- Machine room.- (1) All lifts shall have machine rooms immediately over the lift well, and this shall be arranged whenever possible without restricting the overhead distance required for normal safety precautions. Where the machine room is immediately over the lift well there shall be permanent and direct access from the top of lift landing.
Alternative machine positions may be permitted by the Chief Inspector when there are special reasons justifying the same.
(2) All machine rooms shall be provided with adequate ventilation to dissipate the heat generated by the lift equipment. For most single and double installations, a high and low louvered convection ventilation arrangement shall be provided. For groups of three or more lift in one machine room, increased ventilation is necessary and forced ventilation shall be provided;
(3) All machine rooms shall be considered as plant space, and conditions provided to permit reliable operation of electrical switch gear and space around the machine shall in no case be less then 60 centimeters;
(4) Lighting shall be provided to give at least 200 lux around the controller and machine. The machine room walls, ceiling and floor shall be faced in dust-resisting materials, tiles, etc., or painted to stop dust circulation;
(5) The machine room shall be of strong construction, The floor of the machine room shall be capable of carrying the load of the lift machinery and other equipment housed therein. Whenever a water tank is required to be constructed above or adjacent to the machine room, there shall be a minimum separation of 400 millimeters between the wall or slab of the machine room and the water tank;
.(6) The machine room shall be provided with reasonable access for the entry or removal of the equipments therein or of any part thereof. The height of the machine room shall be sufficient to allow any part of the equipment to be accessible and removal for repairs and replacement and in no case the height shall be less than 2.6 meters clear from the floor or the platform for machine elevator whichever is higher;
(7) The machine room shall be provided with access doors opening outwards;
(8) If the floor or platform of any machine room does not cover the entire lift well, the open sides shall be provided with hand rails or shall be guarded by other suitable means;
(9) The machine-room shall not be used as a store room or for any purpose other than housing the lift machineries and its associate apparatus and equipment. No inflammable or explosive material shall be kept in the machine room;
(10) The machine room shall be kept locked which shall be accessible only to authorized persons. The key of the machine room shall be kept in the custody of the owner or his agent and shall be made readily available for repairs, maintenance or inspection;
(11) The machine room shall be provided with an insulated portable hand lamp for examining the machinery;
(12) Thickness of machine room wall shall be of minimum 150 millimeters for R.C.C. structure or 250 millimeters for Brick construction;
(13). The instructions in English or Hindi and Gujarati for the rescue of persons traveling in the lift by manual operation of brake in case of failure of lift motor or power shall conspicuously be affixed in the machine room.
- Outline dimensions of electric lift:- (1) The outline dimensions of machine room, pit depth, total headroom, overhead distance and sill for following four classes of lifts shall be provided as specified in Tables 1 to 4 and as indicated below :
Passenger lift
Table 1
Goods lift
Table 2
Hospital lift
Table 3
Service lift
Table 4
| Load Persons Kilograms | Car inside Area in Square meters | Lift well Area in Square meters | Entrance Width in millimeters | Machine Room Area in Square meters | |
| 4 | 272 | 0.77 | 2.47 | 800 | 12.92 |
| 6 | 408 | 1.10 | 3.04 | 800 | 13.94 |
| 8 | 544 | 1.43 | 3.61 | 800 | 14.96 |
| 10 | 680 | 1.75 | 3.99 | 800 | 15.64 |
| 13 | 884 | 2.20 | 5.25 | 900 | 18.40 |
| 16 | 1088 | 2.20 | 5.25 | 1000 | 18.40 |
| 20 | 1360 | 3.10 | 6.00 | 1000 | 19.60 |
NOTE-1 : The total head room has been calculated on the basis of car height of 2.2 meter. Total maximum head room shall be 4800 Millimeters up to speed of 1.5 meter per second and 6700 Millimeters up to speed of 2.5 meter per second.
NOTE-2: In case of manually operated doors, clear entrance will be reduced by the amount of projection of handle of the landing door.
NOTE-3: Four and six passenger lift shall be limited to a speed of 1 meter per second.
NOTE-4 : The total minimum depth of the pit shall be 1600 millimeters to a speed upto 1.5 meter per second and 2600 millimeters to a speed up to 2.5 meter per second.
| Load Kilograms | Car inside Area in Square meters | Lift well Area in Square meters | Entrance Width in millimeters | Machine Room Area in Square meters |
|---|---|---|---|---|
| 500 | 1.32 | 2.85 | 1100 | 13.60 |
| 1000 | 2.52 | 4.83 | 1400 | 17.48 |
| 1500 | 3.40 | 5.98 | 1700 | 19.68 |
| 2000 | 4.25 | 7.28 | 1700 | 21.73 |
| 2500 | 5.00 | 8.12 | 2000 | 23.32 |
| 3000 | 6.00 | 9.57 | 2000 | 25.52 |
| 4000 | 7.50 | 11.22 | 2500 | 28.42 |
| 5000 | 9.00 | 13.26 | 2500 | 31.36 |
NOTE-1 : The total headroom shall be calculated on the basis of car height of 2.2 meter Total minimum head room shall be 4800 millimeters.
