7.2.1 Lighting Control:
7.2.1.1 Automatic Lighting Shutoff:
Interior lighting systems in buildings larger than 2 5 0 m 2 ( 2 , 5 0 0 f t 2 ) shall be equipped with an automatic control device. Within these buildings, all office areas less than 30m² ( 300ft² ) enclosed by walls or ceiling-height partitions, all
meeting and conference rooms, all toilets, all school classrooms, and all storage spaces shall be equipped with occupancy sensors. For others spaces, this automatic control device shall function on either,-
(a) A scheduled basis at specific programmed times. An independent program schedule shall be provided for areas of no more than 2 , 5 0 0 m 2 (25,000ft2) and not more than one floor; or
(b) Occupancy sensors that shall turn the lighting off within 30 minutes of an occupant leaving the space. Light fixtures controlled by occupancy sensors shall have a wall- mounted, manual switch capable of turning on lights when the space is occupied:
Exception to clause 7.2.1.1: Lighting system is designed for 24 hour use.
7.2.1.2 Space control:
Each space enclosed by ceiling- height partitions shall have at least one control device to independently control the general lighting within the space. Each control device shall be activated either manually by an occupant or automatically by sensing an occupant. Each control device shall,-
(a) Control a maximum of 250 m² ( 2, 500 ft² ) for a space less than or equal to 1 , 0 0 0 m 2 ( 1 0 , 0 0 0 f t 2 ) , and a maximum of 1,000 ; m2 (10,000 ft2 ) for a space greater than 1 , 0 0 0 m 2 ( 1 0 , 0 0 0 f t 2 ) ;
(b) Be capable of overriding the shutoff control required in 7.2.1.1 for no more than 2 hours; and
(c) Be readily accessible and located so the occupant can see the control.
Exception to clause 7.2.1.2 (c): The required control device may be remotely installed if required for reasons of safety or security. A remotely located device shall have a pilot light indicator as part of or next to the control device and shall be clearly labeled to identify the controlled lighting.
7.2.1.3 Control in Daylighted Areas:
Luminaire in daylighted areas greater than 2 5 m 2 ( 2 5 0 f t 2 ) shall be equipped with either a manual or automatic control device that,-
(a) Is capable reducing the light output of the luminaires in the daylighted areas by at least 50%; and
(b) Controls only the luminaires located entirely within the daylighted area.
7.2.1.4 Exterior Lighting Control:
Lighting for all exterior applications not exempted in clause 7.3.4 of the code shall be controlled by a photo sensor or astronomical time switch that is capable of automatically turning off the exterior lighting when daylight is available or the lighting is not required.
7.2.1.5 Additional Control:
The following lighting applications shall be equipped with a control device to control such lighting independently of general lighting,-
(a) Display/ Accent Lighting: Display or accent lighting greater than 300 m 2 ( 3 , 0 0 0 f t 2 ) area shall have a separate control device;
(b) Case Lighting: in cases used for display purposes greater than 300 m 2 ( 3 , 0 0 0 f t 2 ) areas shall be equipped with a separate control device;
(c) Hotel and Motel Guest Room Lighting: Hotel and motel guest rooms and
guest suites shall have a master control device at the main room entry that controls all permanently installed luminaries and switched receptacles;
(d) Task Lighting: Supplemental task lighting including permanently installed under shelf for under cabinet lighting shall have a control device integral to the luminaires or controlled by a wall mounted control device provided the control device complies with clause 7.2.1.2(c).
(e) Non-visual Lighting: Lighting for non-visual applications, such as plant growth and food- warming , shall be equipped with a separate control device; and
(f) Demonstration Lighting: Lighting equipment that is for sale or for demonstrations in lighting education shall be equipped with separate control device accessible only to authorized personnel.