Lighting systems and equipment shall comply with the mandatory provisions of clause 7.2 and the prescriptive criteria of clause 7.3 and clause 7.3.4. The lighting requirements in this section shall apply to:
(a) Interior spaces of buildings;
(b) Exterior building features, including facades, illuminated roofs, architectural features, entrances, exits, loading docks, and illuminated canopies; and
(c) Exterior building grounds lighting that is provided through the building’s electrical service:
Exception to 7.1:
(a) Emergency lighting that is automatically off during normal building operation and is powered by battery, generator, or other alternate power source
(b) Lighting in dwelling units.
7.3Prescriptive Requirements:
7.3.1 Interior Lighting Power:
The installed interior lighting power for a building or a separately metered or permitted portion of a building shall be calculated in accordance with clause 7.3.4 and shall not exceed the interior lighting power allowance determined in accordance with either clause 7.3.2 or clause 7.3.3. Tradeoffs of interior lighting power allowance among portions of the building for which a different method of calculation has been used are not permitted:
Exception for 7.2.2.1: The following lighting equipment and application shall not be considered when determining the interior lighting power allowance, nor shall the wattage for such lighting be included in the installed interior lighting power. However, any such lighting shall not be exempt unless it is an addition to general lighting and is controlled by an independent control device,-
(a) Display or accent lighting that is an essential element for the function performed in galleries, museums, and monuments;
(b) Lighting that is integral to equipment or instrumentation and is installed by its manufacturer;
(c) Lighting specifically designed for medical or dental procedures and lighting integral to medical equipment;
(d) Lighting integral to food warming and food preparation equipment;
(e) Lighting for plant growth or maintenance;
(f) Lighting in spaces specifically designed for use by the visually impaired;
(g) Lighting in retail display windows, provided the display area is enclosed by ceiling-height partitions;
(h) Lighting in interior spaces that have been specifically designated as a
registered interior historic landmark;
(i) Lighting that is an integral part of advertising or directional signage
(j) Exit signs;
(k) Lighting that is for sale or lighting educational demonstration systems;
(l) Lighting for theatrical purposes, including performance, stage, and film or video production
(m) Athletic playing areas with permanent facilities for television broadcasting.
7.3.2 Building Area Method:
Determination of interior lighting power allowance (watts) by the building area method shall be in accordance with the following:
(a) Determine the allowed lighting power density from Table 7.1 for each appropriate building area type;
(b) Calculate the gross lighted floor area for each building area type; and
(c) The interior lighting power allowance is the sum of the products of the gross lighted floor area of each building area times the allowed lighting power density for that building area types.
Table 7-1Interior Lighting Power-Building Area Method
Building Area Type
LPD(W/m2)
Building Area Type
LPD(W/m2)
Automotive Facility
9.7
Multifamily Residential
7.5
Convention Center
12.9
Museum
11.8
Dining : Bar Lounge/Leisure
14.0
Office
10.8
Dinning: Cafeteria/Fast Food
15.1
Parking Garage
3.2
Dinning : Family
17.2
Performing Arts Theater
17.2
Dormitory./Hostel
10.8
Police/Fire Station
10.8
Gymnasium
11.8
Post Office/Town Hall/
11.8
Healthcare – clinic
10.8
Religious Building
14.0
Hospital/Health Care
12.9
Retail/Mall
16.1
Hotel
10.8
School/University
12.9
Library
14.0
Sports Arena
11.8
Manufacturing Facility
14.0
Transportation
10.8
Motel
10.8
Warehouse
8.6
Motion Picture Theater
12.9
Workshop
15.1
In cases where both a general building area type and a specific building area type are listed, the specific building area type shall apply.
7.3.3 Space Function Method:
Determination of interior lighting power allowance (watts) by the space function method shall be in accordance with the following:
(a) Determine the appropriate building type from Table 7.2 and the allowed lighting power density;
(b) For each space enclosed by partitions 80% or greater than ceiling height, determine the gross interior floor area by measuring to the center of the partition wall. Include the floor area of balconies or other projections Retail spaces do not have to comply with the 80% partition height requirements; and
(c) The interior lighting power allowance is the sum of the lighting power allowances for all spaces. The lighting power allowance for a space is the product of the gross lighted floor area of the space times the allowed lighting power density for that space.
