- High rise building.— For the purposes of this Chapter, ‘high rise building” means a building having a height of 16 metres or more, or with more than 4 floors (excluding basement floor(s)), other than telecommunication towers /poles.
In the case of high rise buildings, the provisions in these rules elsewhere shall apply subject to modification in this chapter.
- Safety provisions.—
(1) Staircase.—
(i) Every high rise building shall have at least two staircases, including fire escape staircases.
(ii) The height of the handrail in the staircase shall not be less than 90 centimetres and if balusters are provided no gap in the balusters shall be more than 10 centimetres wide.
(2) Guard rails or parapets:—
(i) Every balcony overlooking any exterior or interior open space shall be provided with parapet walls or guard rails of height not less than 1.50 metres and such guard rails shall be firmly fixed to the walls and slabs and may also be of blank walls, metal grills or a combination of both.
Provided that if metal grills are used they shall not be made of continuous horizontal members to prevent climbing on them:
Provided further that guard rails shall not be made of glass or any similar material which are not reinforced to prevent breaking.
(ii) The spacing between the grills/ rails should be less than 10 centimetres.
(3) Fire escape staircase.—
Every highrise building shall be provided with a fire escape stairway and shall be as specified in rule 35.
(4) Ducts: —
(i) Every opening to interior or exterior duct shall be provided with protective covering consisting of strong parapet wall having not less than 90 centimetres height from every floor level and the portion above such parapet wall shall be provided with openable and lockable shutters fixed with opaque or translucent glass which do not cause splinters when broken; the shutters shall be provided with opaque metal sheets or with metal grills or bars either in the front or on the rear.
(ii) Parapet walls of 1.2 metres height should also be provided around duct openings at the terrace level. At the top of the duct, metal grills or bars may be provided either above or below the top cover of the duct so as to reinforce the protection. The spacing between the members shall not be more than10centimetres.
(iii) All windows at a height of not less than 2 metres from ground level which can be opened to an open space either interior or exterior shall be fitted with sufficiently strong metal grills or bars in such a way that the spacing between the members is not more than 10 centimetres.
(iv) All Openings at various floor levels to vertical duct, provided for the purpose of lighting and ventilation shall be at a height of not less than 1.5 metres from the respective floor level. The openings shall be fitted with grill mesh of size not more than 10 centimetres x10 centimetres
(5) Access:—The minimum width of access to a high rise building and plot as well as the minimum existing width of the street giving access to the plot from the main street shall be 5 metres or as prescribed elsewhere in these rules, whichever is higher.
(6) Open spaces:—
(i) Clear motorable open spaces of minimum 5 metres width to facilitate fire-fighting shall be provided for the building at any two adjacent sides, of which, one is contiguous to the street/access. Such motorable open spaces shall be kept free of vehicle parking or any other erections or projections thereon other than projections of roof or weather shade or cornices of not more than 75 centimeters width. However, ramp provided as access to the basement floor can be given in this open space if through movement of fire engine is not obstructed in any way.
(ii) In case a group of buildings are to be constructed within any plot belonging to the same owner or by different owners of adjoining lands jointly, the area of the land remaining after accounting for the mandatory front, rear and side yards from the boundary of the plot shall be considered as buildable area of the plot where the buildings may be constructed subject to the conditions regarding floor space index, coverage, access, light & ventilation etc. for the whole plot, distance between the various blocks within this area shall be a minimum of 5 metres.
(iv) Adequate passage way and clearances required for fire fighting vehicles to enter the premises shall be provided at the main entrance; the width of such entrance shall be not less than 5 metres or as stipulated elsewhere in these rules, whichever is higher. If an arch or covered gate is constructed, it shall have a clear headroom of not less than 5 metres.
(7) Lift for residential apartments.—
Every high rise apartment building having more than 16 dwelling units shall be provided with at least one lift capable of carrying a stretcher:
Provided that if only one lift is required for the building as per the rule 40, that lift shall be one capable of carrying a stretcher.
(8) Parapets of terrace floor.—
Where access is provided over the terrace floor or to the terrace floor, the edges of the terrace floor shall be provided with parapet walls made of stable materials to a height of not less than 120 centimetres.
(9) Structural design.—
Application for construction or reconstruction or addition or alteration of any high rise building shall be accompanied by one set of structural design, including that regarding seismic forces as per the provisions contained in the National Building Code of India as amended from time to time and certified drawings and a structural stability certificate prepared and issued by a Structural Engineer.
Provided that the provisions regarding the height of building as specified in the National Building code of India, 2016 shall not apply to multiplexes.
(10) Safety Plan:—
In the case of High rise buildings, every application for approval shall be accompanied by safety plan suitable for the proposed construction in accordance with the Health and Safety Manual published by the Labour Department.
(11) Site supervision:—
(1) The owner shall appoint a person, registered or deemed to have been registered under the provisions of Chapter XXI, competent to supervise such works as per Appendix H2of these rules, as full time supervising professional at the site, from the commencement to the completion of the work. Such person shall have a minimum of 3 years of experience in supervising works of similar nature.
Provided that, no activities shall be undertaken at the site in the absence of such site supervising professional.
(2) The owner shall intimate the Secretary, the details of the appointed supervising professional including his/her date of appointment, photo identity proof and proof of experience along with a copy of the acceptance of appointment duly signed by the supervising professional. The owner shall also intimate the Secretary in writing about replacement, if any, of such supervising professional together with all details specified above without any delay.
Provided that if the work is executed through any person/persons or agency/agencies like developer, the responsibility of appointment of site supervising professional as stipulated in this rule shall be vested with such person/persons or agency/agencies.
(3) The supervising professional shall:—
(i) Ensure that the construction is carried out as per the approved plans, specifications and structural design.
(ii) Take adequate safety precautions at all stages of construction or reconstruction or addition or alteration or repair or demolition or removal of the various parts of the building for safe guarding the life of workers and public against hazards consequent on any aspect of the work.
(iii) Ensure that all protective works carried out to safe guard the adjoining properties during construction are sufficient and in good order to ensure safety.
(iv) Ensure at every stage of construction, that the quality of construction and/or materials used for construction is as per the specifications for that work.
(v) Ensure that the debris, construction wastes or materials are safely and clearly disposed.
82 Display of the details of the permit etc.—
(1) For the entire period of construction, the owner shall display the details of the building permit near the entrance to the site in a board of size not less than 100 centimetres X 75 centimetres. The details to be displayed include the date and the number of building permit, name and address of the owner and developer with phone number, the occupancy group of the building, the number of floors, coverage, F.S.I., area earmarked for parking in sq. metres and the use in each floor.
(2) Prior to commencement of the construction, all sides of the plot shall be covered with protective fencing and screen to ensure safety and convenience of the adjoining properties. Such protective fencing and screen shall be retained throughout the construction period.
(3) Adequate safety measures shall be ensured by the owner and the developer for protection against damage to health, life, buildings and property of the inhabitants around, during and after building construction and land development. The owner and developer shall be solely responsible for any such damages.