71 Definitions.-
In this Chapter unless the context otherwise requires, -
(a) "exit" means a passage, channel or means of access from any building, storey's or floor area to a street or other open space of safety and includes a vertical exit or a horizontal exit or an outside exit.
(i) “vertical exit” means an exit used for ascension or descension between two or more levels including stairways smoke proof, ramps, lifts, escalators and fire escapes,
(ii) "horizontal exit" means a protected opening through or around a fire wall or a bridge connecting two buildings,
(iii) outside exit" means an exit from the building to a street or to an open area leading to a street or to an enclosed fire resistive passage leading to a street;
(b) “travel distance” means the distance from the exit of any premises on a floor of a building to a place of safety, be it a vertical exit, a horizontal exit or an outside exit, measured along the line of travel.
72 Fire protection.-
Every building of more than 12.50 meter height and/or having covered area of more than 500 sqm shall be provided with adequate means of exit and all arrangement for protection in case of fire in accordance with the provisions contained in the latest version of National Building Code.
73 General exit requirements.-
(1) The following general requirements shall apply to exit:-
(a) all exits shall be free from obstructions;
(b) no building shall be altered so as to reduce the number, with or protection of exits to less than what is required under these rules;
(c) exits shall be clearly visible and routes to reach each exit shall be clearly marked;
(d) all exits shall be properly illuminated;
(e) fire-fighting equipments shall, where provided along exits, be suitably located and clearly marked so as not to obstruct the exit way and there shall be clear indication from either side of the exit;
(f) alarm devices shall be installed to ensure prompt evacuation through exits;
(g) all exits shall provide continuous means of access to the exterior of a building or to an exterior open leading to a street or means of access;
(h) exits shall be so arranged that they may be reached without passing through another occupancy unit, except in the case of a building for residential and educational uses.
(2) An exit may be a door-way, corridor, passage way to staircase, ramp or a verandah or terrace which has access to the street or to the roof of a building. An exit may also include a horizontal exit leading to building at the same level.
(3) Lifts and escalators shall not be considered as exits.
(4) All basements shall have a minimum of 2(two) exits.
Explanation – Ramps to the basement shall be considered as exits.
74 Arrangements of exits.-
(1) Exits shall be so located that the distance between 2(two) exits on the floor shall not exceed-
(a) 22.5 meters, in the case of a residential building or an educational building or institutional building or hazardous building; and
(b) 30 meters, in the case if an assembly building or a business building or a mercantile building or an industrial building or a storage building.
(2) For floors with sprinklers, which are not part of requirements for the floor and occupancy, the distance in sub-rule(1) may be increased by 50 percent.
(3) The distance to an exit front the dead end of a corridor shall not exceed half the distance specified in sub-rule(1), except in an educational building or an assembly building or an institutional building in which case it shall not exceed 6 meters.
(4) Whenever more than one exit is required for any room space or floor of building, exits shall be placed as remote from each other as possible and shall be arranged to provide direct access in separate directions from any part in the area served.
75 Requirements regarding staircase. –
All building referred to in rule 72 shall be provided with such number of staircase as the ULB require. Under no circumstances, the number of staircases shall be less than 2(two) in the case of a building of more than 14.0(fourteen) meters in height and one of them shall be on the external face of the building.
76 Minimum width provisions for Staircase.-
The following provisions for minimum width for staircase(s) shall be made:-
(a) for each stairway in a residential building having not more than 2(two) tenements per floor, the minimum width shall be -
(i) 0.90metre in the case of a building having above 11 meters in height.
(ii) 1.05 meters in the case of a building having above 11 meters and up to 14.0 meters in height.
(iii) 1.25 meters for primary stairway in the case of building above 14.5 meters in height.
(b) every additional tenements per floor to be served by the same staircase. The width of each stairway shall be increased by 0.15 meter, provided that for buildings constructed under the each of stairway shall not be less than 0.90 meter.
(c) for each stairway in institutional or mercantile buildings, the minimum width shall be 2.0 meters;
(d) for each stairway in educational or business or assembly buildings other than theatre, motion picture house, city hall, dance hall, auditorium, exhibition hall or similar other halls or such other places, the minimum width shall be 1.80 meters;
(e) (i) for assembly buildings not included in clause (b) above, the minimum width of each stairways shall be 1.80 meters where not more than 300 persons are to be accommodated,
(ii) for the accommodation of more than 300 persons, the minimum width of stairway as at (a) above shall be increased by 0.30 meter for every additional 100 persons or part thereof over 300 persons,
(iii) notwithstanding anything contained in sub-clause(ii), instead of a single staircase, corridor or passageway of the width prescribed by the said sub-rule, there may be two or more staircases, corridors or passageways as may be
sufficient for the number of persons that can accommodated in the building, each having a width as prescribed in sub-rule(i);
(f) for all other buildings, the minimum width of each stairway shall be 1.50 meters; (g) the minimum width of a passage or corridor shall be as follows :-
(i) for passage connecting vertical exits and the apartments/ units, the width shall not be less than the width of each stairways specified in clause(a) to (e) except for mercantile business buildings and assembly buildings;
(ii) for a passage within a apartment, the width shall not be less than 0.90 meter;
(iii) for a passage giving access to shops in a mercantile building, the width shall not be less than 2 meters if the shops are on one side only, and 3 meters if the shops are on both sides;
(iv) for a passage in a business building, the width shall not be less than 2.50 meters;
(v) .for a passage in an assembly building, the width shall not be less than that as derived under sub-clause(i),(ii) and (iii) of clause (e).
77 Provisions for doors for an assembly room or hall.-
The doors of a room or a hall, where groups of people congregate or gather in any building, shall be made to open outside shall be affixed thereto. There shall be at least 2(two) such doors in every such room or hall if not more than 300 persons are intended to be accommodated therein and an additional door shall be provided for every 100 persons or part thereof in excess of 300 persons. The width of every such door shall not be less than 1.80 meters.
78 Other requirements. –
In respect of matters relating to fire prevention and fire protection, for which provisions have not been made in this chapter, the provisions of the latest edition of the National Building Code and the latest edition of the National Electrical Code shall apply.
79 Consultation with the Director of Fire Services before granting permission to erect a building.-
No permission for erection, addition to or alteration of any building other than a building upto 12.50 meter in height and/or having covered area upto 500 sqm shall be granted unless the ULB in consultation with the Director, Fire Service of the Government of Tripura or any officer specially empowered by the Director, Fire Service for the purpose is satisfied about the provisions or means of exits and about the arrangements for protection against fire proposed for the building.
79.(a) Erection of Hoarding, Signboard etc.:-
No hoarding, signboard or any permanent/temporary structure to be used in commercial or other purposes in any building or attaching two or more buildings shall be allowed without the prior permission of the respective ULB.
80 Requirements for special occupancies under any other law in force:-
Notwithstanding anything contained in these rules a building shall comply with special requirements, if any, laid down in Factories Act, 1948 (63 of 1948) or in any other law for the time being in force in relation to such building.