Section 2 Gas Supply
2.1 For the purpose of this Section, the following definitions shall apply.
2.1.1 Appliance Valve — A device that will shut-off the gas supply to the burner(s).
2.1.2 Authority Having Jurisdiction — The Authority which has been created by a statute and which, for the purpose of administering the Code/Part, may authorize a committee or an official to act on its behalf; hereinafter called the ‘Authority’.
2.1.3 Customer’s/Consumer’s Connection — Piping tapped on riser to supply each individual customer/ consumer.
2.1.4 Gas Fitter — An employee of the gas supplying organization.
2.1.5 Pilot — A small flame which is utilized to ignite the gas at the main burner(s).
2.1.6 Pressure Regulator — A device designed to lower the pressure of gas coming from the distribution main and to maintain it practically constants downstream. This normal operation pressure shall be practically in all cases that of the gas appliances used.
2.1.7 Purge — To free a gas conduit of air or gas or a mixture of gas and air.
2.1.8 Qualified Installing Agency — An individual, firm or agency which either in person or through a representative is engaged in and is responsible for the installation or replacement of gas piping on the outlet side of the gas meter, or the connection, installation or repair of gas supply piping and appliances within a building, and who is experienced in such work, familiar with all precautions required, and who has complied with all the requirements as to qualification, registration, licensing, etc, of the Authority.
2.1.9 Riser — Piping usually vertical on most of its length that supplies gas from the service to the various storeys of the building.
2.1.10 Service Pipe — Pipe that runs between the distribution main in the street and the riser in the case of multi-storeyed building or the meter in the case of an individual house.
A device installed outside the premises to cut-off the main supply of gas from pipeline by the supplier.
2.1.12 Vent Pipe — A safety device to which certain regulators are connected to evacuate outside gas that may escape from the normal circuit when some part of system gets damaged or malfunctions or a safety valve is open.
6.1 No person, unless is the employ of the gas company or having permission from the gas company, shall turn on the gas at a service shut-off valve or at any valve that controls the supply of gas to more than one consumer.
6.2 Gas shall not be turned on at any meter valve without specific permission from the gas company or other authority if any of the following conditions exists:
a) If the gas piping appliances or meter supply through the meter valve are known to leak or otherwise to be defective (see 10).
b) If required inspection of the piping or appliance has not been made.
c) If the gas company or other authority has requested that the gas be left turned off.
d) If the meter valve is found shut off for some reason not known to the gas fitter.
The gas shall not be turned on in the event of fire.
6.3 Gas shall not be turned on at any branch line valve if any of the conditions specified in 6.2 prevails. Where a branch line valve is found closed, a gas fitter shall again turn the gas on at such valve only if proper precautions to prevent leakage are taken and no other unsafe conditions are created thereby.
6.4 Gas shall not be turned on at either the meter valve or service line unless all gas keys or valves provided on all outlets in the piping system are closed or all outlets in the piping system are capped or plugged.
10.1 Before turning gas under pressure into any piping, all openings from which gas may escape shall be closed.
No matches, flame or other sources of ignition shall be employed to check for gas leakage from meters, piping or appliances. Checking for gas leakage with soap and water solution is recommended.
Artificial illumination used in connection with a search of gas leakage shall be restricted to electric hand flash lights (preferably of the safety type) or approved safety lamps. In searching for leaks, electric switches should not be operated. If electric lights are already turned on, they should not be turned off.
Immediately after turning gas into the piping, the system shall be checked to ascertain that no gas is escaping. This may be done by carefully watching the test dial of the meter to determine whether gas is passing through the meter. In no case should a leakage test be made using a gas meter unless immediately prior to the test it has been determined that the meter is in operating condition.
This may be done by attaching to an appliance, orifice or a manometer or equivalent device and momentarily turning on the gas supply and deserving the gauging device for pressure drop with the gas supply shut-off. No discernible drop in pressure shall occur during a period of 3 min.
10.6 After piping has been checked, all gas piping shall be fully purged. Piping shall not be purged into the combustion chamber of an appliance. A suggested method for purging the gas piping to an appliance is to disconnect the pilot piping at the outlet of the pilot valve.
10.7 After the gas piping has been effectively purged, all appliances shall be purged and the pilots lighted.
10.8 In addition to the checking of gas leakage with soap and water solution, a suitable gas detector is also recommended for use.