NOTE-2: Clear entrance width "E" is based on vertical lifting car door and vertical bi-parting landing doors. For collapsible mid-bar doors the clear entrance width will be reduced by 200 millimeters (maximum 1800 millimeters)
NOTE-3: The total maximum depth of the pit shall be 1600 millimeters.
| Load Persons Kilograms | Car inside Area in Square meters | Lift well Area in Square meters | Entrance Width in millimeters | Machine Room Area in Square meters |
|---|---|---|---|---|
| 15 1620 | 2.28 | 5.10 | 800 | 20.35 |
| 20 1360 | 3.12 | 6.60 | 1200 | 23.10 |
| 26 1768 | 3.84 | 7.05 | 1200 | 23.92 |
NOTE -1: The total head room has been calculated on the basis of a car height of 2.2 meter. NOTE-2 : In case of manually operated doors, clear entrance will be reduced by the amount of projection of handle on the landing door. NOTE-3 : Although 15 persons capacity lift is not a standard one, this is included to cover lift of smaller capacity which can be used in small hospitals. NOTE-4 : The total minimum depth of the pit shall be kept 1800 millimeters
| Load Kilograms | Car inside Area in Square meters | Lift well Area in Square meters | Entrance Width in millimeters | Machine Room Area in Square meters |
|---|---|---|---|---|
| 100 | 0.49 | 1.08 | 700 | 13.80 |
| 150 | 0.64 | 1.30 | 800 | 14.90 |
| 200 | 0.81 | 1.54 | 900 | 16.10 |
| 250 | 1.00 | 1.80 | 1000 | 18.00 |
(2). PIT : The pit depth of the lift shall normally accommodate compensating chains. If compensating ropes are required, pit depth shall be increased for all loads and speed.
(3) MINIMUM FLOOR TO FLOOR HEIGHT : - Minimum floor to floor height for horizontally sliding doors is f + 750 millimeters and for vertically bi-parting doors shall 1.5 f + 250 millimeters, where "f is clear entrance height in millimeters.
- Sheaves and pulleys. (1) Sheaves and pulleys shall be of cast iron and free from cracks, sand holes and other injurious defects. They shall have machined rope grooves. The traction sheave shall be grooved to produce proper traction and shall be sufficiently thick to provide for future wear in the groove. The deflector sheave shall be grooved so as to provide a smooth bed for the rope. Deflector or secondary sheave assemblies where used shall be mounted in proper alignment with the traction sheave.
(2) The grooving of a diverter sheave or pulley shall have a radius larger than the radius of the rope by not less than the amount shown in table below and shall extend at least over one third of the circumference of the rope.
TABLE FLANGE AND DIVERTER SHEAVE OR PULLEY GROOVES
Rope Diameter Minimum difference between radius of groove and rope radius.
| (1)Up to 16 | 0.75 |
|---|---|
| 18 to 22 | 1.25 |
| 24 to 27 | 1.5 |
| 31 and above | 2.5 |
(3) The diameter of sheave or pulley shall be not less than that obtained from the following:
Class of rope ____ Diameter of sheave or pulley
Round Strand
6 X 19 (12/6/1)
6 X 19 (12/6/1) Plus 6 filler wires
D (2.95 S + 37) with a minimum of 40 D
8 X 19 (12/6/1) Plus 6 filler wires
8 X 19 (9/9/1) scale
Note :- D = diameter of rope in centimeters, and S = Rope Speed in meter per second
(4) Overhead pulleys and the allied machinery shall be so fixed and enclosed as will allow safe and convenient access to them and will enable their maintenance and repairs to be carried out with safety;
Where the platform or floor of the enclosure does not extend to the full area of the lift well, suitable guard rail or similar fitting shall be provided to ensure safety. Provision shall also be made for adequate lighting and ventilation of the space.
(5) Where the driving sheave or drum is connected through worm gear, the worm gear shall be of non reversible type.
45.Lift machine :- (1) No friction gearing, belt, chain, clutch or chain driven mechanism shall be used for connecting the main driving gear to the traction sheaves;
(2) The motor of each lift machine or the worm shaft shall be arranged so as to provide hand winding facilities and shall be suitably marked for the direction of up and down travel of the lift.
(3) Electric lift machine shall be provided having brakes released electrically;
(4) Traction machines for lift shall be equipped with the brakes applied automatically by means of springs in compression only or by gravity when the operating device is in the "off" position or in the event of the power being cut off due to any cause;
(5) No single earth fault, short circuit or counter electromotive force shall prevent the brake from being applied during normal operation;
(6) The brake shall be designed to have a capacity sufficient to hold the car at rest with 125 percent of its rated load;
(7) No toggle or other device which is dependent upon impact operation shall be used to hold off the brake;
(8) Brake of passenger and goods lift shall have at least two brake shoes and the lining used shall be of incombustible material;
(9) Means of releasing the brake in emergency shall be provided and the re-application of the brake ensured. It shall be ensured, that hand winding of lift, by releasing the brake is done only by trained persons;
(10) No brake shall be released in normal operation until power has been applied to the motor;
(11) Any emergency release device fitted to a brake shall not be capable of holding the brake in the "off" position during normal operation.
