LIETS
- Lift wells - (1) Every lift well intended for the installation of the lift or any equipment necessary for its maintenance shall be exclusively reserved for that purpose and shall not be used for any other purpose;
(2) The inner sides of a lift well shall, so far as practicable, form a smooth, continuous flush surface devoid of projections or recesses. Where any projections extending inwards from the general surface of the enclosure at or near openings or landing cannot be rendered flush, then they shall be leveled on the underside to an angle of not less than 60 degree from the horizontal by means of metal plates, cement rendering, or other suitable fire resisting materials;
(3) Where there is more than one lift in common well, minimum allowance of 100 millimeters for separator beam shall be made in the widths shown in tables 1 to 4 of rule 43;
(4) Where there is more than one lift in common well, a suitable separator screen through out the whole height of lift well having adequate strength shall be fixed in the lift well to protect the person working in the lift well or in the lift car, from accidental contact with counter weights and other lift car at any stage of their travel;
(5) No room, passenger way or thoroughfare shall be provided under any lift well except in case of the lift having counter weight fitted with over speed governor safety device;
(6) Where a lift car leveling device is operative with the lift car gate opening such interior surfaces shall always form a smooth flush surface below each landing level for a depth to at least the depth of the car leveling zone plus distance through which the lift car may travel of its own momentum when power is cut off;
(7) Sufficient space shall be provided between the guides for the car and the side walls of the lift well enclosure to allow safe and easy access to the parts of the safety gear for their maintenance and repairs;
(8) A notice with the word "lift" shall be placed on the outside of each landing door.
- Lift well enclosures. (1) Except as provided in sub-rule (2) every lift well shall be protected by a substantial fire resisting enclosure extending on all sides and fitted with gates or doors. The enclosure shall
be so constructed that no person may fall down in the lift well or come into contact with any moving part of the lift when the gates of doors are shut;
(2) Where fire-resistance construction cannot be provided, the lift well shall be enclosed to a height of not less than 2.00 meters or such greater height as may be recommended by the Chief Inspector;
(3) Where wire grill or similar construction is used, the mesh or opening shall not be greater than 3 centimeters. and the lift well enclosure shall be of sufficient strength to resist accidental impacts by users of the staircase or adjoining floors, and in the case of goods lift, by movements of materials in the vicinity;
(4) Where the clearance between the inside of an open type lift well enclosure and any moving or movable part of the lift equipment or apparatus is less than 5 centimeters, the openings in the enclosure shall be further protected by netting of square mesh not greater than 10 millimeters. and of wire not smaller than 1 millimeter or in a manner approved in writing by the Chief Inspector;
(5) There shall be no opening in the lift well enclosure permitting access to the lift car by passing under the counterweight;
(6) In the construction of lift well enclosure glass shall not be used. However condition may be relaxed in case of specially designed, well protected, fully transparent laminated type, sandwich safety glass construction or poly carbonate material sheet construction as may be permitted by the Chief Inspector. A certificate from the qualified structural engineer regarding the proper fixation in respect of such type of construction shall be submitted along with the application for renewal of licence;
(7) Lift wells and wells for the counterweight, if located independently of the lift well, shall be adequately protected by means of suitable enclosure work which shall be extended on all sides from floor to ceiling;
(8) In all counter-weight wells located independently of the main lift well, suitable access shall be provided for the inspection, maintenance and repairs to counter-weights, wire ropes and their anchorages, guides and guide supports;
(9). All such doors giving access to such counter-weight wells shall be provided with electro-mechanical locking devices;
(10) No counter weight shall be allowed to travel in any lift well or part of any lift well other than that to which it belongs;
(11) The lift well enclosure on the sides facing any lift car entrance shall so far as is practicable, be not more than 25 millimeters from the edge of the lift car platform;
(12) The walls enclosing lift well in the buildings having height more than 30 meters shall have fire resistance of not less than two hours. The lift well shall have permanent vents immediately under the machine room not less than 0.2 square meter in clear area;
(13) The lift well for fire lift (a lift to enable fire brigade personnel to get to the upper floors with the minimum delay and to be used exclusively by firemen in an emergency and directly accessible to every landing on every floor), in the building having more than 30 meters height shall be segregated from the other lift wells by means of brick masonry or R.C.C. wall of a fire resistance of not less than two hours;
(14) Fire lift in a building having more than 24 meters travel, shall work at or above the speed of 1.0 meter per second so as to reach the top floor from ground level within one minute;
(15) Thickness of the lift enclosure wall shall be of minimum 150 millimeters for R.C.C structure or 250 millimeters for brick construction;
H-537-4
(16). Capsule lifts as well as glass lifts shall not be allowed to be installed "open to sky" Whenever installed in house, following provisions shall apply.
