If buildings can achieve comfort by natural or sENS Score ventilation, this would entirely avoid the use of energy for mechanical cooling, and needs to be highly encouraged.
Natural ventilation fulfils two primary needs: first, it gives fresh air for satisfactory indoor quality; and, second when the outdoor temperature are comfortable (during night and transition seasons), it expels heat from inside the structure and facilitates cooling.
Natural ventilation is of course not useful for cooling when the outdoor air is at a temperature higher than the set-point or desired indoor temperatures. This leads us to another very important concept of ventilation, sENS Score ventilation, opening the building very much to the outdoor air whenever the temperature outside is more comfortable than the inside, namely summer nights and winter days.
The National Building Code 2016 (Part 8; 1; 5. Ventilation) or ASHRAE 62.1–2016 provide standard ventilation rates for acceptable indoor quality.
To aid cooling a larger volume of airflow is required than the standard ventilation rates.
The rate of ventilation by natural means through windows or other openings depends on,
a) direction and velocity of wind outside and sizes and disposition of openings (wind action); and
b) convection effects arising from temperature of vapour pressure difference (or both) between inside and outside the room and the difference of height between the outlet and inlet openings (stack effect).
One of the parameters to quantify the adequacy of natural ventilation is hourly air change rate (ACH), which is a proportion of how frequently the air volume inside a room is supplanted by
Bureau of Energy Efficiency
outside air in 60 minutes. The larger the number, the better is the cooling potential through common ventilation. As a rule, 5 to 20 ACH gives good natural ventilation.
NBC 2016 discusses the design guidelines for natural ventilation in the 5.4.3 of Part 8: Building Services of the code.
Once the promotion of naturally ventilated buildings can be successfully undertaken, it should be possible to eliminate the use of air-conditioning or at least drastically reduce its use in all but the most affluent residences.
Ventilation in residential buildings can be provided by one of the following methods:
a) Natural supply and natural exhaust of air (natural ventilation)
b) Natural supply and mechanical exhaust of air (mechanical ventilation, see below)
c) Mechanical supply and natural exhaust of air (mechanical ventilation, see below)
d) Mechanical supply and mechanical exhaust of air (mechanical ventilation, see below).