14.1 Construction Inspection:
Prior to performance testing verify and document the following:
System controls are wired correctly to ensure economizer is fully integrated (i.e. economizer will operate when mechanical cooling is enabled.)
Economizer lockout control sensor location is adequate (open to air but not exposed to direct sunlight nor in an enclosure; away from sources of building exhaust; at least 8m [25ft] away from cooling towers).
System is provided with barometric relief, relief fan or return fan to control building pressure.
14.2 Equipment Testing:
Step 1: Simulate a cooling load and enable the economizer by adjusting the lockout control setpoint. Verify and document the following:
Economizer damper modulates opens to 100% outside air.
Return air damper modulates closed and is completely closed when economizer damper is 100% open.
Economizer damper is 100% open before mechanical cooling is enabled.
Relief fan or return fan (if applicable) is operating or barometric relief dampers freely swing open.
Step 2: Continue from Step 1 and disable the economizer by adjusting the lockout control setpoint. Verify and document the following:
Economizer damper closes to minimum ventilation position.
Return air damper opens to at or near 100%
Relief fan (if applicable) shuts off or barometric relief dampers close. Return fan (if applicable) may still operate even when economizer is disabled.