(a) lift well enclosure of this type of lifts shall have partial covering on one side in which capsule lift protruding structure moves. The area immediately beneath this side of the lift enclosure shall be declared as no man area and shall be provided with adequate guarding.
(b) In case of glass lift, one side of the lift enclosure shall have laminated glasses of minimum 8 millimeters thickness. The area beneath this side of the lift enclosure shall be declared as no man area and shall be provided with adequate guarding.
- Lift pit :- (1) A pit of adequate depth shall be provided for every lift below the level of its lowest landing;
(2) The lift pit shall be so constructed as to be capable of withstanding the impact of the lift car with the rated load or the impact of the counter-weight when either is descending at rated speed or at governor tripping speed in case governor operated safety gear is used;
(3) Where the pit depth exceed 2 meter, suitable access shall be provided by a ladder or any other suitable device and light point with a switch along with a car control switch at entrance level shall also be provided for facility of maintenance and repair work.
- Bottom and top car clearances:-(1.) Bottom car clearance :- When the car rests on its fully compressed buffer, there shall be a vertical clearance of not less than 600 millimeters between the pit floor and the buffer striker plate or the lowest structural or mechanical part, equipment or device installed. This clearance shall be available beneath the whole area of the platform except for guide shoes or rollers, safety jaw blocks, platform aprons, guards or other equipment located within 300 millimeters measured horizontally from the sides of the car platform; and compensating sheaves :
Provided that in all the cases, including small cars, a minimum clearance of 600 millimeters is available over a horizontal area of 800x 500 millimeters:
Provided also that in all the cases, when the car rests on its fully compressed buffers, there shall be a horizontal clearance of not less than 50 millimeters. between any part of the car and any obstruction of device mounted in the pit.
(2) Top car clearance :- The vertical clearance between the car cross head and the nearest overhead obstruction within 500 millimeters measured horizontally to the nearest part of the cross head when the car platform is in level with the top landing, shall be not less than the sum of the following;
(a) The bottom counter - weight runby :
(b) The stroke of the counter-weight buffer used :
(c) One half of the gravity stopping distance based on :
(d) 115 percent of the rated speed where oil buffers are used and no provision is made to prevent the jump of the car at counter weight buffer engagement, and.
(e) Governor tripping speed where spring buffers are used.
Note:-The gravity stopping distance based on the gravity retardation from any initial velocity be calculated according to the following formula :
S = 5 / V ² (V square)
Where
S= free fall in millimeters (gravity stopping distance), and
V= initial velocity, in meter per second.
(d) 600 millimeters.
Where there is a projection below the ceiling of the well and the projection is more than 500 millimeters, measured horizontally from the center line of the cross head, but over the roof of the car, a minimum
vertical clearance not less than that calculated above shall be available between the roof of the car and the projection:
Provided that the vertical clearance between any equipment mounted on top of the car and the nearest overhead obstruction shall be not less than the sum of the three items (a), (b) and (c) as calculated above plus 150 millimeters.
30.Bottom runby for cars and counter weights:- (1) The bottom runby of cars and counterweights shall be not less than the following:
(a)15 centimeters where oil buffers are used,
(b) Where spring buffers are used:
(i) 15 centimeters where variable speed drive is used; and
(ii) Not less than the following where constant speed drive is used:
| RATED SPEED | RUNBY |
|---|---|
| Meter per second | Centimeters |
| Upto .0.125 | 07.5 |
| 0.125 to 0.25 | 15.0 |
| 0.25 to 0.50 | 22.5 |
| 0.50 to 1.00 | 30.0 |
(2) Maximum bottom runby :- The maximum bottom runby shall not exceed the following :
(a) 60 centimeters for cars, and
(b) 90 centimeters. for counter weights.
