Angle of inclination.- The angle of inclination of an escalator shall normally be not in excess of 30 degrees from the horizontal. In exceptional circumstances, it may be permitted up to 35 degrees but vertical rise in any case should not exceed 6 meters;
-
Width of escalators.- The width between balustrades shall be measured on the incline at a point 68.5 centimeter vertically above the nose line of the steps, and shall not be less than the width of the step. It shall not exceed the width of the step by more than 33 centimeter with a maximum of 16.5 centimeter on either side of the escalator.
-
Balustrading-(1). Escalators shall be provided on each side with solid balustrading. On the step side the balustrading shall be smooth and substantially flush except for protective moulding parallel to the run of the steps and properly bevelled vertical mouldings projecting not more than 6.5 millimeters, that cover joints of panels;
(2). Glass panels when used in balustrade shall be laminated;
(3) There shall be no abrupt changes in the width between the balustrading on the two sides of the escalator. Where a change in width is unavoidable, such change shall not exceed 8 percent of the greatest width. In changing the direction of the balustranding resulting from a reduction in width the maximum allowable angle of change in balustrading shall not exceed 15 degree from the line of escalator travel;
(4) The clearance on either side of the steps between the steps and the adjacent skirt guard shall not be more than 5 millimeters and the sum of the clearance on both sides shall not be more than 6 millimeters;
(5) A solid guard shall be provided in the intersecting angle of the outside balustrade (deck board) and the ceiling of soffitt except where the intersection of the outside balustrade (deck board) and the ceiling of soffitt is more than 60 centimeters from the centre line of the handrail;
The vertical face of the guard shall project at least 36 centimeter horizontally from the apex of the angle;
The exposed edge of the guard shall be rounded to eliminate shear hazard. Guards may be of shatter proof glass.
- Hand rail:- (1). Each balustrade shall be provided with a hand rail moving in the same direction and at substantially the same speed as the steps.
(2). Proper arrangement shall be made to prevent trapping of an object between the handrail and the balustrading or between the steps and the balustrading:
(3). Each moving handrail shall extend at normal handrail height not less than 30 centimeters beyond the line of points of the comb plate teeth at the upper and lower landings;
(4). Hand or finger guards shall be provided at the point where the hand rail enters the balustrade;
(5). The horizontal distance between the centre lines of the two-hand rails, measured on the incline, shall not exceed the width between the balustrades by more than 15 centimeters with a maximum of 7.5 centimeters on either side of the escalator.
- Step treads and landings:- (1). Step frame shall be made of incombustible material. Step treads shall be horizontal and made of incombustible material and shall afford a secure foothold.
(2) If the landing is of concrete, it shall have edge insertions of metal, wood or other anti slip material;
(3) The depth of any step tread in the direction of travel shall be not less than 40 centimeters and the rise between treads shall be not more than 22 centimeters. The width of a step tread shall be not less than 40 centimeters and not more than 102 centimeters;
(4)The maximum clearance between step treads on the horizontal run shall be 4 millimeters;
(5) The tread surface of each step shall be slotted in a direction parallel to the travel of the steps. slot shall be not more than 6.5 millimeters wide and not less than 9.5 millimeters deep and the distance centre of adjoining slots shall be not more than 9.5 millimeters. Each from
- Comb plates.- (1) There shall be a comb plate at the entrance and at the exit of every escalator.
(2). The comb plate teeth shall be meshed with and set into slots in the tread surface so that the points of the teeth are always below the upper surface of the treads;
(3). Comb plates shall be adjustable both horizontally and vertically. Sections forming the comb plate teeth shall be readily removable without the use of special tools in case of emergency;
- Trusses or girders.-(1) The factor of safety based on the static loads shall be atleast as follow:
(a) For trusses and all structural members including tracks -five.
(b) For driving machine parts.
(i) Where made of steel, or bronze.
(ii) Where made of cast iron or other materials
(c) For power transmission members
Step change composed of cast steel links which, if thoroughly annealed shall be permitted with a factor of safety of twenty.
(2) The escalator truss or girders shall be designed to safely sustain the steps and running gear in operation. In the event of failure of the track system it shall retain the running gear in its guides.
-
Track arrangement.- Step wheel track shall be so designed as to prevent displacement of the steps and running gear if a step chain breaks.
-
Capacity and loading.-The rated load in kilograms on an escalator shall be computed as follows:
Rated load = 2.7 WA
Where W = The width in centimeter between the balustrades and A = The horizontal distance between the upper and lower comb plate teeth in meter.
-
Limits of speed:-The rated speed of the escalator shall not be more than 38 meters per minute
-
Application of power, driving machine, motor and brake. (1) The driving machine shall be connected to the main drive shaft by toothed gear, a coupling, or a chain;
(2)An electric motor shall not drive more than one escalator;
(3) Each escalator shall be provided with an electrically released, mechanically applied brake capable of stopping the up or down travelling escalator with any load upto rated load. This brake shall be located either on the driving machine or on the main drive shaft;
(4) Where a chain is used to connect the driving machine to the main drive shaft, a brake shall be provided on this shaft. If an electrically released brake is provided on the driving machine, it may not be necessary of electrically released type.
-
Chain.-All chains shall have a factor of safety not less than ten. Material requiring periodical heat treatment shall not be used for chains.
-
Safety Devices:-(1). Where starting pushes or switches are within reach of the public they shall be either be the key-operated type or be enclosed in a box provided with a lock and key and shall be located within sight of the escalator steps.
