Section 2 Gas Supply
2.1 For the purpose of this Section, the following definitions shall apply.
2.1.1 Appliance Valve — A device that will shut-off the gas supply to the burner(s).
2.1.2 Authority Having Jurisdiction — The Authority which has been created by a statute and which, for the purpose of administering the Code/Part, may authorize a committee or an official to act on its behalf; hereinafter called the ‘Authority’.
2.1.3 Customer’s/Consumer’s Connection — Piping tapped on riser to supply each individual customer/ consumer.
2.1.4 Gas Fitter — An employee of the gas supplying organization.
2.1.5 Pilot — A small flame which is utilized to ignite the gas at the main burner(s).
2.1.6 Pressure Regulator — A device designed to lower the pressure of gas coming from the distribution main and to maintain it practically constants downstream. This normal operation pressure shall be practically in all cases that of the gas appliances used.
2.1.7 Purge — To free a gas conduit of air or gas or a mixture of gas and air.
2.1.8 Qualified Installing Agency — An individual, firm or agency which either in person or through a representative is engaged in and is responsible for the installation or replacement of gas piping on the outlet side of the gas meter, or the connection, installation or repair of gas supply piping and appliances within a building, and who is experienced in such work, familiar with all precautions required, and who has complied with all the requirements as to qualification, registration, licensing, etc, of the Authority.
2.1.9 Riser — Piping usually vertical on most of its length that supplies gas from the service to the various storeys of the building.
2.1.10 Service Pipe — Pipe that runs between the distribution main in the street and the riser in the case of multi-storeyed building or the meter in the case of an individual house.
A device installed outside the premises to cut-off the main supply of gas from pipeline by the supplier.
2.1.12 Vent Pipe — A safety device to which certain regulators are connected to evacuate outside gas that may escape from the normal circuit when some part of system gets damaged or malfunctions or a safety valve is open.
6.1 No person, unless is the employ of the gas company or having permission from the gas company, shall turn on the gas at a service shut-off valve or at any valve that controls the supply of gas to more than one consumer.
6.2 Gas shall not be turned on at any meter valve without specific permission from the gas company or other authority if any of the following conditions exists:
a) If the gas piping appliances or meter supply through the meter valve are known to leak or otherwise to be defective (see 10).
b) If required inspection of the piping or appliance has not been made.
c) If the gas company or other authority has requested that the gas be left turned off.
d) If the meter valve is found shut off for some reason not known to the gas fitter.
The gas shall not be turned on in the event of fire.
6.3 Gas shall not be turned on at any branch line valve if any of the conditions specified in 6.2 prevails. Where a branch line valve is found closed, a gas fitter shall again turn the gas on at such valve only if proper precautions to prevent leakage are taken and no other unsafe conditions are created thereby.
6.4 Gas shall not be turned on at either the meter valve or service line unless all gas keys or valves provided on all outlets in the piping system are closed or all outlets in the piping system are capped or plugged.
7.1 The gas fitter shall put the gas off to any appliance, pipe or piping system and shall leave the gas turned off, until the causes for interrupting the supply has been removed in any one of the following cases:
a) If ordered to do so by the Authority.
b) If leakage of gas is noted, which appears to be sufficient to cause fire, explosion or asphyxiation.
c) If an installation of some gas appliance is found to be such as to cause a serious hazard to persons or property.
d) If any condition exists which threatens interruption of gas supply which may cause burner outage or otherwise prove dangerous.
7.2 It shall be the duty of the installing agency when the gas supply is to be turned off to notify all affected consumers.
7.3 Before turning off the gas at the meter, for the purpose of installation, repair, replacement or maintenance of piping or appliance, all burner and pilot valves on the premises supplied with gas through the meter shall be turned off and the meter test hand observed for a sufficient length of time to ascertain that there is no gas passing through the meter. Where there is more than one meter on the premises, precaution shall be exercised to ensure that the concerned meter is turned off.
8.1 Installation, repair and replacement of gas piping
or appliances shall be performed only by a qualified installing agency.
8.2.1 Piping shall be of wrought iron, steel, copper or cast iron when the gas pressure is less than 7kN/m2; with higher gas pressure use of cast iron shall be prohibited.