- Top Counter weight Clearances:- The top counter weight clearance shall not be less than the sum of the following four items :
(a) The bottom car runby;
(b) The stroke of the car buffer used
(c) 15 centimeters; and
(d) One -half the gravity stopping distance based on :
(i) 115 percent of the rated speed where oil buffers are used; and
(ii) Governor tripping speed where spring buffers are used.
- Landing doors.- (1) The landing doors of all lifts other than goods lift shall be imperforate
(2) All landing openings in lift well enclosure shall be protected by doors which shall extend the full height and full width of the landing opening. The top track of a landing door shall not obstruct the entrance to the lift car;
(3) The distance between the lift well side of the car door and the lift well side of the landing door shall not exceed 13 centimeters; where the car door or the landing door consists of two or more panels, the 13 centimeters dimensions shall apply to the door panel nearest to the side edge. The distance between the car and the landing sills shall not exceed 30 millimeters;
(4) The opening for the landing doors shall be not wider than that of the width of lift car. Minimum landing door opening width and height shall be 0.7 m and 2m respectively;
(5) Landing doors and their tracks shall be capable of withstanding a thrust of 345 N applied normally at any point, excepting any vision panel, without causing permanent deformation and without the doors being sprung from their tracks;
[ 1 N (newton) = - - - - Kgms ]
(6) In the case of manually operated landing doors and car doors, a vision panel, with maximum 225 millimeters x 125 millimeters in size shall be provided. Any projection on or recesses (including vision panels) in sliding car doors shall be kept to a minimum in order to avoid finger trapping between sliding parts of the door and any fixed part of the structure;
(7) Hangers and tracks for doors together with their fixings shall be of adequate strength to withstand stresses specified in sub-rule (5). Means shall be provided to prevent hangers for all landing sliding doors from jumping the tracks or jamming, and suitable stops shall be provided to prevent the hanger carriage from leaving the end of the track;
(8) The landing doors shall be securely fixed. The landing doors which are self closing shall be equipped with safety devices fitted on lift door to prevent persons while entering or leaving the lift car;
(9). Swing doors may be used where hoist way width is not enough to accommodate sliding doors. The distance between swing door and the lift car door shall not exceed 7.5 centimeters upto a height of 600 millimeters from the bottom of the door;
(10) Entrance frame of the swing door shall be designed to support in place the panel with its hinges or pivots, door closer if attached to the frame and interlock. It shall withstand the forces referred to in Sub-rule (5) and the forces resulting from the normal opening of the door or normal attempts to open it when locked in the closed position;
(11) All collapsible type landing doors provided in case of lifts installed prior to the commencement of these rules and for goods lift used on industrial premises shall be of a close picket type and no openings shall exceed 5.5 centimeters. in width between the vertical members of the doors when it is fully extended;
(12) Automatic fire door or shutter which operates by means of a fusible link or otherwise, due to the action of heat, shall not be allowed in any landing, opening or in the lift-well enclosure of any lift if such opening provides an access for exit from the building;
(13) In swing type doors the vision panels shall be so located that lift operator can have convenient vision when opening the door from the lift car side;
(14) A door open alarm shall be provided to draw attention when a car or landing door which has been left open in passenger lift;
(15). For the lift in buildings having travel of more than 30 meters;
(i) The landings doors shall have fire resistance of not less than one hour; and
(ii) The landing door for fire lift shall be power operated, automatic closing and opening type, and the words 'FIRE LIFT' shall conspicuously be displayed in radium paint on lift landing doors on each floor.
- Locking devices for landing doors : -(1) Every landing gate or door shall be fitted with locking device which shall comply with the following requirements, unless otherwise permitted in writing by the Chief Inspector;
(a) Suitable means shall be provided so that it shall not be possible to open the gate or door from the landing side unless the lift car is in the landing zone pertaining thereto;
Provision shall be made so that landing gate or door may be opened in, case of an emergency or for inspection by the Inspector or by any authorized person, by means of a special key or other suitable device, irrespective of the position of the lift car.