Table 7-2Interior Lighting Power-Space Function Method
Space Function
LPD (W/m2)
Space Function
LPD (W/m2)
Office – Enclosed
11.8
For Reading Area
12.9
Office –Open plan
11.8
Hospital
Conference/meeting/multipurpose
14.0
For Emergency
29.1
Classroom/lecture/training
15.1
For Recovery
8.6
Lobby *
14.0
For Nurse Station
10.8
For Hotel
11.8
For Exam Treatment
16.1
For Performing Arts Theater
35.5
For Pharmacy
12.9
For Motion Picture Theater
11.8
For Patient Room
7.5
Audience/Seating Area *
9.7
For Operating Room
23.5
For Gymnasium
4.3
For Nursery
6.5
For Convention Center
7.5
For Medical Supply
15.1
For Religious Building
18.3
For Physical Therapy
9.7
For Sports Arena
4.3
For Radiology
4.3
For Performing aRts Theater
28.0
For Laundry- Washing
6.5
For Motion Picture Theater
12.9
Automotive – Service Repair
7.5
For Transportation
5.4
7.3.4 Installed Interior Lighting Power:
The installed interior lighting power calculated for compliance with clause 7.3 shall include all power used by the luminaries, including lamps, ballasts, current regulators, and control devices except as specifically exempted in clause 7.1:
Exception to clause 7.3.4: If two or more independently operating lighting systems in a space are controlled to prevent simultaneous user operation, the installed interior lighting power shall be based solely on the lighting system with the highest power.
7.3.4.1 Luminaire Wattage:
Luminaire wattage incorporated into the installed interior lighting power shall be determined in accordance with the following,-
(a) The wattage of incandescent luminaries with medium base sockets and not containing permanently installed ballasts shall be the maximum labeled wattage of the luminaries;
(b) The wattage of luminaires containing permanently installed ballasts shall be the operating input wattage of the specified lamp/ ballast combination based on values from manufacturers’ catalogs or values from independent testing laboratory reports;
(c) The wattage of all other miscellaneous luminaire types not described in (a) or (b) shall be the specified wattage of the luminaires; and
(d) The wattage of lighting track, plug-in bus way, and flexible lighting systems that allow the addition and/ or relocation of luminaries without altering the wiring of the system shall be the larger of the specified wattage of the luminaires included in the system or 135 W/m (45W/ft). Systems with integral overload protection such as fuses or circuit breakers shall be rated at 100% of the maximum rated load of the limiting device.
7.3.5 Exterior Lighting Power:
For building exterior lighting applications specified in Table 7.3 the connected lighting power shall not exceed the specified lighting power limits specified for each of these applications. Trade- off between applications is not permitted. Exterior lighting for all other applications (except those included in the Exception to clause 7.3.4) shall comply with the requirements of clause 7.2.3:
Table 7-3Interior Lighting Power-Space Function Method
Exterior Lighting Applications
Power Limits
Building entrance (with canopy)
13 W/m2(1.3W/ft2) of canopied area
Building entrance (without canopy)
90 W/lin m (30 W/lin f) of door width
Building exit
60 W/lin m (20 W/lin f) of door width
Building facades
2 W/m2(0.2W/ft2)of vertical façade area
Exception to clause 7.3.5: Lighting used for the following exterior application is exempt when equipped with an independent control device,-
(a) Specialized signal, directional, and marker lighting associated with transportation;
(b) Lighting used to highlight features of public monuments and registered historic landmark structures or buildings; and
(c) Lighting that is specifically designated as required by health or life safety statute, ordinance, or regulation.
