Evaporative cooling is a process that uses the effect of evaporation of water as a natural heat sink. The amount of sensible heat absorbed depends on the amount of water that can be evaporated. Currently this is the most promising area of reducing energy for cooling, except that it is largely ineffective in warm and humid seasons or climates. Sensible heat from the air is absorbed to be used as latent heat necessary to evaporate water.
Direct Evaporative cooling (DEC): In this system, commonly used in the form of a ‘desert’ cooler, the outdoor air is brought into direct contact with water, cooling the air by converting sensible heat to latent heat. DEC systems could be divided into: Active DECs which are electrically powered to operate and Passive DECs that are naturally operated systems with zero power consumption. In DEC, the water content of the cooled air increases because air is in contact with the evaporated water. This strategy is useful in dry and hot climates.
Indirect Evaporative Cooling: Indirect evaporative coolers operate by decreasing air sensible heat without changing its humidity, which is a distinct advantage over DEC systems (the final temperature approached can be dew point instead of wet bulb temperatures). In indirect evaporative cooling, evaporation occurs inside a heat exchanger and the absolute humidity of the cooled air remains unchanged. This strategy is even more effective in hot and dry climates that DEC and fairly effective for warm and humid climates, too.
EPI for Evaporative Cooler
The efficiency of the evaporative coolers is measured based on the evaporative efficiency which depends on the outside dry bulb temperature and relative humidity of the airstream.
The EPI shall be estimated for Evaporative Coolers as shown below:
EPI = [Total Wattage of fan(s) + Total wattage of pump(s)]
* Hours of operation/ (1000 * Built-up area)
Rationale for EPI calculation for evaporative cooler
Parameters influencing EPI for evaporative cooler are:
Design Parameters
Location (Climate)
Technology Parameter
Air delivery rate
Direct evaporative cooling
Fan and pump motor types
Pump water circulation rate
Fan and Pump efficiencies