i. In basement, there shall be two staircases preferably in opposite directions as per the provisions of the fire safety rules and the National Building Code as amended from time to time.
ii. The setback area can be sunk for light& ventilation (upto 4’-6” deep from plinth and 6’-0” wide), provided fire tender movement is not hindered.
iii. The height of all rooms for human habitation shall not be less than 2.75 m measured from the surface of the floor to the lowest point of the ceiling (bottom of slab) provided that the minimum clear headway under any beam shall not be less than 2.4 m. In the case of pitched roof, the average height of rooms shall not be less than 2.75 m. The minimum clear head room under a beam, folded plates or eaves shall be 2.4 m.
iv. No portion of a room shall be assumed to be lighted, if it is more than 7.5 metres or as stated in National Building Code, away from the opening provided for lighting that portion.
v. Where the lighting and ventilation requirements are not met through day lighting and natural ventilation, the same shall be ensured through artificial lighting and mechanical ventilation as per Part VIII Building Services Section I Lighting and ventilation of National Building Code of India published by the Bureau of Indian Standards.
vi. No room containing water-closet shall be used for any other purposes except as lavatory and no such room shall open directly into any kitchen or cooking space by a door/ window or another opening.
vii. Soil or ventilating pipes shall not be allowed on the exterior face of any building, provided these shall either be embedded in the walls or pipe ducts to be provided to accommodate them.
viii. A Staircase shall not be arranged around a lift shaft.
ix. All staircase and walls enclosing the staircases in public buildings and warehouse and industrial buildings shall be of fire-proof materials and flooring shall be antiskid.
x. The staircases in private portions of public buildings/ commercial buildings or warehouse and industrial buildings, not open to general public may be of width 1.0m (3’-3”).
xi. All the passages and corridors shall be naturally lighted and ventilated and if not possible, provision for artificial lighting and mechanical ventilation shall be made.
xii. The minimum clear height of a basement storey shall be 2.40 metres(8’-0”) and maximum height of the basement storey shall be up to 3.66 metres(12’) from floor to ceiling. However, in case of the services such as Printing Press, lifts, A.C. Plants, Electrical Panels, Filtration Plants, Laundry Plants or Machines relating with the services relating to the use of the site and provision of automated/stack parking related with the services relating to the use of the site, the clear height up to 16’-6” shall be allowed subject to the condition that no mezzanine floor shall be permitted after ensuring the structural stability and provision of the Fire Safety Rules.