6.1General
All service water heating equipment and systems shall comply with the mandatory provisions of clause 6.2.
6.2 Mandatory Requirements
6.2.1 Solar Water Heating
Residential facilities, hotels and hospitals with a centralized system shall have solar water heating for at least 1/5 of the design capacity.
Exception to clause 6.2.1: Systems that use heat recovery for at least 1/5 of the design capacity.
6.2.2 Equipment Efficiency
Service water heating equipment shall meet or exceed the performance and minimum efficiency requirements presented in available Indian Standards.
(a) Solar water heater shall meet the performance/minimum efficiency level mentioned in IS 13129 Part (1&2)
(b) Gas Instantaneous Water heaters shall meet the performance/minimum efficiency level mentioned in IS 15558 with above 80% thermal efficiency.
(c) Electric water heater shall meet the performance/minimum efficiency level mentioned in IS 2082. All heating equipments shall comply with the provisions of clause 3.1.4.6.
6.2.3 Supplementary Water Heating System
Supplementary heating system shall be designed to maximize the energy efficiency of the system and shall incorporate the following design features in cascade:
(a) Maximum heat recovery from hot discharge system like condensers of air conditioning units
(b) Use of gas fired heaters wherever gas is available
(c) Electric heater as last resort
6.2.4 Piping Insulation
Piping insulation shall comply with clause 5.2.4.1. The entire hot water system including the storage tanks, pipelines shall be insulated conforming to the relevant 15 standards on material and applications.
Service Hot Water and Pumping
6.2.5 Heat Traps
Vertical pipe risers serving storage water heaters and storage tanks not having integral heat traps and serving a non-recirculating system shall have heat traps on both the inlet and outlet piping as close as practical to the storage tank.
6.2.6 Swimming Pools
Heated pools shall be provided with a vapor retardant pool cover on or at the water surface. Pools heated to more than 3 2 ° C ( 9 0 ° F ) shall have a pool cover with a minimum insulation value of R-2.1 (R-12)
Exception to clause 6.2.6: Pools deriving over 60% of their energy from siterecovered energy or solar energy source.
6.2.7 Compliance Documentation
The application for approval shall furnish detailed calculation showing the design to ensure that at least 20% of the heating requirement shall be met from solar heat/heat recovery and not more than 80% of the heat shall be met from electrical heating. Wherever gas is available, not more than 20% of the heat shall be met from electrical heating.