(1) Sanitation facilities to be provided for occupancies other than Group A1shall be provided in numbers not less than those stipulated in Table 14and Table 15, as the case may be. The occupant load for this purpose shall be computed at the rate given in Table13.
TABLE 13OCCUPANT LOAD FOR CALCULATING SANITATION REQUIREMENTS
Sl.No
Occupancy
Built-up area in sq. metres/person
1
Group A2, B, C,E and F
5.9
2
Group D and J
1.8
3
Group G1 , G2 , H and I
30
Note :—It may be assumed that 2/3 of the number are males and 1/3 are females.
TABLE 14SANITATION REQUIREMENTS
Sl. No
Fitments
Assembly occupancy and Multiplex complex,
Assembly
Assembly
Assembly
Theatres, Auditorium, Art Galleries, Libraries, Restaurants, Wedding halls, Community halls
Bus Terminal
Railway Station
Air ports
(1)
(2)
(3)
(4a)
(4b)
(4c)
1
Water Closet
1 per 200 males or part thereof and 1 per 100 females or part thereof for the first 1000 sq. meters of built up area and 1 per 400 males or part thereof and 1 per 200 females or part thereof for the remaining area.
4 for first 1000 persons and 1 for every subsequent 1000 persons or part thereof
5 for first 1000 persons and 1 for every subsequent 1000 persons or part thereof
5 for first 1000 persons and 1 for every subsequent 1000 persons or part thereof
2
Urinals
1 per 50 persons or part thereof for the first 1000 sq. meters of built up area and 1 per 100 persons or part thereof for the remaining area.
6 for first 1000 persons and 1 for every subsequent 1000 persons or part thereof
6 for first 1000 persons and 1 for every subsequent 1000 persons or part thereof
6 for first 1000 persons and 1 for every subsequent 1000 persons or part thereof
3
Wash Basin
1 for every 200 males and 1 for every 200 females for the first 1000 sq. meters of built up area and 1 per 400 males and 1 per 400 females or part thereof for the remaining area.
4 wash basins in each male and female toilet stalls
4 wash basins in each male and female toilet stalls
4 wash basins in each male and female toilet stalls
4
Bath
Sl. No
Fitments
Hotels
Storage occupancy
Boarding Institutions/Hostels/Dormitories
Other educational institutions
Office/mercantile occupancies
Industrial occupancy
(5)
(6)
(7)
(8)
(9)
(10)
1
Water Closet
1 per100males and 1 per 100 females
1 per 50 males and 1 per 25 females
1 per every 10 boys and 1 per every 8 girls
1 per every 40 boys and 1 per every 25 girls
1 for every 25 males or part thereof and 1 for every 15 females or part thereof
1 per every 25 males and 1 per every 15 females
2
Urinals
1 for every25persons or part thereof
1 per 100 males or part thereof
1 per every 25 boys
1 per every 50 boys
1 for every 25 persons or part thereof
1 per every 25 persons or part thereof
3
Wash Basin
1 for every25persons or part thereof
1 per every 10 boys and 1 per every 10 girls
1 per every 40 boys and 1 per every 40 girls
Preferably one on each floor
4
Bath
1 per100persons
1 per every 10 boys and 1 per every 10 girls
As required for particular trades or occupancy
TABLE 15SANITATION REQUIREMENTS FOR MEDICAL/HOSPITAL OCCUPANCY
Sl.No
Fitments
Hospitals with indoor patients ward
Hospitals with outdoor patients
Administration Building
For males and females
For males
For females
For males personnel
For females personnel
(1)
(2)
(3)
(4)
(5)
(6)
(7)
1
Water Closet
One for every 8 beds or part thereof
One for every100 persons or part thereof
Two for every 100 persons or part thereof
One for every 25 persons or part thereof
One for every 15 persons or part thereof
2
Ablution taps
One in each water closet plus one water tap with draining
One in each water closet. One water tap with draining arrangement shall
One in each water closet. One water tap with draining arrangement shall be provided
arrange-ment in the vicinity of water closets and urinals for every 50 beds or part thereof
be provided for every 50 persons or part thereof in the vicinity of water closets and urinals
for every 50 persons or part thereof in the vicinity of water closets and urinals
3
Wash Basins
Two up to 30 beds; add one for every additional 30 beds or part thereof
One for every 100 persons or part thereof
One for every 25 persons or part thereof
4
Baths with shower
One bath with shower for every 8 beds or part thereof
One on each floor
5
Bed pan washing sink
One in each ward
6
Cleaners sink
One in each ward minimum
One per floor minimum
One per floor minimum
7
Kitchen sink and dish washers (where kitchen is provided)
One in each ward minimum
8
Urinals
One for every 50 persons or part thereof
Nil up to 6 persons, 1 for 7-20 persons, 2 for 21-45 persons, 3 for 46-70 persons, 4 for 71-100 persons From 101 to 200 persons add at the rate of 3%. For over 200 persons add at the rate of 2.5%.