(b) No lift car shall be started or kept in motion, unless all landing gates or doors pertaining to the lift are in the closed position;
(2) The electrical and mechanical parts of all locking devices for gates or doors, shall be sufficiently strong so that reasonable wear may not cause an unsafe condition;
(3) Every electro-mechanical lock shall be suitably encased and the removal of any detachable cover fitted to such casing must not affect the operation of the locking device. Where springs are used in locking devices, they shall be of compression type only and properly supported;
(4) The contacts of locking devices for landing gates or doors shall be opened positively;
(5) The locking devices for landing doors shall be so designed that the lock contact is not closed until the door is closed, and the circuit shall not be completed until the leading edge of the door is within 5 millimeters of the nearest face of the door-jamb or when the leading edges of the center opening door are within 50 millimeters contact of each other:
· Provided that the locking device shall not prevent the operation of the lift whilst the emergency release push is in temporary use, or when the lift car is being moved under the control of the leveling device.
(6) Contact shall be of solid type pivoted, hinged on sliding and of sturdy construction;
(7) Provision shall be made on lift operated from the car and landings to prevent the opening of any landing door when the car is passing that zone in response to a call from another landing;
(8) The levers operating the mechanical part of the locking device shall be protected from interference from the landing side of the lift enclosure;
(9) Locking devices used with multiple panel doors shall lock all panels of the doors or only one panel provided that the interconnecting mechanism of door panels is so arranged that the locking of one will prevent the movement of all panels, not withstanding the breakage of chain or rope used for interlocking the panels.
When a door locking device is used on one panel of vertically biparting landing door reliance shall not be pressed on gravity to keep the other panel closed.
- Guide rails:- (1) Car and counter weight guide rails shall be of steel in all cases except where the nature of the processes carried on in the building render them unsuitable due to acid fumes for similar causes. In such cases prior approval of the Chief Inspector shall be obtained;
(2) For passenger and goods lifts having rated speed of more than 0.50 meter per second, the car guide rails shall have their working surfaces machined;
(3) For passenger and goods lifts having a rated speed of more than 1.5 meter per second the counter weight guide rails shall have their working surface machined;
(4) Round guide rails and cast iron guide rails shall not be used. "T" section to be adopted shall be one of the sizes specified in relevant Indian Standard or any other alternative section, provided they have adequate section modulus, moment of inertia and sectional area to withstand the forces resulting from the application of the car or counterweight safety devices;
(5) Guide rails shall be continuous throughout the entire length of the lift well, and shall be so jointed and fixed to their brackets which shall be of iron or steel so that the guides shall not deflect by more than 6 millimeters under round the clock operation. Wood blocks, plugs or similar methods shall not be used for fixing guide brackets;
H-537-5
(6) Guide rails shall be of such length that it shall not be possible for any other car or counter weight shoes to run off the guide rails;
(7) Guide rails and their fixings shall be so arranged to withstand the action of safety gear when stopping a counter weight or a fully loaded car;
(8) Guide rails shall be held to their fastening by clips of such design that any rotary movement of the clip will not release the guide rails;
(9) The clips used for fastening the guide rails shall be of forged steel, formed steel or malleable iron or machined mild steel. The fasteners used shall conform to the relevant Indian Standard;
(10) If the guides are attached to overhanging stairs, the method of fixing shall be such that no vertical stress is transferred from the guides to the stairs;
(11) Guide brackets and shims if any, shall be of steel and shall not be directly supported and fastened to the lift well enclosure wall unless such wall is of such construction and strength so as to adequately withstand the thrust imposed on the guides under all conditions of the lift service. The fastenings shall be by means of bond blocks built in to the wall or expansion bolts or through bolts with metal plates of such thickness and size so as to adequately distribute the load on the wall.
