see the control.
Exception to clause 7.2.1.2 (c): The required control device may be remotely installed if required for reasons of safety or security. A remotely located device shall have a pilot light indicator as part of or next to the control device and shall be clearly labeled to identify the controlled lighting.
7.2.1.3: Control in Day lighted areas
2 2Luminaries in day lighted areas greater than 25m (250 ft ) shall be equipped with either a manual or automatic control device that:
(a) Is capable of reducing the light output of the luminaries in the day lighted areas by at least 50%, and
(b) Controls only the luminaries located entirely within the day lighted area.
7.2.1.4: Exterior Lighting Control
Lighting for all exterior applications not exempted in clause 7.3.4 shall be controlled by a photo sensor or astronomical time switch that is capable of automatically turning off the exterior lighting when daylight is available or the lighting is not required.
7.2.1.5 Additional control
The following lighting applications shall be equipped with a control device to control such lighting independently of general lighting:
2a) Display/Accent Lighting: Display or accent lighting greater than 300m 2(3000 ft ) area shall have a separate control device
b) Case Lighting: Lighting in cases used for display purposes greater than 2 2300m (3000 ft ) area shall be equipped with a separate control device.
c) Hotel and Motel Guest Room Lighting: Hotel and motel guest rooms and guest suites shall have a master control device at the main room entry that-
Lighting
controls all permanently installed luminaries and switched receptacles.
(d) Task Lighting: Supplemental task lighting including permanently installed under shelf or under cabinet lighting shall have a control device integral to the luminaries or be controlled by a wall-mounted control device provided the control device compiles with clause 7.2.1.2 ( c)
(e) Non-visual Lighting: Lighting for non-visual applications, such as plant growth and food-warming, shall be equipped with a separate control device.
(f) Demonstration Lighting: Lighting equipment that is for sale or for demonstrations in lighting education shall be equipped with a separate control device accessible only to authorized personnel.