Provided that in the case of Information technology parks / technology parks sanitation requirements shall be that of 75 % of the office occupancy.
(2) The Minimum sanitation facilities to be provided in hazardous buildings shall be as given below:
(a) at the rate of one water closet for the first 50 males or part thereof and two water closet for the first 50 females or part thereof and thereafter one water closet for every additional 70 persons or part thereof, whether male or female;
(b) at the rate of one urinal for every 100 males or part thereof ;
(c) at the rate of one drinking water fountain for every 100 person or part thereof;
(d) at the rate of one washing facility for 50 persons or part thereof; and
(e) In cases where the total number of workers does not exceed 5, at least one water closet shall be provided.
Chapter VParts of Building
Mezzanine floor.—(1) The built-up area of mezzanine floor shall not exceed one third area of the main floor or room accommodating the mezzanine floor.
(2) The clear headroom beneath and above the mezzanine floor shall not be less than 2.2 metres.
Height of room.— The height of room intended for human entry in a building other than residential occupancy and livestock/poultry farm shall not be less than 3 metres: Provided that in the case of air conditioned rooms it shall not be less than 2.4 metres.
Sanitation Facilities:—
(1) Size of bathroom and latrine.—
(1) The area of bathroom shall not be less than 1.50 sq. metres with either side not less than1.1m, area of a latrine shall not be less than 1.10 sq. metres with one side not less than 1.0 metre:
Provided that the area of combined bathroom and latrine shall be not less than 2.2 sq. metres with one side not less than 1. 1 metres:
(2) The height of bathroom or latrine shall be not less than 2.20metres.
(2) Water closet.—Every building above 50 square metres of build up area shall be provided with at least one water closet.
35Staircases and fire escape staircases.-—
(1) Staircases.—
(1) Any building having more than one floor shall be provided with a staircase unless each such floor is independently accessible from ground.
(2) The number and width of stair shall be determined with respect to the occupant load as table 16 of these rules and maximum travel distance between two stairs shall not be less than 60m.
(3) For such stair:-
(a) minimum width of stair shall be 120 centimeters,
(b) minimum width of tread shall be 30 centimeters,
(c) maximum height of riser shall be 15 centimeters
(d) minimum height of handrail shall be 90 centimeters
The minimum headroom in a passage under the landing of a staircase and under the staircase shall be 2.2m.
(5) Any building having more than three floors including basement floor(s) shall have at least two staircases, one of which may be a fire escape staircase:
(6) Escalators can be provided instead of staircases. The width of such escalators shall not be less than one metre.
(2) Fire escape staircase:—
(1) Fire escape staircase shall be provided for every building under:—
(a) Residential occupancy exceeding three storeys above ground level;
(b) Non-residential occupancies exceeding two storeys above ground level
Note:—Fire escape staircase is one which is connected to public areas and/or common areas on all floors and leads directly to exterior open space at ground, has at least one side abutting external wall, this side being provided with openable glass or break open glass or fully open and has landing areas accessible from the external side to facilitate rescue operations during an emergency.
(2) Width of fire escape staircase shall not be less than one metre
(3) Tread shall not be less than 25 centimetres
(4) Riser shall not exceed 19 centimetres and the number of risers shall not exceed 16 per flight of stairs
(5) Height of handrail of a fire escape staircase shall not be less than 100 centimetres and not more than 120 centimetres.
(6) The spacing between the balustrades should be less than 15 centimetres.
(7) The use of spiral staircase shall be limited to buildings up to 10 metres in height. Spiral staircase shall not be less than 150 centimetres in diameter and shall be designed to give adequate head room.
(8) Fire escape stairs shall have straight flight for building exceeding 10 metres height
(9) Entrance to fire escape stair shall be separated and as far as possible remote from other staircase(s) if any.
(10) If the staircase provided for the building up to three storeys satisfies the provisions of fire escape stair also, no separate fire escape stair is needed.
(3) Ramps.—
Ramps, if provided as a substitute for stairways, shall be laid with a slope not exceeding 1 in 10 and such ramp shall comply with all requirements of a stairway and shall be surfaced with approved non-slippery materials.
Travel distance to emergency exit.—(1) Every building meant for human occupancy shall be provided with emergency exit sufficient to facilitate safe escape of occupants in case of fire or other emergency.
(2) Emergency exits shall be located in such a way that the travel distance on each floor shall not exceed 30 metres for every occupant.
(3) Emergency exists may be either horizontal or vertical.
(4) Emergency exits in the case of ground floor may be a doorway, corridor or passage to an internal staircase or external staircase, ramps to the street or to the roof of a building,which may be horizontal exits leading to the ground or adjoining building at the same level. In the case of upper or lower floors, emergency exits may be a staircase leading to the ground.
