10.2.1 Energy Simulation Program
The simulation program shall be a computer based program for the analysis of energy consumption in buildings and be approved by the authority having jurisdiction. The simulation program shall model the following:
a) Energy flows on an hourly basis for all 8,760 hours in the year.
b) Hourly variations in occupancy, lighting power, miscellaneous equipment power, thermostat set points, and HVAC system operation, defined separately for each day of the week and holidays,
c) Thermal mass effects,
d) Ten or more thermal zones,
e) Part load and temperature dependent performance of heating and cooling equipment,
f) Air side and water side economizers with integrated control, and
g) All of the standard design characteristics specified in this chapter.
10.2.2 Climatic Data
The simulation program shall use hourly values of climatic data, such as temperature and humidity from representative climatic data, for the city in which the proposed design is to be located. For cities or urban regions with several climatic data entries, and for locations where weather data are not available, the designer shall select available weather data that best represent the climate at the construction site.
10.2.3 Compliance Calculations
The proposed design and standard design shall be calculated using the following:
a) Same simulation program,
b) Same weather data,
Appendix B: Whole Building Performance Method
c) Same building operation assumptions (thermostat set points, schedules, internal gains, occupant loads, etc.)
10.3 Calculating the Energy Consumption of the Proposed Design and the Standard Design
10.3.1 The simulation model for calculating the proposed design and the standard design shall be developed in accordance with the requirements in Table 10.1
10.3.2 HVAC Systems
The HVAC System type and related performance parameters for the standard design shall be determined from table 10.1 and the following rules:
a) Other Components: Components and parameters not listed in Table 10.2 or otherwise specifically addresses in this subsection shall be identical to those in the proposed design.(Exception to clause 10.3.2(a) where there are specific requirements in clause 5.2.2., the component efficiency in the standard design shall be adjusted to the lowest efficiency level allowed by the requirement for that component type).
b) All HVAC and service water heating equipment in the standard design shall be modeled at the minimum efficiency levels, both part load and full load, in accordance with clause 5.2.2.
c) Where efficiency ratings, such as EER and COP, include fan energy, the descriptor shall be broken down into its components so that supply fan energy can be modeled separately.
d) Minimum outdoor air ventilation rates shall be the same for both the standard and the proposed design.
e) The equipment capacities for the standard design shall be sized proportionally to the capacities in the proposed design based on sizing runs; i.e. the ratio between the capacities used in the annual simulations and the capacities determined by the sizing runs shall be the same for both the proposed design and the standard design. Unmet load shall be the same for both the proposed design and standard design shall not differ from unmet load hours for the standard design by more than 50 hours. The maximum number of unmet hours shall not exceed 300 for either case.
Appendix B: Whole Building Performance Method
| Case | Proposed Building | Standard Design |
|---|---|---|
| Design Model | (A) The simulation model of the Proposed Design shall be consistent with the design documents, including proper accounting of fenestration and opaque envelope types and area; interior lighting power and controls; HVAC system types, sizes, and controls; and service water heating systems and controls. (B) When the whole building performance method is applied to buildings in which energy related features have not yet been designed (e.g., a lighting system), those yet-to-be designed features shall be described in the Proposed Design so that they minimally comply with applicable mandatory and prescriptive requirements from clause4 through clause8. | The Standard Designs shall be developed by modifying the Proposed Design as described in this table. Except as specifically instructed in this table, all building systems and equipment shall be modeled identically in theStandard Designs and Proposed Design. |
| Space Use Classification | The building type or space type classifications shall be chosen in accordance with clause7.3.2 or clause7.3.3. More than one building type category may be used in a building if it is a mixed-use facility | Same as Proposed Design |
| Schedules | The schedules shall be typical of the proposed building type as determined by the designer and approved by the authority having jurisdiction. | Same as Proposed Design. |
| Building Envelope | All components of the building envelope in the proposed design shall be modeled as shown on architectural drawings or as installed for existing building envelopes. Exceptions: The following building elements are permitted to differ from architectural drawings. (A) Any envelope assembly that covers less than 5% of the total area of that assembly type (e.g.,exterior walls) need not be separately described. If not separately described, the area of an envelope assembly must be added to the area of the adjacent assembly of that same type. (B) Exterior surfaces whose azimuth orientation and tilt differ by no more than 45 degrees and are otherwise the same may be described as either a single surface or by using multipliers. | The standard design shall have identical conditioned floor area and identical exterior dimensions and orientations as the proposed design, except as noted in (a), (b), (c), and (d) below. (A) Orientation. The baseline building performance shall be generated by simulating the building with its actual orientation and again after rotation the entire building 90, 1 8 0 , 2 7 0 d e g re e s , t h e n averaging the results. The building shall be modeled so that it does not shade itself. |
Appendix B: Whole Building Performance Method
| (C) For exterior roofs other than roofs with ventilated attics, the reflectance and emittance of the roof surface shall be modeled. The reflectance and emittance shall be tested in accordance with 4.3.1.1 (D) Manually operated fenestration shading devices such as blinds or shades shall not be modeled. Permanent shading devices such as fins, overhangs, and light shelves shall be modeled. | (B) Opaque assemblies such as, floors, doors, and walls shall be modeled as having the same heat capacity as the proposed design but with the minimum u-factor required in 4.3.1 and 4.3.2. (C) Fenestration- fenestration areas shall equal that in the proposed design or 40% of gross above grade wall area, whichever is smaller, and shall be distributed uniformly in horizontal bands across the four orientations. No shading projections are to be modeled; fenestration shall be assumed to be flush with the exterior wall or roof. Manually operated fenestration shading devices such as blinds or shades s h a l l n o t b e m o d e l e d . Fenestration U-factor shall be the minimum required for the climate, and the solar heat gain coefficient shall be the maximum allowed for the climate and orientation. (D) Roof albedo. All roof surfaces shall be modeled with a reflectivity of 0.30 | |
