4.1 Service shut-off valves shall be installed on all new services including replacements in a readily accessible location.
4.2 Service shut-off valves shall be located upstream of the meter if there is no regulator or upstream of the regulator, if there is one.
4.2.1 Service shut-off valves shall be located in the upstream of the meter, if a single regulator is supplying more than one consumer and each such stream shall have one additional shut off valve upstream of regulator.
4.3 All gas services operating at pressure greater than 7 kN/m2 shall be equipped with an approved service shut-off valve located on the service pipe outside the building.
4.4 Underground shut-off valves shall be located in a covered durable curb box, manhole, vault or stand pipe which is designed to permit ready operation of the valve and the covers of which shall be clearly marked ‘Gas’.