3.1 Pressure regulation is required to economize the sizing of piping system. Where the pressure of gas supplied to domestic system or other low pressure gas piping system in buildings is in excess of the pressure to be used in the appliance, a gas pressure regulator of suitable specification shall be installed in service pipe of each system to prevent excess pressure reaching the appliance. The pressure regulators to be used can be from 400 kN/m2 upstream pressure to 2.1 kN/m2 for domestic consumers and 10 kN/m2, 30 kN/m2, 200 kN/m2 for commercial consumers, as the case may be.
3.1.1 In some place the reduction of pressure from main distribution source of 400 kN/m2 to intermediate pressure (say 7 kN/m2) and then to operating pressure of 2.1 kN/m2 is achieved.
3.1.2 Whereas in most of the other places the reduction of pressure from main distribution source of 400 kN/m2 to directly operating pressure (say 2.1 kN/m2, 10 kN/m2, 30 kN/m2, 200 kN/m2) is achieved in single stage pressure reduction.
3.2 If located inside a building, the required regulator shall comply with the following:
a) If any of the diaphragms of the regulator ruptures, the gas shall be sent to an outlet vent pipe made of brass or plastic in order to ventilate or drain the gas out of the building. The vent pipe will, however, lead to outer air about 1 m above the topmost storey of the building. Means shall be employed to prevent water from entering this pipe and also to prevent stoppage of it by insects or other foreign bodies.
b) If the gas pressure at the outlet of the regulator falls below 50 percent of the operating gas pressure or rises above twice the operating gas pressure, the gas input to the pressure regulator shall be cut off.
c) In the event of malfunctioning of this safety device, a supplementary device shall connect the low pressure circuit to the outlet circuit (vent pipe) as soon as the exit pressure reaches 7 kN/m2.
3.3 It shall also be ensured by the supply authority that the calorific value and supply pressure of gas shall not exceed the values for the type of gas used.