- Buffers :- (1) Buffers of spring or oil shall be fitted under the lift car directly or on the pit floor with suitable concrete or steel foundation. Oil resistant rubber buffers may be used for lift having a rated speed not exceeding 0.25 meter per second;
(2) Buffers shall be located symmetrically with reference to the vertical center line of the car frame within a tolerance of 50 millimeters;
(3) Spring or oil buffers shall be used with lift having rated speed in excess of 0.25 meter per second and up to and including 1.5 meter per second. Oil buffers shall be used with lift having rated speed in excess of 1.5 meter per second;
(4) The stroke of the spring buffer for car shall be equal to or greater than the following :
Car Speed Meter per second Stroke millimeters
0.5 or less
0.51 to 0.75
0.76 to 1.0
100
1.1 to 1.25
1.26 to 1.5
250
(5) Spring buffers shall be capable of supporting a static load equivalent to two times the weight of car and its rated load for car buffers and two times the weight of counter weight for counter weight buffers without being compressed solid;
(6) Spring buffers shall be compressed solid with a static load three times the weight of the car and its rated load for car buffers and three times the weight of counterweight for counterweight buffers;
(7) The minimum stroke of oil buffers shall be such that the car or the counter weight on striking the buffer at 115 percent of rated speed shall be brought to rest with an average retardation of not more than 10 meter per second per second;
(8) Oil buffers shall develop an average retardation not in excess of 10 meter per second per second shall develop no peak retardation grater than 25 meter per second per second having a duration exceeding 1/25 of a second with any load in the car from rated load to a minimum load of 68 Kilograms when the buffers are struck with an initial speed of not more than 115 rated speed for buffers conforming with sub rule (7);
(9) Oil buffers shall be provided with means for determining that the oil level is within the maximum allowable limits. Glass sight gauges shall not be used;
(10) Oil buffers shall be self resetting type.
- Counter weights :- (1) All Counterweights sections (filler weights), metal or non metal, shall be carried in a steel frame. Means shall be provided to retain counterweight sections in place and prevent displacement. In case of non metallic filler weights, the counter weight sections shall be totally enclosed in a metallic covering. Where tie rods are used, minimum two shall be provided, passing through all sections. The factor of safety of steel frame members and tie rods shall not be less than 5.
(2) All counterweights shall travel between rigid guide rails;
(3) Counterweights shall withstand the effect of buffer impact;
(4) Every counterweight shall travel in juxta-position to its car in the same lift well;
(5) At least four replaceable guide shoes with renewable lining or set of roller guides shall be provided, two at the top and two at the bottom of the counter weight;
(6) The guide shoes of counterweight shall be fixed and adjusted so that the play in the direction of the width of the counterweight does not exceed 5 millimeters;
(7) If an independent lift car counterweight is used, it shall not be of such weight as will cause undue slackening of any of the suspension ropes during acceleration or retardation;
(8) The travel-way of the counterweight in the lift pit shall be protected by means of a suitable enclosure work up to a height of 2 meters from the floor of the pit. Provided that a gap of 30 centimeters or up to the top of the counterweight buffer, which ever is higher may be kept from the floor of the pit.
- Lift cars :- (1) Lift cars shall be enclosed on all-sides by means of car body and doors or gates and such enclosures shall be at least 2 meter clear in height. A roof solid or perforated, capable of supporting 2 persons, that is, 2 X 68 kilograms shall be provided. Perforations shall be sufficiently close in mesh and shall reject a ball of 25 millimeters diameter to provide reasonable protection against falling articles on any person traveling in the car. The car floor shall be of a flat non-slip surface or checkered surface.
(2) Where car leveling devices are used, substantial aprons of sufficient depth shall be fitted to the car floor to ensure that no space more than the running clearances is permitted between the threshold and the landing while the car is being leveled to a floor;
(3) Where the lift car has solid enclosure and doors, provisions shall be made for a fan and for adequate ventilation. To permit switching off the power supply to the lift without switching of the fan and light, a separate circuit with control in machine room shall be provided for fan and light. Ventilation openings shall be provided in the enclosure walls above 1.8 m level and below 0.3 level. The total area of openings shall be not less than 0.035 square meter for each square meter of area of the car floor divided suitably between the top and the bottom levels. Any opening provided by a ventilating fan may be regarded as forming part of the ventilation area in that part of the car in which it is fitted;
- 1
(4) The car enclosure and doors, including their tracks of every lift car shall withstand a thrust of 345 newton applied normally at any point, excepting any vision panel, without permanent deformation
1 Newton = 1/9.81 Kilograms
(5) A three-pin plug socket with switch for a hand lamp shall be fitted on roof of the lift car for use by persons working thereon;
(6) Lift car platforms shall be of framed construction and designed on the basis of rated loads evenly distributed. Platforms for cars for goods lifts shall be designed to suit the particular condition of loading. The minimum factor of safety shall be 5 for steel and 8 for timber;
(7) Glass shall not be used in lift car except for the following purposes;
(a) As covers for certificates.
