5.1 General:
All heating, ventilation, and air conditioning equipment and systems shall comply with the mandatory provisions of clause 5.2 and the prescriptive criteria of clause 5.3.
5.2 Mandatory Requirements:
5.2.1 Natural Ventilation:
Natural ventilation shall comply with the design guidelines provided for natural ventilation in the National Building Code of India 2005 Part 8 Section 1, 5.4.3 and 5.7.1
5.2.2 Minimum Equipment Efficiencies:
Cooling equipment shall meet or exceed the minimum efficiency requirements of Table 4.1. Heating and cooling equipment not covered in table shall comply with ASHRAE 90.1- 2004 clause 6.4.1:
Unitary Air Conditioner shall meet IS1391 (part 1), Split air conditioner shall meet IS 1391 (part 2), Packaged air conditioner shall meet IS 8148 and Boilers shall meet IS 13980 with above 75% thermal efficiency.
| Equipment Class | Minimum COP | Minimum IPLV | Test Standard |
|---|---|---|---|
| Air Cooled Chiller <530 kW(<150tons) | 2.90 | 3.16 | ARI 550/590-1998 |
| Air Cooled Chiller≥530 kW(≥150tons) | 3.05 | 3.32 | ARI 550/590-1998 |
| Centrifugal Water Cooled Chiller<530kW (<150 tons) | 5.0 | 5.25 | ARI 550/590-1998 |
| Centrifugal Water Cooled Chiller ≥530 and <1050 kW(≥150 and < 300 tons ) | 5.55 | 5.9 | ARI 550/590-1998 |
| Centrifugal Water Cooled Chiller≥1050 kW) (≥300tons) | 6.1 | 6.4 | ARI 550/590-1998 |
| Reciprocating Compressor, Water Cooled Chiller all sizes | 4.20 | 5.05 | ARI 550/590-1998 |
| Rotary Screw and Scroll Compressor , Water Cooled Chiller <530kW (<150tons) | 4.70 | 5.49 | ARI 550/590-1998 |
| Rotary Screw and Scroll Compressor | 5.40 | 6.17 | ARI 550/590- |
| Water Cooled Chiller ≥ 530kW and <1050 kW(≥150and <300 tons) | 1998 | ||
| Rotary Screw and Scroll Compressor | 5.75 | 6.43 | ARI 550/590-1998 |
| Water Cooled Chiller ≥1050kW(≥300tons) | 5.75 | 6.43 | ARI 550/590-1998 |
5.2.3 Controls:
5.2.3.1 All mechanical cooling and heating systems shall be controlled by a time clock that,-
(a) can start and stop the system under different schedule for three different day- types per week;
(b) is capable of retaining programming and time setting during loss of power for a period of at least 10 hours; and
(c) includes an accessible manual override that allows temporary operation of the system for up to 2 hours:
Exception to clause 5.2.3.1:
(a) Cooling systems< 28kW (8tons)
(b) Heating systems < 7 kW (2 tons).
5.2.3.2 All heating and cooling equipment shall be temperature controlled. Where a unit provides both heating and cooling, controls shall be capable of providing a temperature dead band of 3o C (5 0F) within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum. Where separate heating and cooling equipment serve the same temperature zone, thermostats shall be interlocked to prevent simultaneous heating and cooling.
5.2.3.3 All cooling towers and closed circuit fluid coolers shall have either two speed motors, pony motors, or variable speed drives controlling the fans.
5.2.3.4 The automatic door closure and door gaps sealing arrangement should be provided in all air conditioned rooms.
5.2.4 Piping and Ductwork:
5.2.4.1 Piping for heating systems with a design operating temperature of 6 0 ° C (1400F) or greater shall have at least R-0.70(R-4) insulation. Piping for heating systems with a design operating temperature less than 6 0 ° C ( 1 4 0 0 F ) but greater than 40°C(104°F) , piping for cooling systems with a design operating temperature less than 1 5 0 C ( 5 9 0 F ) , , and refrigerant suction piping on split systems shall have at least R-0.35 (R-2) Insulation exposed to weather shall be protected by aluminum sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above, or be painted with water retardant paint.
5.2.4.2 Ductwork shall be insulated in accordance with Table 5.2.
| Duct Location | Required Insulationa | |
| Supply Ducts | Return Ducts | |
| Exterior | R-1.4 | R-0.6 |
| Ventilated Attic | R-1.4 | R-0.6 |
| Unventilated Attic without Roof Insulation | R-1.4 | R-0.6 |
| Unventilated Attic with Roof Insulation | R-0.6 | No Requirement |
| Unconditioned Spaceb | R-0.6 | No Requirement |
| Indirectly conditioned Spacec | No Requirement | No Requirement |
| Buried | R-0.6 | No Requirement |
a Insulation R-value is measured on a horizontal plane in accordance with ASTM C518 at a mean temperature of 2 4 ° C ( 7 5 ° F ) at the installed thickness.
b Includes crawlspaces both ventilated and non ventilated.