7.1 The gas fitter shall put the gas off to any appliance, pipe or piping system and shall leave the gas turned off, until the causes for interrupting the supply has been removed in any one of the following cases:
a) If ordered to do so by the Authority.
b) If leakage of gas is noted, which appears to be sufficient to cause fire, explosion or asphyxiation.
c) If an installation of some gas appliance is found to be such as to cause a serious hazard to persons or property.
d) If any condition exists which threatens interruption of gas supply which may cause burner outage or otherwise prove dangerous.
7.2 It shall be the duty of the installing agency when the gas supply is to be turned off to notify all affected consumers.
7.3 Before turning off the gas at the meter, for the purpose of installation, repair, replacement or maintenance of piping or appliance, all burner and pilot valves on the premises supplied with gas through the meter shall be turned off and the meter test hand observed for a sufficient length of time to ascertain that there is no gas passing through the meter. Where there is more than one meter on the premises, precaution shall be exercised to ensure that the concerned meter is turned off.
11.1 The cylinders used for the storage and transportation of liquefied petroleum gas (LPG) shall conform to accepted standards [9-2(2)] approved by the statutory authority.
11.2 The handing, use, storage and transportation of liquefied petroleum gas in cylinders exceeding 500 ml water capacity shall be done in accordance with good practice [9-2(3)].
The following recommendations apply to installation in commercial, industrial, educational and institutional premises.
11.3.1.1 Those responsible for the installation of cylinders, equipment and piping should understand the characteristics of LPG and be trained in good practice of handling, installing and maintaining installations.
11.3.1.2 The jointing compound used at different joints in the system shall be decided by the Qualified Installing Agency. Hemp and similar materials shall not be used at the joint. In any joint in which the thread provides a gas-tight seal, jointing compound shall be used only on the male thread.
11.3.1.3 Fire extinguishers of dry powder type or carbon dioxide type conforming to accepted standards [9-2(4)] shall be provided in places where LPG cylinder installations are situated and shall be located near such installations. Two buckets filled with sand and two with water shall also be installed nearby. The number, type and size of the fire extinguishers shall be as follows:
| Number | Type | Capacity | ||
|---|---|---|---|---|
| a) | For installations with LPG 40 kg to 200 kg | 2 | Dry Powder | 10 kg |
| b) | For installations with LPG more than 200 kg and up to 320 kg | 2 | Dry powder | 10 kg |
| c) | For installations with LPG more than 320 kg and up to 1 000 kg | 3 | Dry powder | 10 kg |
For electrical installations, one number CO fire extinguisher (4.5 kg capacity) shall be provided.
11.3.1.4 Liquefied petroleum gas shall not be transferred from the cylinders in which it is received to any other container.
a) Stationary installation not exceeding 40 kg of LPG may be installed indoors on any floor. It is recommended to have a minimum floor area of 5 m2 for such an installation.
b) Stationary installations each not exceeding 40 kg of LPG may be installed indoors on any floor within the same workspace provided the minimum distance between two such installations is 3 m, the proportion of such installations to floor area is one installation per 5 m2 and the aggregate quantity of gas of all such installations does not exceed 200 kg.
c) Stationary installation not exceeding 80 kg of LPG may be installed indoors on any floor provided the floor area for such an installation is not less than 12 m2.
d) Stationary installations each not exceeding 80 kg of LPG may be installed indoors on any floor and within the same workspace provided the minimum distance between two such installations is 3 m, the proportion of such installations to floor area is one installation per 12 m2 and the aggregate quantity of gas of all such installations does not exceed 200 kg.
e) Stationary installation not exceeding 320 kg of LPG may be installed indoors in an enclosed section of a building or a room reserved exclusively for this purpose and ventilated at low level directly to the outside air.
f) Stationary installation above 320 kg [200 kg in case provision as in (e) is not possible] but not exceed 1 000 kg shall be installed outdoors on ground level only. A minimum distance of 3 m shall be maintained between an installation and any building, public place, roadways, and other surroundings. The installation shall be protected from excessive weathering by sun, rain, etc, and from tampering by unauthorized persons. A leanto-roof with expanded metal on angle-iron framework on the sides is considered suitable for this purpose. In any case, adequate ventilation at ground level to the outside air shall be provided. The distance between any two such installations shall be 3 m unless separated by a leakproof wall of fire-resistant
material up to at least 1 m above the height of the manifold valve.