7.2Mandatory Requirements:
7.2.1 Lighting Control:
7.2.1.1 Automatic Lighting Shutoff:
Interior lighting systems in buildings larger than 2 5 0 m 2 ( 2 , 5 0 0 f t 2 ) shall be equipped with an automatic control device. Within these buildings, all office areas less than 30m² ( 300ft² ) enclosed by walls or ceiling-height partitions, all
meeting and conference rooms, all toilets, all school classrooms, and all storage spaces shall be equipped with occupancy sensors. For others spaces, this automatic control device shall function on either,-
(a) A scheduled basis at specific programmed times. An independent program schedule shall be provided for areas of no more than 2 , 5 0 0 m 2 (25,000ft2) and not more than one floor; or
(b) Occupancy sensors that shall turn the lighting off within 30 minutes of an occupant leaving the space. Light fixtures controlled by occupancy sensors shall have a wall- mounted, manual switch capable of turning on lights when the space is occupied:
Exception to clause 7.2.1.1: Lighting system is designed for 24 hour use.
7.2.1.2 Space control:
Each space enclosed by ceiling- height partitions shall have at least one control device to independently control the general lighting within the space. Each control device shall be activated either manually by an occupant or automatically by sensing an occupant. Each control device shall,-
(a) Control a maximum of 250 m² ( 2, 500 ft² ) for a space less than or equal to 1 , 0 0 0 m 2 ( 1 0 , 0 0 0 f t 2 ) , and a maximum of 1,000 ; m2 (10,000 ft2 ) for a space greater than 1 , 0 0 0 m 2 ( 1 0 , 0 0 0 f t 2 ) ;
(b) Be capable of overriding the shutoff control required in 7.2.1.1 for no more than 2 hours; and
(c) Be readily accessible and located so the occupant can see the control.
Exception to clause 7.2.1.2 (c): The required control device may be remotely installed if required for reasons of safety or security. A remotely located device shall have a pilot light indicator as part of or next to the control device and shall be clearly labeled to identify the controlled lighting.
7.2.1.3 Control in Daylighted Areas:
Luminaire in daylighted areas greater than 2 5 m 2 ( 2 5 0 f t 2 ) shall be equipped with either a manual or automatic control device that,-
(a) Is capable reducing the light output of the luminaires in the daylighted areas by at least 50%; and
(b) Controls only the luminaires located entirely within the daylighted area.
7.2.1.4 Exterior Lighting Control:
Lighting for all exterior applications not exempted in clause 7.3.4 of the code shall be controlled by a photo sensor or astronomical time switch that is capable of automatically turning off the exterior lighting when daylight is available or the lighting is not required.
7.2.1.5 Additional Control:
The following lighting applications shall be equipped with a control device to control such lighting independently of general lighting,-
(a) Display/ Accent Lighting: Display or accent lighting greater than 300 m 2 ( 3 , 0 0 0 f t 2 ) area shall have a separate control device;
(b) Case Lighting: in cases used for display purposes greater than 300 m 2 ( 3 , 0 0 0 f t 2 ) areas shall be equipped with a separate control device;
(c) Hotel and Motel Guest Room Lighting: Hotel and motel guest rooms and
guest suites shall have a master control device at the main room entry that controls all permanently installed luminaries and switched receptacles;
(d) Task Lighting: Supplemental task lighting including permanently installed under shelf for under cabinet lighting shall have a control device integral to the luminaires or controlled by a wall mounted control device provided the control device complies with clause 7.2.1.2(c).
(e) Non-visual Lighting: Lighting for non-visual applications, such as plant growth and food- warming , shall be equipped with a separate control device; and
(f) Demonstration Lighting: Lighting equipment that is for sale or for demonstrations in lighting education shall be equipped with separate control device accessible only to authorized personnel.
7.2.2 Signage/Advertising Signage:
Internally – illuminated exit signs shall not exceed 5W per face. The lighting power density in case of signage/advertisement signage should not exceed 5W/f2 for internally illuminated signage and 2.5W/f2 for externally illuminated signage.
7.2.3 Exterior Building Grounds Lighting:
Lighting for exterior building grounds luminaires which operate at greater than 100W shall contain lamps having minimum efficacy of 60lm/W unless the luminaire is controlled by a motion sensor or exempt under clause 7.1.