Section 2 Gas Supply
2.1 For the purpose of this Section, the following definitions shall apply.
2.1.1 Appliance Valve — A device that will shut-off the gas supply to the burner(s).
2.1.2 Authority Having Jurisdiction — The Authority which has been created by a statute and which, for the purpose of administering the Code/Part, may authorize a committee or an official to act on its behalf; hereinafter called the ‘Authority’.
2.1.3 Customer’s/Consumer’s Connection — Piping tapped on riser to supply each individual customer/ consumer.
2.1.4 Gas Fitter — An employee of the gas supplying organization.
2.1.5 Pilot — A small flame which is utilized to ignite the gas at the main burner(s).
2.1.6 Pressure Regulator — A device designed to lower the pressure of gas coming from the distribution main and to maintain it practically constants downstream. This normal operation pressure shall be practically in all cases that of the gas appliances used.
2.1.7 Purge — To free a gas conduit of air or gas or a mixture of gas and air.
2.1.8 Qualified Installing Agency — An individual, firm or agency which either in person or through a representative is engaged in and is responsible for the installation or replacement of gas piping on the outlet side of the gas meter, or the connection, installation or repair of gas supply piping and appliances within a building, and who is experienced in such work, familiar with all precautions required, and who has complied with all the requirements as to qualification, registration, licensing, etc, of the Authority.
2.1.9 Riser — Piping usually vertical on most of its length that supplies gas from the service to the various storeys of the building.
2.1.10 Service Pipe — Pipe that runs between the distribution main in the street and the riser in the case of multi-storeyed building or the meter in the case of an individual house.
A device installed outside the premises to cut-off the main supply of gas from pipeline by the supplier.
2.1.12 Vent Pipe — A safety device to which certain regulators are connected to evacuate outside gas that may escape from the normal circuit when some part of system gets damaged or malfunctions or a safety valve is open.
6.1 No person, unless is the employ of the gas company or having permission from the gas company, shall turn on the gas at a service shut-off valve or at any valve that controls the supply of gas to more than one consumer.
6.2 Gas shall not be turned on at any meter valve without specific permission from the gas company or other authority if any of the following conditions exists:
a) If the gas piping appliances or meter supply through the meter valve are known to leak or otherwise to be defective (see 10).
b) If required inspection of the piping or appliance has not been made.
c) If the gas company or other authority has requested that the gas be left turned off.
d) If the meter valve is found shut off for some reason not known to the gas fitter.
The gas shall not be turned on in the event of fire.
6.3 Gas shall not be turned on at any branch line valve if any of the conditions specified in 6.2 prevails. Where a branch line valve is found closed, a gas fitter shall again turn the gas on at such valve only if proper precautions to prevent leakage are taken and no other unsafe conditions are created thereby.
6.4 Gas shall not be turned on at either the meter valve or service line unless all gas keys or valves provided on all outlets in the piping system are closed or all outlets in the piping system are capped or plugged.
7.1 The gas fitter shall put the gas off to any appliance, pipe or piping system and shall leave the gas turned off, until the causes for interrupting the supply has been removed in any one of the following cases:
a) If ordered to do so by the Authority.
b) If leakage of gas is noted, which appears to be sufficient to cause fire, explosion or asphyxiation.
c) If an installation of some gas appliance is found to be such as to cause a serious hazard to persons or property.
d) If any condition exists which threatens interruption of gas supply which may cause burner outage or otherwise prove dangerous.
7.2 It shall be the duty of the installing agency when the gas supply is to be turned off to notify all affected consumers.
7.3 Before turning off the gas at the meter, for the purpose of installation, repair, replacement or maintenance of piping or appliance, all burner and pilot valves on the premises supplied with gas through the meter shall be turned off and the meter test hand observed for a sufficient length of time to ascertain that there is no gas passing through the meter. Where there is more than one meter on the premises, precaution shall be exercised to ensure that the concerned meter is turned off.