g) The position of the cylinders shall facilitate: 1) changing and quick removal of any cylinder in case of necessity, and
h) Cylinders shall be installed upright with the valves uppermost.
j) Cylinder shall not be installed or used below ground level in cellars or basements.
k) Cylinders containing more than 20 kg of gas shall not be located on floors above ground level.
m) Cylinders shall be located on a concrete or brick floor, preferably raised in case of outdoor installations.
n) Cylinders shall not be placed close to steam pipes or any other source of heat and shall be protected from the weather and direct sun’s heat. Cylinders shall be placed at a distance of 3 m away from any other source of heat which is likely to raise the temperature of cylinders above the room temperature unless separated by metal sheet or masonry partition.
11.3.3.1 All materials, fittings, etc, used in cylinder manifold systems shall comply with the distributing company’s stipulations.
11.3.3.2 The individual component parts of manifolds, that is, piping, fittings, pigtails, etc, which are subject to cylinder pressure shall be capable of withstanding a test pressure without bursting of 2.5 N/mm2 or one and a half times the maximum pressure corresponding in the maximum assessed temperature of the cylinder, whichever is more.
11.3.3.3 Where cylinder installations are made up with service and reserve batteries of cylinders, suitable change-over devices or valves shall be incorporated in the manifold header to prevent undue escape of the gas when cylinders are changed.
11.3.3.4 If pressure regulators, manifold headers, automatic change-over devices, etc, are connected to cylinders by semi-flexible connectors, they shall be rigidly supported. Copper tube pigtails are considered to be flexible or semi-flexible connectors for this purpose.
11.3.3.5 Suitable line shut-off valves shall be fitted for each appliance or burner when more than one appliance is connected to the gas supply. Both ends of the connection to portable appliances shall be securely attached by means of clips. Hose shall be of a type resistant to liquefied petroleum gas.
11.3.3.6 It is recommended that joints in manifold headers which do not have to be taken in normal use should be welded or brazed using a material and which shall have a melting point of at least 540°C.
11.3.3.7 All joints between manifold headers and cylinder connectors shall be readily accessible.
11.3.4.1 Pressure regulators and other devices used to control the gas shall comply with the distributing company’s stipulations and accepted standards [9-2(5)].
11.3.4.2 Pressure regulator fitted with a safety valve shall be either:
a) installed in the open air, or
b) vented to the open by means of a metal vent pipe connected to the safety valve outlet.
11.3.4.3 Care shall be taken that safety valve outlets do not become choked with dust or other foreign matter.
11.3.4.4 If the regulator is fitted with a relief valve, care should be taken in positioning the regulator to avoid unnecessary hazards if the relief valve functions.
11.3.4.5 Pressure regulators and other control devices shall be adequately supported.
A handbook containing all instructions with regard to the following aspects shall be supplied by the supplier to the consumers:
a) operation of the whole system;
b) how to recognize gas leaks;
c) action to be taken in case of leakage;
d) action to be taken in case of fire; and
e) action to be taken in case of damage to, or failure of any part of the installation.
11.3.6 For detailed information regarding installation of LPG cylinders in commercial, industrial, educational and institutional premises, reference may be made to good practice [9-2(6)].
8.1 Installation, repair and replacement of gas piping
or appliances shall be performed only by a qualified installing agency.
8.2.1 Piping shall be of wrought iron, steel, copper or cast iron when the gas pressure is less than 7kN/m2; with higher gas pressure use of cast iron shall be prohibited.
8.2.1.1 SS 316/304/321 Flexible PE coated flexible pipe in rolls shall be permitted in low pressure system provided the pipe meets the required standard, to avoid the bends, fittings and leakages from the joint which are potential leakage points. Also, reference may be made to accepted standard [9-2(1)]. Heavy rubber flexible tube shall be permitted only as direct connection to burner from appliance valve.
Gas piping shall be of such size and so installed as to provide supply of gas sufficient to meet the maximum demand without undue loss of pressure between the meter or service regulator when a meter is not provided, and the appliance(s).
8.2.2.1 The size of gas piping depends upon the following factors:
a) allowable loss in pressure from meter or service regulator, when a meter is not provided, to appliance;
b) maximum consumption to be provided;
c) length of piping and number of fittings; and
d) specific gravity of gas.