(b) For lighting fixtures,
(c) For appliances used in connection with operation of car and,
(d) For mirrors
(The glass if used shall be of laminated or sandwich type.)
The glass used for any of the said purposes shall not be more than 930 square centimeters in dimension.
However, conditions may be relaxed in case of glass or capsule type lifts and specially designed, well protected, fire resistance, fully transparent, laminated type, sandwich safety glass construction or polycarbonate material construction as may be permitted by the Chief Inspector;
(8) Car operating panel of every lift shall be provided with emergency stopping device operated by a push button in the car and it shall be clearly marked in red;
(9) Each lift car entrance shall be provided with a gate or door which shall cover the full height and width of the car opening. The top track of the gate or door shall not obstruct the car entrance
(10) The car doors shall be imperforated. The door shall when closed, guard the full opening except in the case of vertical opening car doors of goods lift, which may be limited to 2 meter and each door shall be equipped with an electric contact which shall prevent the movement of the car and the circuit shall not be completed until the leading edge of the door is within 5 millimeters of the nearest face of the door-jamb or when the leading edges of the centre opening doors are within 50 millimeters of contact of each other. The contacts shall be opened positively, independent of gravity. The electric contact shall be situated or protected so as to be reasonably inaccessible from inside the car;
(11) Goods lift used in industrial premises may use collapsible door or vertically sliding car doors and these may be in mesh or perforated panel form. The dimensions of the mesh or perforations shall not exceed 10 millimeters horizontally and 60 millimeters vertically. Collapsible door for car shall be of close picket type and no openings exceeding 55 millimeters in width shall be permitted between the vertical members of the doors when they are fully extended;
(12) Each lift car gate or door shall be provided with an electric switch which will prevent the lift car from being started or kept in motion unless the car gates or doors are closed. Provided that slow speed leveling of the lift car will be permitted from a position of 38 centimeters above or below the landing level with the gates on doors open;
(13) Every lift car controlled by an attendant shall be operated by a removable handle or key which shall remain at all times in the possession of the attendant. The handle or key shall automatically return to the off position when power is cut off. Lending gates of such lift cars shall also be opened only by a similar removable handle or key.
(14) Every lift car shall be fitted with a suitable light for adequate illumination of the car and the light shall be kept on during the whole time the lift is available for use;
(15) Every lift car shall be provided with an emergency alarm signal which can be operated by a push button in the lift car and shall be clearly audible outside the lift well in order that assistance may be obtained in case of a breakdown or failure between the floors. Every such button shall be clearly marked;
(16) A battery operated unit for lift car light and emergency alarm signal shall be provided to provide assistance in case of failure of power;
(17) The approach to the landing gate on each floor shall be kept lighted during the whole time the lift is available for use at night, and during the day time, if the situation so requires;
(18) In the case of lift cars having more than one entrance, the lift car gates shall be provided with electro mechanical interlocking device so that the gate can be opened only at the landing at which access to the lift car is provided;
(19) For the lift in buildings having height of more than 24 meters
(a) lift car for fire lift when provided shall have floor area of not less than 1.4 square meters. It shall also have loading capacity of not less than 544 Kilograms (8 persons)
(b) lift car door shall have fire resistance of one hour.
(c) lift car for fire lift shall have power operated automatic closing and opening doors synchronized with landing doors while at landing level;
(20) When the lift car is having automatic doors, it shall be possible to open the same manually from inside, in case of power failure.
- Load Plate :- (1) A load plate giving the rated load of the lift shall be fitted in each lift car in a conspicuous position. For passenger lift, the rated load shall be given in persons and kilograms. For goods lift, the rated load shall be given in kilograms or other convenient units and in persons. For the purpose of this clause, a person shall be regarded as weighing 68 kilograms;
(2) The minimum rated load of a passenger lift corresponding to the net inside car area shall be as per table given below
| Kilograms | Square meters |
|---|---|
| 272 | 0.77 |
| 340 | 0.95 |
| 408 | 1.12 |
| 476 | 1.28 |
| 544 | 1.45 |
| 612 | 1.60 |
| 680 | 1.76 |
| 748 | 1.91 |
| 816 | 2.05 |
| 884 | 2.20 |
| 1000 | 2.43 |
| 1500 | 3.38 |
2000 2500
4.22 4.99
- Lift car frame.- (1) The car of every passenger or goods lift shall be carried in a steel frame which shall be sufficiently rigid and of adequate strength to withstand the operation of the safety gear without permanent deformation.