(2). (a) An emergency "Stop" push or switch conspicuously marked "STOP PUSH" or STOP SWITCH and accessible to the public shall be fixed at the top and bottom landings of each escalator;
(b)The operation of a stop push or switch shall open a circuit and cause the power supply to the escalator to be disconnected. It shall not be possible to start the escalator by means of such pushes or switches;
(c) Any escalator operating the ascending direction shall be equipped with means to cause the power supply to the escalator to be disconnected and the brake applied in the event of accidental reversal of direction of travel
(3). A speed governor shall be provided, the operation of which shall cause the interruption of power to the driving machine should the speed of the steps exceed a predetermined value which shall be not more than 40 percent above the rated speed.
Provided that the over speed governor is not required where a low slip alternating current squirrel cage induction motor is used and the motor is directly connected to the driving machine.
(4). A broken step chain device shall be provided which shall cause the interruption of power to the driving machine if a step chain breaks and where automatic chain tension device is not provided, it shall cause the interruption if excessive sag occurs in either of the step chain;
(5). Where the driving machine is connected to the main drive shaft by a chain, a broken drive chain device shall be provided to cause the application of the brake on the main drive shaft of the drive chain parts;
(6). Stop switch in machinery area:- (A) A stop switch shall be provided around machinery area where means of access to the space is provided. This switch, when opened, shall cause electric power to be cut off from the escalator driving machine motor and brake. The stop switches shall be-
(a) Of the manually opened and closed type;
(b) Conspicuously and permanently marked STOP and;
(c) Positively opened mechanically and their opening shall not be solely dependent on springs;
(B) Escalators driven by polyphase motor shall be protected against phase reversal or phase failure;
(7). An electrically released brake shall automatically stop the escalator when any of the safety devices required under sub rules (2), (3), (4), and (5) of this rule come into operation.
H-537-10
- Machine room.-(1). A machine room of suitable size and construction shall be provided for the housing of the escalator machines, and associated apparatus and equipment.
(2). The machine room shall be of sound construction, weather proof and dry and shall be properly ventilated to prevent any undue rise in temperature inside the room. Necessary means shall also be provided to maintain a reasonable temperature in the machine room. The floors of the machine rooms shall be capable of carrying the load of the escalator machinery and other equipments housed therein;
(3). The machine room shall be arranged to allow reasonable access to and the removal of the equipments therein or of any part thereof. The height of machine room shall be sufficient to allow any part of the equipment to be accessible and removable for repairs and replacement;
(4). Safe and convenient access to machine room entrances shall be provided with access doors opening outwards;
(5). The machine room shall not be used as store room or for any other purpose other than housing the escalator machine and associated apparatus and equipment. No inflammable or explosive material shall be kept in the machine room;
(6) The machine room shall be kept locked, which shall be accessible only to an authorized person. The key of the machine room shall be kept in the custody of the owner or his agent and shall be made readily available for repairs, maintenance or inspection. A danger notice in Hindi or English and Gujrati with sign of skull and bones shall be affixed on the outside of the door and in a conspicuous position near the machinery.
-
Lighting of step treads.-Step treads shall be illuminated throughout their run. The light intensity on the tread surfaces shall be not less than 20 Lux. The illumination shall preferably be of uniform intensity and it shall not contrast materially with that of the surrounding area.
-
Access to interior of escalator.-Reasonable access to the interior of the escalator shall be provided for inspection and maintenance.
-
Tests.-(1) No new escalator shall be brought into use unless the escalator has been tested as follows.
(a). Site tests of escalators :- Each type and size of escalator shall be tested for the rated load that is designed to carry;
(b). Over speed test;-The application of the over speed safety device shall be obtained by causing the escalator to travel at the governor tripping speed as specified in sub rule (3) of rule 64. With escalators driven by alternating current motors, the governor may be tripped by hand with the escalator traveling at its normal speed;
(c) Reversal test:-The accidental reversal device as provided in Sub-rule (2) (c) of rule 64 shall be made to function by manually operating or attempting to operate the escalator in the reversal direction.
(d) Broken chain test.-The application of the broken chain safety device as provided in Sub-Rule (4) of Rule 64 may be obtained by operating the device by hand. Broken drive chain device operation of the broken drive chain device required by sub rule (5) of rule 64, where a device chain is used, shall be tested by operating the actuating device by hand.
(e) Stop buttons: -The emergency stop buttons required by sub rule (2) (a) of Rule 64 operated in each direction of the travel;
(2) The person authorized under section 13 for the erection of the escalator shall certify in writing that all the tests specified in these rules are carried out by him to determine the suitability of the escalator for the normal and regular service and if required by the Inspector such tests may also be carried out by him.
- Other precautions.-(1) Adequate precautions shall be taken to guard against any possibility of an escalator being operated by un-authorized persons. Precautions shall also be taken to prevent an escalator from being operated by any person when it is not intended for use.
(2) An attendant shall be on duty in the premises where an escalator is installed during the whole period the escalator remains in use;
(3) Where an escalator is under examination or repairs suitable steps shall be taken to ensure that the escalator is not operated inadvertently by any person in such a manner which may endanger the safety of persons working in the escalator;
(4) Explosive or other inflammable materials shall not be carried in the escalator as may endanger the safety of persons;
(5) The escalator machine room shall be provided with a suitable fire extinguisher;
(6) Escalator pit pans shall be periodically cleaned of oil and refuse;
(7) All parts of the machine and equipment requiring lubrication shall be lubricated at regular periodical intervals with lubricants of standard grade;
(8) The sides and undersides of escalator trusses and machinery area shall be enclosed in fire resistive materials. Means shall be provided for adequate ventilation of the driving and driven machine and control spaces;
(9) Floor openings for escalator shall be protected against the passage of flame, smoke or gases in the event of fire.