8.2.2.2 No gas pipe smaller than 8 mm shall be used.
8.2.3 As far as possible, straight lengths of piping should be used. Where there are bends in the pipe line, these should have a radius of at least five times the diameter of the pipe.
8.2.4 For any thread joint proper sealant shall be used on male threads only.
8.3 The gas piping shall be of the colour stipulated by explosive authority to distinguish it from other piping and the piping shall be painted silver grey with red band of 150 mm width. The gas pipeline shall be painted canary yellow in case of natural gas.
Piping shall be buried to a minimum depth of 1 m or covered in a manner so as to protect the piping from physical damage.
Generally all the piping within the premises where it
has to run on the wall shall be exposed and should not be in contact with wall to ensure that no corrosion takes place. Epoxy sealant or polyethylene conduit shall be used to ensure no contact of pipe with the wall in the situation of pipe crossing the wall. Under ground or concealed gas pipeline in contact with earth or other materials which may corrode the piping shall be protected against corrosion by application of adequate corrosion resistant coating backed up by cathodic protection system.
8.5 The building shall not be weakened by the installation of any gas piping.
8.6 Gas piping in building shall be supported with pipe hooks, metal pipe straps, bonds or hangers suitable for the size of piping and of adequate strength and quality and located at proper intervals so that the piping may not be moved accidentally from the installed position.
Where gas pipe enters a building through a wall or floor of masonry or concrete, any gas piping or other piping entering the walls or floors shall be suitably sealed against the entrance of water/moisture or gas. Regarding protection of openings in walls or floors, from fire, reference shall be made to Part 4 ‘Fire and Life Safety’.
Piping in solid floors, such as concrete, shall be laid in channels in the floor suitably covered to permit access to the piping with a minimum damage to the building.
8.7.2 Single pipe without joint shall be used for wall crossing in any building.
8.8 Gas pipe shall not be bent. Fittings shall be used when making turns in gas pipe.
8.9 Generally concealed piping shall not be allowed. However, if it is necessary then it shall be under the 8.4 of underground piping and all protection such as coating, cathodic protection shall be done.
8.10 A drip shall be provided in the gas distribution system, if the moisture contents in the gas is likely to reach saturation point at any stretch of pipe line in the system; a drip shall, however, be provided at any suitable point in the line of the pipe where condensate may collect and from where it can be easily removed. This drip should be so installed as to constitute a trap where in an accumulation of condensate will shut off the flow of gas before it will run back into the meter.
8.10.1 Drip has to be provided in the case of gas consisting moisture content.
No device shall be placed inside the gas piping or fittings that will reduce the cross-sectional area or otherwise obstruct the free flow of gas.
8.12 Piping shall be electrically continuous throughout its length and properly earthed except in stretches where cathodic protection system is used for protection against corrosion. It shall not, however, be used to earth any electrical equipment.
8.12.1 The distance between gas piping and electrical wiring system shall be at least 60 mm and, where necessary, they shall be securely fixed to prevent contact due to movement. The gas piping should run above the electrical wiring. In this type of installation in the event of any leakage of natural gas, the gas would move up (natural gas being lighter than air) and would not come directly in contact with the electrical wiring. If the gas to be supplied is heavier than the air then the gas piping should run below the electrical wiring.
8.13 The distance between the gas piping and steam piping, if running parallel, shall be at least 150 mm. The gas piping should preferably run below the steam piping.
8.15 Smoking shall not be permitted when working on piping which contains or has contaminated gas.
8.16 Meters shall be installed in such a way that there shall be no load transfer from the pipeline to the inlet/ outlet of the meter and shall be easily accessible.
11.4.0 The following recommendations apply to LPG bulk storage installations where storage tanks over 450 litres water capacity are used at industrial, commercial and domestic consumers’ premises.
The maximum capacity of an individual tank and group of tanks at industrial, commercial and domestic premises shall be as follows:
| Premises | Maximum Water Capacity of an Individual Tank, 1 | Maximum Water Capacity of Group of Tanks, 1 |
|---|---|---|
| Industrial | 130 000 | 260 000 |
| Commercial | 40 000 | 80 000 |
| Domestic | 20 000 | 80 000 |
11.4.1.1 Storage tanks shall be located outside the buildings and shall not be installed one above the other.
11.4.1.2 Each individual tank shall be located with respect to the nearest important building or group of buildings or line of adjoining property which may be built in accordance with Table 1. The distances given refer to the horizontal distance in plan between the nearest point of the storage tank and building/property line.