C Include return air plenums with or without exposed roofs above.
5.2.5 System Balancing:
5.2.5.1 General:
Construction documents shall require that all HVAC systems be balanced in accordance with generally accepted engineering standards.
Construction documents shall require that a written balance report be provided to the owner or the designated representative of the building owner of HVAC systems serving zones with a total conditioned area exceeding 2 5 0 m 2 ( 2 , 5 0 0 f t 2 )
5.2.5.1.1 Air System Balancing:
Air systems shall be balanced in a manner to first minimize throttling losses. Then, for fans with fan systems power greater than 0.75 kW (1.0 hp), fan speed shall be adjusted to meet design flow conditions.
5.2.5.1.2 Hydronic System Balancing:
Hydronic Systems shall be proportionately balanced in a manner to first minimize throttling losses, then the pump impeller shall be trimmed or pump speed shall be adjusted to meet design flow conditions:
Exceptions to 5.2.5.1.2,-
(a) Impellers need not be trimmed nor pump speed adjusted for pumps with pump motors of 7.5 kW (10 hp) or less;
(b) Impellers need not be trimmed when throttling results is no greater than 5% of the nameplate horsepower draw, or 2.2 kW (3hp), whichever is greater.
5.2.6 Condensers:
5.2.6.1 Condenser Locations:
Care shall be exercised in locating the condensers in such a manner that heat sink is free of interference from heat discharge by devices located in adjoining spaces and also does not interfere with such other systems installed nearby.
The condensers (outdoor units) especially of single unit room split air conditioners shall be located in shaded and well ventilated area closest to the evaporator (indoor unit). In case of unavailability of shaded area, the condensers shall be provided with artificial shading to prevent direct heating of the unit during day time by the sun light. The unitary air conditioners shall also be
installed at suitable locations to avoid direct sunlight and shading may be provided for improved performance. The piping system connecting the outdoor and indoor units shall be insulated as per clause 4.2.4.1and the length of such pipes shall not exceed the length as specified by the manufacturer.
5.2.6.2 Treated Water for condensers:
All high - rise buildings using centralized cooling water systems shall use soft water for the condenser and chilled water systems.
5.3 Prescriptive Requirements:
Compliance shall be demonstrated with the requirements in clause 5.3.1 through clause 5.3.2 for each HVAC system that meets the following criteria,-
(a) Serves a single zone;
(b) Cooling (if any) is provided by a unitary packaged or split – system air conditioner or heat pump;
(c) Heating (if any) is provided by a unitary packaged or split-system heat pump, fuel- fired furnace, electric resistance heater or baseboards connected to a boiler; and
(d) Outside air quantity is less than 1,400 l/s (3000 cfm) and less than 70% of supply air at design conditions.
Other HVAC system shall comply with ASHRAE 90.1-2004 clause 6.5
5.3.1 Economizers:
5.3.1.1 Air side Economizers:
Each individual cooling fan system that has a design supply capacity over 1,200 l/s (2,500 cfm) and a total mechanical cooling capacity over 22kW (6.3 tons) shall include either,-
(a) An air economizer capable of modulating outside-air and return – air dampers to supply 100 percent of the design supply air quantity as outside –air; or
(b) A water economizer capable of providing 100% of the expected system cooling load at outside air temperatures of 10 oC (50 oF ) dry-bulb/7.2 o C (45 oF) wet-bulb and below:
Exception to 5.3.1.1:
(a) Projects in the Hot-Dry and Warm- Humid climate zones are exempt.
(b) Individual ceiling mounted fan systems < 3,200 l/s (6,500cfm) are exempt.
5.3.1.2 Where required by clause 4.3.1.1 economizers shall be capable of providing partial cooling even when additional mechanical cooling is required to meet the cooling load.
5.3.1.3 Air–side economizer shall be tested in the field following the requirements in Appendix F to ensure proper operation:
Exception to 5.3.1.3: Air economizer installed by the HVAC system equipment manufacturer and certified for that building as being factory calibrated and tested as per the procedure in Appendix F.
5.3.2 Variable Flow Hydronic Systems:
5.3.2.1 Chilled or hot-water systems shall be designed for variable fluid flow and shall be capable of reducing pump flow rates to not more than the larger of:
(a) 50% of the design flow rate; or
(b) The minimum flow required by the equipment manufacturer for proper operation of the chiller or boilers.
5.3.2.2 Water cooled air conditioning or heat pump units with a circulation pump motor greater than or equal to 3.7 kW (5 hp) shall have two – way automatic isolation valves on each water cooled air-conditioning or heat pump unit that are interlocked with the compressor to shutoff condenser water flow when the compressor is not operating.
5.3.2.3 Chilled water or condenser water systems that must comply with either clause 5.3.2.1 or clause 5.3.2.2 of ECBC and that have pump motors greater than or equal to 3.7 kW ( 5 hp) shall be controlled by variable speed drives.