(2) The deformation of the lift car frame cross-head and the members carrying the lift car platform shall not exceed 1/1000 of their span under static conditions with the contract load on the lift car platform;
(3) Replaceable guide shoes with renewal linings shall be provided at the top and bottom of both the sides of the lift car frame;
(4) The factor of safety of the component parts of the lift car frame and their connections shall be not less than 5 based on the ultimate strength of the material and the static load imposed on them.
- Safety gears :- (1) Every lift shall be provided with one or more car safety devices, attached to the lift car frame and located preferably at the lower part of the car. The safety devices shall be capable of stopping and sustaining the lift car with full rated load in the car at governor tripping speed;
(2) Every lift having a travel exceeding 5.5 meter shall be equipped with an over speed governor device which operates to apply the safety gear in the event of the speed of the lift car in the descending direction exceeding a predetermined limit;
(3) The application of the safety device shall not cause the lift car platform to become out of level in excess of 3 centimeters measured in any direction;
(4) When the safety gear is applied, no decrease in the tension of the governor rope or motion of the car in the descending direction shall release the safety gear.
(5) When a safety gear comes into operation, it shall automatically open the operating circuit, but it shall be possible for responsible person to release the safety gear, after a thorough inspection of the equipment and after taking any necessary precautions, by reversing the direction of the motion of the machine or by any other equally suitable means;
(6) The safety gear shall operate to stop and sustain the lift car in the event of failure of the suspension ropes, or in the event of the lift exceeding a pre-determined maximum over speed in the descending direction when a speed governor is fitted;
(7) Every safety gear shall operate positively and mechanically independent of any springs used in its construction;
(8) Any levels or dogs operated by shafts shall be keyed to such shafts by keys conforming to relevant Indian Standard;
(9) The design of the safety gear shall provide for its application to both guide rails, equally and simultaneously;
(10) Any additional rope used solely for purpose of operating the safety gear shall be led over independent pulleys, running on independent shafts;
(11) Bearings in safety gears and of the safety operating mechanism shall be of corrosion-resistant construction with one or both members of a bearing made of, or electroplated/coated with a corrosion-resistant material;
(12) Car and counterweight safety devices shall be actuated by separate governors. Provision shall be made to cause the application of counterweight safety gear, but at not more than 10 percent in excess of that at which the lift car safety gear applies;
at which the lift car safety gear applies, (13) Slack rope safety gear of the instantaneous type may be used on counterweights within the limits specified in Table below
TABLE FOR SLACK ROPE SAFETY GEARS
| RATED SPEED | MINIMUM WEIGHT OF COUNTERWEIGHT |
|---|---|
| Meter per second | Kilograms |
| 1.25 | 900 |
| 1.0 | 1350 |
| 0.75 | 1800 |
| 0.5 | 2250 |
(14) No safety gear shall be permitted to stop an ascending lift car or counter weight. If any ascending car is to be stopped on account of over speed, a safety gear shall be fitted to the counterweight for this purpose. The governor may, however, open the motor circuit and apply the brake in the event of over speed in the ascending direction;
(15) Any drive to the car governor rope shall be effected from the car frame;
(16) Any connecting device between a governor rope and car frame (or counter weight) that is intended to be released when the safety gear is applied shall be retained in its normal position by a spring loaded device;
(17) No safety gear shall depend on the completion or maintenance of an electric circuit for its operation. All safety gears shall be applied mechanically;
(18) The gripping surfaces of the car or counterweight safety gears shall not be used to guide the lift car or counterweight but shall run free of the guide rails during normal operation of the lifts;
(19). Vibration of the lift car shall be restricted to the extent that safety gear is not operated;
(20) Safety gear, designed to stop the lift car or counterweight in a distance related to car counterweight speed, shall stop the lift car with rated load or the counterweight from governor tripping speed within the range of stopping distances given in Table below sub rule (23). The stopping distance shall mean the actual slide as observed from the markings on the guide rails made by the safety gear;
(21) The motor-control and the brake - control circuit shall be opened automatically before or at the time the safety gear is applied;
(22) In case of a safety gear actuated by means of a rope unwinding from a drum, the rope shall have at least three complete turns on the drum after the safety gear has been applied and the lift car has stopped. The minimum diameter of such drum shall be 13 centimeters. The device for holding the safety rope or rod in position during normal operation shall be fixed to the steel frame work of the lift car and not to the body work of the lift car. The ends of the governor rope shall be held by cleaves or other similar means, which shall effect its purpose by friction. The cleaves or other holding device shall be supported by or from the steel frame work of the car and not fixed to the body work of the lift car;
(23) Safety gears shall be of the following types: (a) Safety gears shall be of the instantaneous type and may be used on lift car having a rated speed not exceeding 1 meter per second.