|---|---|---|
| Lighting | Lighting power in the Proposed Design shall be determined as follows: (A) Where a complete lighting system exists, the actual lighting power shall be used in the model. (B) Where a lighting system has been designed, the LPD should match the design which shall be determined in accordance with either clause7.3.2 or clause7.3.3. © Where no lighting exists or is specified, lighting power shall be determined in accordance with the clause7.3.2 for the appropriate building type. (D) Lighting system power shall include all lighting system components shown or provided for on plans (including lamps, ballasts, task fixtures, and furniture-mounted fixtures). | Lighting power in the Standard Designs shall be determined using the same categorization procedure (building area or space function) and categories as the Proposed Design with lighting power set equal to the m a x i m u m a l l o w e d fo r t h e corresponding method and category in either clause7.3.2 or clause7.3.3. Power for fixtures not included in the lighting power density calculation shall be modeled identically in the Proposed and Standard Design. Lighting controls shall be the minimum required. |
Appendix B: Whole Building Performance Method
| HVAC Systems | The HVAC system type and all related performance parameters, such as equipment capacities and efficiencies, in the Proposed Design shall be determined as follows: (A) Where a complete HVAC system exists, the model shall reflect the actual system type using actual component capacities and efficiencies. (B) Where an HVAC system has been designed, the HVAC model shall be consistent with design documents. Mechanical equipment efficiencies shall be adjusted from actual design conditions to the standard rating conditions specified in clause5, if required by the simulation model. (C) Where no heating system exists or no heating system has been specified, the heating system shall be modeled as electric resistance. The system characteristics shall be identical to the system modeled in the Standard Designs. (D) Where no cooling system exists or no cooling system has been specified, the cooling system shall be modeled as an air-cooled single-zone system, one unit per thermal zone. The system characteristics shall be identical to the system modeled in the Standard Designs. | The HVAC system type and related performance parameters for the Standard Designs shall be determ i ned from Table 10.2. Equipment performance shall meet the requirements of clause 5. |
|---|---|---|
| Service Hot Water | The service hot water system type and all related performance parameters, such as equipment capacities and efficiencies, in the Proposed Design shall be determined as follows: (A) Where a complete service hot water system exists, the Proposed Design shall reflect the actual system type using actual component capacities and efficiencies. (B) Where a service hot water system has been specified, the service hot water model shall be consistent with design documents. ( C) Where no service hot water system exists or has been specified but the building will have service hot water loads, a service hot water system shall be modeled. | The water heating system shall be of the same type of the Proposed Design. For residential facilities, hotels and hospitals the Standard Designs shall have a solar system capable of meeting 20% of the design load. Systems shall meet the e ffi c i e n c y re q u i re m e n t s o f clause6.2.2, the pipe insulation requirements of clause6.2.4 and incorporate heat traps in accordance with clause6.2.5. |
| Miscellaneous Loads | Receptacle, motor, and process loads shall be modeled and estimated based on the building type or space type category. These loads shall be included in simulations of the building and shall be included when calculating the standard design and proposed design. All end-use load components within and associated with the building shall be modeled, unless specifically excluded, | Receptacle, motor and process loads shall be modeled the same as the Proposed Design. The water heating system shall be of the same type of the proposed design. |
Appendix B: Whole Building Performance Method
| but not limited to, exhaust fans, parking garage ventilation fans, exterior building lighting, swimming pool heaters and pumps, elevators and escalators, refrigeration equipment, and cooking equipment. | ||
|---|---|---|
| Modeling Limitations to the Simulation Program | If the simulation program cannot model a component or system included in the Proposed Design, one of the following methods shall be used with the approval of the Authority Having Jurisdiction: (A) Ignore the component if the energy impact on the trade-offs being considered is not significant. (B) Model the component substituting a thermodynamically similar component model. (C) Model the HVAC system components or systems using the Standard Designs's HVAC system in accordance with clause5. Whichever method is selected, the component shall be modeled identically for both the Proposed Design and Standard Designs models. | Same as proposed design. |
| Nonresidential | ||||
| Residential More than 3 stories | Less than 3 floors or less than 7,500 m² | 4 or 5 floors or less than 7,500 m² or less and 7,500- 15,000 m² | More than 5 floors or more than 15,000 m | |
| Code | PTAC | PSZ | RHFS | RHFS |
| System type | Packaged terminal air conditioner | Packaged rooftop air conditioner | Central cooling plant with constant volume AHU for each zone | Central cooling plant with variable air volume AHU for each zone |
| Fan control | Constant Volume | Constant Volume | Constant Volume air handler for each zone | Variable volume air handler |
| Cooling type | Direct expansion | Direct expansion | Chilled Water* | Chilled Water* |
| Heating type | Electric resistance | Electric resistance | Electric resistance | Electric resistance |
If the proposed building has an air cooled chiller/system then the budget building shall have air cooled chiller otherwise the budget case shall have water cooled centrifugal chillers. If the building has a mix of air and water cooled chillers then, the baseline building shall have the mix of air and water cooled chillers in the same proportion. Chiller Efficiencies shall be as per Table 5.1