Provided that lifts and escalators shall not be considered as emergency exits.
Exit Width.—(1) The unit of exit width used to measure the capacity of any exit shall be 50 centimetres, a clear width of 25 centimetres shall be counted as an additional half unit and clear width less than 25 centimetres shall not be counted for exit width.
(2) Occupants per unit exit width shall be as in Table 16.
TABLE 16OCCUPANTS PER UNIT EXIT WIDTH
Sl. No.
Group of occupancy
No. of Occupants per unit exit width of Stairway
No. of Occupants per unit exit width of Doors
(1)
(2)
(3)
(4)
1
Group A1 Residential
25
75
2
Group A2 Lodging Houses & Special residential
50
75
3
Group B Educational
25
75
4
Group C Medical/Hospital
25
75
5
Group D Assembly
60
90
6
Group E Office
50
75
7
Group F Mercantile (Commercial)
50
75
8
Group G1 Industrial-I
50
75
9
Group G2 Industrial-II
50
75
10
Group H Storage (including Warehousing)
50
75
11
Group I Hazardous
25
40
12
Group J Multiplex complex
50
75
(3) For determining the exit width required, the number of persons in any floor or the occupant load shall be based on the actual number of occupants but in no case less than that specified in Table 17.
TABLE 17OCCUPANT LOAD
Sl. No.
Group of occupancy
Occupant Load (built up area in square metres per person)
(1)
(2)
(3)
1
Group A1 Residential
12.5
2
Group A2 Lodging houses & Special residential
4.0
3
Group B Educational
4.0
4
Group C Medical/Hospital
15.0
5
Group D Assembly
1.5
6
Group E Office
1.5
7
Group F Mercantile (Commercial)
4.5
8
Group G1 Industrial-I
10.0
9
Group G2 Industrial-II
10.0
10
Group H Storage (including Warehousing)
30.0
11
Group I Hazardous
10.0
12
Group J Multiplex complex
4.5
(4) Exits shall be either horizontal or vertical type.
(5) An exit may be a doorway corridor or passageway to an internal staircase or an external staircase (upstairs, downstairs or both), or a ramp which has access to the street or to the roof of a building;
Provided that lifts and escalators shall not be considered as exits.
(6) For determining the exit width of staircases, the width of one flight of stair is considered.
Doorways.—(1) Every exit doorway shall open into an enclosed stairway or a horizontal exit or a corridor or passageway providing continuous and protected means of egress.
(2) No exit doorway shall be less than 75 centimeters in the case of residential and 1.2metres in the case of all other occupancies.
(3) Revolving door shall not be provided as a means of fire exit.
Corridor, verandahs and passageways.— The clear width of any corridor, verandah or passageway in any building shall be not less than 1.0 metre at any point. The width of passages giving access to the staircase shall not at any point be less than the width of the stair.
Lift /Escalator.—(1) Any building exceeding three storeys in the case of group C-Hospital/medical occupancy and four storeys in the case of other occupancies shall have at least one lift:
Provided that, additional lift shall be provided at the rate of one lift for every 2500 sq. metres of the total built up area or part thereof (except parking area provided inside the building) in excess of the first 4000 square metres, or by adopting the provisions in the National Building Code for calculating the number of lifts/ escalator, in which case, the respective registered engineer, architect etc. shall furnish certificate, design calculation and specifications all duly signed, along with the application for building permit. The certificate shall be to the effect that the lifts/ escalator provided conform to the provisions of the National Building Code
(2) The planning, design and installation of lifts / escalator shall be in accordance with Part 8, Volume 2, Section 5 in National Building Code of India, 2016.
Whenever more than one lift is required as per sub-rule (1) or bye laws made under the Act, at least one lift shall be a higher capacity lift that can carry a stretcher.
(4) In the case of high-rise apartment building having more than 16 dwelling units, at least one lift capable of carrying a stretcher shall be provided:
Lighting and Ventilation.—(1) Every habitable room shall be furnished with sufficient number of openings such as windows and ventilators affording effectual means of admission of light and air by direct communication with the external air or shall be sufficiently lighted and ventilated by artificial means.
(2) No portion of a room shall be assumed to be lighted if it is more than 7.5 metres away from the opening assumed for lighting that portion unless it is artificially lighted.
(3) Windows and ventilators which open into a verandah shall be deemed to communicate with the external air, if such verandah is not more than 3 metres wide and open throughout its entire length into an open space open to the sky, the width of suchopen space being not less than 3.0 metres. Trellising, mesh, grill or net may, however, be provided on the open side of the verandah;
(4) Every kitchen shall be ventilated according to the standards stipulated for habitable rooms and shall have suitable flue for the escape of smoke and heated air unless it is provided with an approved form of smokeless installation.