(b) Safety gears of the instantaneous type be used on counterweight having rated speed not exceeding 1.25 meters per second.
(c) Where the contract speed exceeds 1 meter per second, safety gears of the following types shall be used:
(1) Gradual wedge clamp type, with gradual increasing retarding force.
(2) Flexible guide clamp type, with constant retarding force.
The maximum stopping distance of lift, car with safety gear of gradual wedge clamp, and flexible guide clamp types and the minimum stopping distance shall be as per the table given below : TABLE
STOPPING DISTANCES FOR GRADUAL WEDGE CLAMP AND FLEXIBLE GUIDE CLAMP TYPE SAFETY GEARS
Sr. No, Governor Tripping speed Stopping Distance
meter per second millimeters, millimeters
Note :- The stopping distance shall mean the actual slide as measured by the marks on the guides.
NOTE : The following formula shall be used to determine the maximum and minimum stopping distance for gradual wedge clamp and flexible, guide clamp type safeties for car and counterweight for all intermediate speeds: $1 = 145 V² + 256
Where
S1 = Maximum stopping distance in millimeters
S2 = minimum stopping distance in millimeters, and
V = Governor tripping speed meter per second
(d) Combination of instantaneous and oil buffer safety gear for speed not exceeding 2.5 meter/second. (e) Any other type as may be approved by the Chief Inspector
- Governor.- (1) Governor shall be placed where it is not struck by the lift car or counter weight in the event of over run;
(2) Governors for car safety gears shall be adjusted to actuate the safety gear at the following speeds:
(a) For rated speeds up to 1 Meter per second maximum governor tripping speed shall be either 140 percent of rated speed or 0.88 meter per second, whichever is higher.
For rated speed above 1 meter per second, maximum governor tripping speed shall be 115 percent of the rated speed plus 0.25 meter per second
(b) Minimum governor tripping speed shall be 115 percent of the rated speed;
(3) Any governor for a counterweight safety gear shall be adjusted to trip at a speed greater than, but not more than 10 percent above the tripping speed of the car governor;
(4) Each governor shall be marked with its tripping speed in meters per second.
(5) Where safety device other than the instantaneous type are provided, a switch, operated by the over speed action of the governor, shall be provided on it to open the motor control and brake control circuits at the following speeds before or at the time the governor trips;
(a) In the down direction at not more than 90 percent of the speed at which the governor is set to trip in the down direction, and
(b) In the up direction at not more than 100 percent of the speed at which the governor is set to trip in the down direction;
(6) Governor ropes shall be not less than 6 millimeters in diameter and shall be of iron, steel or phosphor bronze and of suitable construction. When replacement of original governor ropes becomes necessary, these shall be normally of the same size, material and capacity as the ropes originally supplied by the makers of the lift. Before replacement by any other kind of rope, the suitability of such rope shall be tested to the satisfaction of the Chief Inspector;
(7) Governor ropes shall run clear of the governor jaws during normal operation of the lift;
(8) The area of contact made by the governor rope and the governor sheave shall, in conjunction with the rope tension device, provide sufficient tractive effort to cause proper operation of the governor;
(9) Governor jaws and their mounting shall be so designed that any cutting, tearing or deformation of the rope resulting from their application shall not prevent proper operation of the safety gear;
(10) Governor gears should have self-lubricating bearings which do not require frequent attention;
(11) The motor control circuit and the brake control circuit shall be opened before or at the time the governor trips.