8.2.1.1 SS 316/304/321 Flexible PE coated flexible pipe in rolls shall be permitted in low pressure system provided the pipe meets the required standard, to avoid the bends, fittings and leakages from the joint which are potential leakage points. Also, reference may be made to accepted standard [9-2(1)]. Heavy rubber flexible tube shall be permitted only as direct connection to burner from appliance valve.
Gas piping shall be of such size and so installed as to provide supply of gas sufficient to meet the maximum demand without undue loss of pressure between the meter or service regulator when a meter is not provided, and the appliance(s).
8.2.2.1 The size of gas piping depends upon the following factors:
a) allowable loss in pressure from meter or service regulator, when a meter is not provided, to appliance;
b) maximum consumption to be provided;
c) length of piping and number of fittings; and
d) specific gravity of gas.
8.2.2.2 No gas pipe smaller than 8 mm shall be used.
8.2.3 As far as possible, straight lengths of piping should be used. Where there are bends in the pipe line, these should have a radius of at least five times the diameter of the pipe.
8.2.4 For any thread joint proper sealant shall be used on male threads only.
8.3 The gas piping shall be of the colour stipulated by explosive authority to distinguish it from other piping and the piping shall be painted silver grey with red band of 150 mm width. The gas pipeline shall be painted canary yellow in case of natural gas.
Piping shall be buried to a minimum depth of 1 m or covered in a manner so as to protect the piping from physical damage.
Generally all the piping within the premises where it
has to run on the wall shall be exposed and should not be in contact with wall to ensure that no corrosion takes place. Epoxy sealant or polyethylene conduit shall be used to ensure no contact of pipe with the wall in the situation of pipe crossing the wall. Under ground or concealed gas pipeline in contact with earth or other materials which may corrode the piping shall be protected against corrosion by application of adequate corrosion resistant coating backed up by cathodic protection system.
8.5 The building shall not be weakened by the installation of any gas piping.
8.6 Gas piping in building shall be supported with pipe hooks, metal pipe straps, bonds or hangers suitable for the size of piping and of adequate strength and quality and located at proper intervals so that the piping may not be moved accidentally from the installed position.
Where gas pipe enters a building through a wall or floor of masonry or concrete, any gas piping or other piping entering the walls or floors shall be suitably sealed against the entrance of water/moisture or gas. Regarding protection of openings in walls or floors, from fire, reference shall be made to Part 4 ‘Fire and Life Safety’.
Piping in solid floors, such as concrete, shall be laid in channels in the floor suitably covered to permit access to the piping with a minimum damage to the building.
8.7.2 Single pipe without joint shall be used for wall crossing in any building.
8.8 Gas pipe shall not be bent. Fittings shall be used when making turns in gas pipe.
8.9 Generally concealed piping shall not be allowed. However, if it is necessary then it shall be under the 8.4 of underground piping and all protection such as coating, cathodic protection shall be done.
8.10 A drip shall be provided in the gas distribution system, if the moisture contents in the gas is likely to reach saturation point at any stretch of pipe line in the system; a drip shall, however, be provided at any suitable point in the line of the pipe where condensate may collect and from where it can be easily removed. This drip should be so installed as to constitute a trap where in an accumulation of condensate will shut off the flow of gas before it will run back into the meter.
8.10.1 Drip has to be provided in the case of gas consisting moisture content.
No device shall be placed inside the gas piping or fittings that will reduce the cross-sectional area or otherwise obstruct the free flow of gas.
8.12 Piping shall be electrically continuous throughout its length and properly earthed except in stretches where cathodic protection system is used for protection against corrosion. It shall not, however, be used to earth any electrical equipment.
8.12.1 The distance between gas piping and electrical wiring system shall be at least 60 mm and, where necessary, they shall be securely fixed to prevent contact due to movement. The gas piping should run above the electrical wiring. In this type of installation in the event of any leakage of natural gas, the gas would move up (natural gas being lighter than air) and would not come directly in contact with the electrical wiring. If the gas to be supplied is heavier than the air then the gas piping should run below the electrical wiring.
8.13 The distance between the gas piping and steam piping, if running parallel, shall be at least 150 mm. The gas piping should preferably run below the steam piping.
8.15 Smoking shall not be permitted when working on piping which contains or has contaminated gas.
8.16 Meters shall be installed in such a way that there shall be no load transfer from the pipeline to the inlet/ outlet of the meter and shall be easily accessible.