24.1 Kitchen, Bathroom and Water closet:
Every kitchen, bathroom and water closet shall:-
(i) be so planned that one of its wall shall open to external air by ventilator/exhaust fan etc.;
(ii) No room containing water-closets shall be used for any purpose except as a lavatory and no such room shall open directly into any kitchen or cooking space by a door, window or other opening. Every room containing watercloset shall have a door completely closing the entrance to it.
(iii) A flue, if found necessary for a kitchen and;
(iv) In case of 4-storey building, a refuse chute may be provided. They shall be constructed with the I.S. 6024-1973 Code of practice for construction of refuse chute in multi-storey building.
Table V
Combined Ventilation Shaft for Kitchen and Toilet
| Height of the building (in floors.) | Minimum size of ventilation shaft (in sq.m.) | Minimum width of the shaft (in m.) |
|---|---|---|
| Up to 4 floors | 3.0 | 1.5 |
Provided further that no chajja shall be allowed in any ventilation shaft
Provided also that no ventilation shaft may be required for fully air-conditioned building, or mechanically ventilated toilet, kitchen, bath and water closet.
24.2 Mezzanine Floor:
In case of a Mezzanine floor the following conditions shall be provided:-
(i) It conforms to the standards of living rooms as regards lighting and ventilation in case the area of mezzanine floor is 9.5 Sq.m or more.
(ii) It is so constructed so as not to interfere under any circumstances with the ventilation of the space over and below it;
(iii) Such mezzanine floor is not sub-divided into small compartments in case of residential buildings;
(iv) Such mezzanine floor or any part of it shall not be used as a kitchen
24.3 Plinth:
The plinth of any part of a building shall be raised above ground level or road level provided adequate drainage of site is assured. In no case, this shall not be less than 0.45 meter. Every interior court-yard or garage shall be raised by a minimum of 0.15 meter above ground level and shall be satisfactorily drained.
24.4 Roof:
The roof shall be so constructed permit effective drainage of the rain water thereof by means of sufficient rain water pipes of adequate sizes, joined and fixed so as to ensure dampness does not occur in any part of the walls or foundations of the buildings or those of an adjacent building.
25. PROVISION OF LIFTS
Provision of lifts shall be mandatory for Hospitals, Nursing Homes having more than one storey. For all other buildings viz. apartments, flats etc. more than 3 floors in height provision of a lift are mandatory.