(5) Every bathroom or latrine shall be provided with sufficient light and ventilation.—
(6) Every bathroom or latrine shall have at least one of its walls abutting on an open space or open verandah or an air shaft if not centrally air conditioned; the size of air shaft shall not be less than that specified in Table 18.
TABLE 18SIZE OF AIR SHAFT
Sl. No.
No. of Storeys
Area of the airshaft in Square metre
Minimum width of Airshaft in metre
(1)
(2)
(3)
(4)
1
Upto 3
1.08
0.9
2
Upto 6
2.4
1.2
3
Upto 10
3.0
1.5
4
Above 10
5.0
2.0
(7) All buildings coming under the purview of sub rule (5) of Rule5 shall also follow the lighting and ventilation standards mentioned in the KSECBC
Provisions for Differently-abled, Elderly and Children.—All buildings under occupancy groups A2, B,C,D, E,F and J which have access to the public and all apartment buildings/residential flats under occupancy group A1 shall be provided with the following facilities for the differently-abled, elderly and children:
(1) Every such building shall have easy access to the main entrance through a ramp.
(2) Every public building exceeding 1000 sq. metres and residential flats exceeding 2500 sq. metres built-up area shall have lift or separate approach through a ramp (intended for the differently-abled and elderly) to each floor. The minimum cage dimensions of such lift shall be as follows:
(i) Clear internal width 110 cm
(ii) Clear internal depth 200 cm
(iii) Entrance door width 90 cm
(3) The maximum gradient of any ramp approach intended for the differently-abled, elderly and children shall not exceed 1 in 12 and shall be finished with non-slippery material. The minimum width of ramp shall be 120 cm. and provided with handrails of 80 cm height on both sides. Minimum gap from the adjacent wall to the hand rail shall be 50mm. The slope of all such ramps shall be constant within a building. Entrance landing shall be provided adjacent to ramp with the minimum dimension 120 cm x 150 cm.
(4) Toilets:—
A minimum of one special water closet shall be provided for the use of the differently-abled and elderly with essential provision of a wash basin at an easily accessible location with proper signages:
Provided that in the case of such special toilets:
(a) These shall be provided at the ground floor for A1, A2,B,C,D,E, F & J occupancies and at every floor in multiples of three for A2,B,C,D,E, F& J occupancies.
(b) Minimum size of toilet shall be 1.50 m x 1.75 m.
(c) Minimum clear opening of the door shall be 90 cm. wide, the door shall swing out, or be sliding or folding type.
(d) Suitable arrangements of vertical/horizontal handrails with 5cm. clearance from the wall shall be provided in the toilet.
(e) The water closet seat shall be 50 cm. above from the floor level:
(f) At least one sink in each floor shall have a knee room of 70cm. high under the sink; and
(g) Locks of such toilet doors shall be of a type that can be opened from outside in case of emergency.
(5) Parking facilities
(a) 3% of the required parking subject to a minimum of one car space, shall be provided near the entrance, exclusively for use of the differently-abledwith maximum travel distance of 30 metres, from the building entrance.
(b) The width of such parking bay shall be at least 3.6 metres.
(6) Walks and paths:
(a) Walks shall be smooth with hard level surface suitable for walking and wheeling. Avoid grates and manholes in walks. If grates cannot be avoided, then bearing bar shall be perpendicular to the travel path and opening between bars shall not be greater than 12mm in width.
(b) The walkway shall not cross vehicular traffic.
(7) In Group A2 Lodging Houses and Special residential, one room for every 25 rooms or part thereof shall be set apart for the differently-abled.
(3) Segregated sanitation for Visitors in Public Buildings
(a) In respect of the following new buildings, special segregated sanitation facilities as separate block shall be provided within the plot, in a conspicuous location, outside the main building block(s):
(i) Civil stations, Municipal offices, Taluk offices, village offices
(ii) Any other office in plots owned by Government or Municipality as decided by the Government or municipality respectively from time to time;
(iii) Hospitals with total built-up area more than 1000 sq. metres;
(iv) Bus stations, railway stations, air ports and public water transport terminals.
(v) Automobile fuel filling stations
(b) Such sanitation facility shall be at least 10 percent of the sanitation requirement stipulated in Tables 14 and 15 for water closets, urinals and wash basins subject to a minimum of one WC, urinal and washbasin each for male, one WC and washbasin each for female and one WC and washbasin each for disabled persons. The minimum standards for WC and Washbasin for disabled shall be as provided in rule 42.
(c) It must be accessible to visitors and general public during the operational hours of the building.
(4) As far as possible, low water consumption plumbing fixtures shall be provided in all buildings.
(5) In the case of Government owned Information Technology Parks, Government approved Private Information Technology Parks, Government approved private Information Technology buildings under Group E occupancy, additional sanitation facilities for visitors need not be provided.