11.4.1.3 In heavily populated or congested areas the authority may determine the need for other reasonable protective methods to be taken, such as provision of fire walls, etc. If fire walls are to be provided, the authority may determine the extent to which the safety distances for above ground tanks may be reduced.
11.4.1.4 No LPG tank(s) shall be located within the bunded enclosures of any petroleum installation. The minimum distance of separation between LPG storage tanks and any petroleum installation shall be as prescribed under the Petroleum Rules, 1976 or as specified in Table 1 whichever is more.
11.4.1.5 The number of storage tanks in one storage installation shall not exceed six. In case there are more than one storage installations, the safety distance between two installations shall be the same as the distance between the tanks and the property line in accordance with Table 1.
Since LPG is heavier than air, storage tank shall not be enclosed within bund walls. The accumulation of flammable liquid under LPG tanks shall be prevented by suitably slopping the ground.
9.1 No person shall use or permit the use of a new system or an extension of an old system of gas piping in a building or structure before the same has been inspected and tested to ensure the tightness of the system, and a certificate has been issued by the Authority.
Before any system of gas piping is finally put in service, it shall be carefully tested to ensure that it is gas-tight. Where any part of the system is to be enclosed or concealed, this test should precede the work of closing in. To test for tightness the piping may be filled with city gas, air or inert gas but not with any other gas or liquid. In no case shall oxygen be used. The piping shall stand a pressure of at least 20 kN/m2 measured with a manometer or slope gauge, for a period of not less than 10 min without showing any drop in pressure.
9.1.2 When the gas pressure exceeds 7 kN/m2, the piping shall withstand a pressure of 0.6 MN/m2 for 4 h.
(This test is for piping designed for working pressure less than 0.4 MN/m2.)
9.2 The Authority shall, within a reasonable time after being requested to do so, inspect and test a system of gas piping that is ready for such inspection and test, and if the work is found satisfactory and test requirements are complied with, it shall issue the certificate.
p) When cylinders are being connected or disconnected, there shall be no open flame or similar source of ignition in the vicinity; and smoking shall be prohibited.
q) Cylinders shall not be installed at a place where they are likely to cause an obstruction, to be damaged or to be exposed to conditions likely to affect their safety.
r) In order to prevent the hazardous collection of gas, cylinders shall be placed at least 1 m away from culverts, depressions, or openings leading to below ground level compartment, and drains.
s) Cylinders which have safety relief valves or similar devices incorporated in them shall be so positioned that if the relief device operates, escaping gas is not hazardous.
When portability of cylinders is necessary the following requirements shall be fulfilled:
a) The sum total capacity of the cylinders connected to each manifold shall not exceed 80 kg of LPG. The total quantity of gas thus installed in a workspace shall not exceed 200 kg.
b) If cylinders are mounted on a trolley shall be stable. Where necessary, the cylinders shall be secured to prevent them from falling.
c) The regulator shall be connected directly to the cylinder valve or to a manifold which shall be connected to the cylinder valves by means of rigid connections to give adequate support to the regulator. The only exception to this requirement is where cylinders are mounted on a trolley and the manifold is rigidly supported on the trolley. In such a case flexible or semi-flexible connections may be used between the cylinder valves and the manifold but not between the manifold and the regulator.
d) At any time the total quantity of gas at portable installations shall be in proportion to the floor area as specified in 11.3.2.1(a) to 11.3.2.1(f).
e) At any time the provisions at 11.3.2.1 shall be ensured for all installations.
11.4.3.1 To prevent trespassing or tampering, the area which includes tanks, direct fired vapourisers, pumping equipment and loading and unloading facilities shall be enclosed by an industrial type fence at least 2 m high along the perimeter of the safety zone. Any fence shall have atleast two means of exit. Gates shall open outwards and shall not be self-locking.
11.4.3.2 When damage to LPG systems from the LPG tank lorry is a possibility, precautions against such damage shall be taken.
11.4.3.3 Underground tanks shall be protected from above ground loading by providing a suitable curb to prevent a possible accidental damage to the tank and its fittings by LPG tank lorry.
Road ignitable material, such as weeds, long grass or any combustible material shall be removed from an
| Sl No. | LPG Storage Water Capacity of Individual Tank | Distance from Building/Property Line | Distance between Tanks | ||
| 1 | Above Ground m | Under Ground m | Above Ground m | Under Ground m | |
| (1) | (2) | (3) | (4) | (5) | (6) |
| i) | Up to 2 000 | 5 | 5 | 1 | 1.5 |
| ii) | Above 2 000 and up to 10 000 | 10 | 7.5 | 1 | 1.5 |
| iii) | Above 10 000 and up to 20 000 | 15 | 10 | 1.5 | 1.5 |
| iv) | Above 20 000 and up to 40 000 adjacent | 20 | 15 | 2 | 0.25 dia of vessel or 1.5 m, Min |
| v) | Above 40 000 and above adjacent | 30 | 15 | 2 | 0.25 dia of vessel or 1.5 m, Min |
| NOTE — If the aggregate water capacity of a multi-tank installation is 40 000 litres or greater, the above minimum safety distances shall apply to the aggregate storage capacity rather than the capacity per individual storage tank. | |||||
area within 3 m from the shell of any LPG tank of up to 2 000 litres water capacity, and within 6 m from the shell of larger tanks. If weed killers are used, chemicals which are a potential source of fire hazard shall not be selected for this purpose.
No smoking or naked flames shall be permitted within the safety zone of the installation. Prominent notices to this effect shall be posted at access point.
The possibility of a major fire outbreak, leading to direct flame impingement of the storage tank, shall be minimized by sound engineering in plant design and layout, good operating practice, and proper education and training of personnel on both routine operations and on action to be taken in an emergency.
Provision shall be made for an adequate supply of water and fire protection in the storage area according to the local hoses and mobile equipment, fixed monitors or by fixed spray systems which may be automatic. Control of water flow should be possible from outside any danger area.
At least two dry chemical powder type fire extinguishers of 10 kg capacity each, conforming to the quality requirements in accordance with the accepted standards [9-2(7)], each shall be installed at points of access to the storage installations.
11.4.7 For detailed information regarding LPG bulk storage installations reference may be made to good practice [9-2(8)].
The following list records those standards which are acceptable as ‘good practice’ and ‘accepted standards in the fulfillment of the requirements of the Code. The latest version of a standard shall be adopted at the time of enforcement of the Code. The standards listed may be used by the Authority as a guide in conformance with the requirements of the referred clauses in the Code.
| IS No. | Title |
|---|---|
| (1) 14885 : 2001 | Specification for polyethylene pipe for the supply gaseous fuel |
| (2) 3196 (Part 1) : 1992 | Specification for welded low carbon steel cylinders exceeding 5 litre water capacity for low |
| IS No. | Title |
|---|---|
| pressure liquefiable gases: Part 1 Cylinders for liquefied petroleum gases (LPG) (fourth revision) | |
| 7142 : 1995 | Specification for welded low carbon steel cylinders for low pressure liquefiable gases not exceeding 5 litre water capacity (first revision) |
| (3) 8198 (Part 5) : 1984 | Code of practice for steel cylinders for compressed gases: Part 5 Liquefied petroleum gas (LPG) (first revision) |
| IS No. | Title | IS No. | Title |
| (4) 2171 : 1999 | Specification for portable fire extinguisher, dry powder (cartridge type) (third revision) | (6) 6044(Part 1) : 2000 | Code of practice for liquefied petroleum gas storage installations: Part 1 Commercial and industrial cylinder installations (first revision) |
| 2878 : 1986 | Specification for fire extinguisher, carbon dioxide type (portable and trolley mounted) (second revision) | (7) 2171 : 1999 | Specification for portable fire extinguishers, dry powder (cartridge type) (third revision) |
| (5) 4784 : 1968 | Specification for low pressure regulators for use with butane gases | (8) 6044(Part 2) : 2001 | Code of practice for liquefied petroleum gas storage installations: Part 2 Commercial, industrial and domestic bulk storage installations (first revision) |
| 4785 : 1968 | Specification for low pressure regulators for use with propane gas | ||
| 4786 : 1968 | Specification for variable high pressure regulators for use with liquefied petroleum gas |