(12) The sheave, drum worm wheel or spur gear of any lift machine shall be fixed to its shaft or driving unit either by means of sunk keys or splines according to Indian standards or shall be secured to a flange forming an integral part of the shaft or driving unit by means of turned tight fitting bolts. No set screw fastenings shall be used in lieu of keys or other positive connections.
(13) All machines, pulleys, over speed governors and similar units shall be so supported and held as to prevent any of these machineries or parts thereof from becoming loose or displaced affecting their safe working. Supporting beams shall be of steel or reinforced concrete.
- Suspension :- (1) Chains shall not be used for the suspension of a lift. Not less than three independent suspension ropes shall be used for car or counterweight of any lift with traction drive;
(2) The minimum diameter of ropes for cars and counterweights of passenger and goods lift shall be 10 millimeter;
(3). The factor of safety of the suspension ropes shall not be less than as prescribed below.
Rope Speed in meter per second Factor of safety
In the case of traction drive, the factor of safety shall be based on static contract load plus the weight of the lift car and accessories. In case of drum type drives, the factor of safety shall be calculated with dynamic conditions.
For the purposes of these rules, the factor of safety shall be as under :
Where
F = minimum breaking strength of one rope; n = number of separate suspension ropes under load;
k = roping factor, that is 1 for 1:1, 2 for 2:1 roping: and
w = maximum static load imposed on all car ropes with the car and its rated load at any position in the lift well, in the same units as F
(4) (i) The car and counterweight ends of the suspension ropes shall be fastened by spliced return loops or clipped return loops or individual tapered babbitted sockets.. Loops shall not hold directly on their fixings, but shall be lined with proper thimble eyes or equal protection. In all cases the fastenings shall be capable of sustaining a load not less than 80 percent of the minimum breaking strength of the suspension ropes;
(ii) A data plate indicating the following shall be fixed on the cross head of the car frame:
(a) Diameter of rope
(b) Number of ropes, and
(c) Manufacturer's rated breaking strength of rope in kilograms.
(5) All ropes anchored to a winding drum shall have not less than one complete and one half turns of the ropes on the winding drum when the lift car or counter weight has reached the extreme limit of its over travel;
(6) Every lift car or counter weight rope shall be free from joints;
(7) Rope compensation shall be used for any travel but it shall be necessary for travels over 30 meters;
(8) The winding drum and the lift car and counterweight suspension ropes shall be properly secured by clamps on the inside of the drum;
(9) Means shall be provided for adjusting the lengths of the ropes to equalize the load on the individual suspension ropes;
(10) (a) The material, quality, construction and the fixing of ropes shall, as far as possible, conform to Indian standards and methods pertaining to the same;
(b) The suspension ropes shall conform to relevant Indian standard;
(11) Tensioning devices for compensation ropes, governor ropes and the like shall be protected against damage due to falling objects;
(12) Each suspension rope shall be separately and independently fixed to the car and to the counterweight. The simple suspension of the lift car or the counter weight by means of a sheave or the like shall count as one suspension only.
- Controllers and operating devices.- (1) A manually operated mains disconnecting switch shall be installed in the main circuit cables of electric lift machines or motor generator sets. This switch shall be placed close to and visible from the machine or motor generator set controls.
(2) When there are more than one lift machine in machine room, each machine shall have a separate disconnecting switch. These switches shall be numbered to correspond to the number of the driving machine which they control and they shall be conveniently situated with respect to the driving machine;
(3) When any type of contact is used on the controller switches, for disconnecting the main circuit, at least two independent current breaks shall be incorporated in the design. In the event of an earth fault with any door open, the lift shall not work;
(4) Operation of a spring or springs in tension or the completion of another electric circuit shall not depend on to break the circuit to stop the lift at terminal landings;
(5) The interruption of the electrical circuit shall stop and prevent the movement of the car;
(6) Each lift machine operated by a poly-phase A.C. motor shall be protected against phase reversal or failure. This protection shall be extended to motor generator set driving D.C. or A.C. motor;
(7) All control circuits shall be independently protected by fuses or miniature circuit broker;
(8) The voltage of any controller operating circuit shall not exceed 250 volts The control circuit shall be suitably protected independent of the main circuit and it shall be so arranged that an earth fault or open circuit shall not create an unsafe condition;
(9) It shall not be possible to start the lift car under normal operation unless every landing door and car door is in the closed position;
(10) In case of lift with car switch control, the handle of the car switch shall be so arranged as to return to stop position automatically when released;
(11) Following requirements shall be complied with when the lift is put in "inspection mode";
(a) It shall not be possible to control the car from any other position;
(b) The car will travel only at a speed of 25% of the rated speed subject to a maximum of 1.0 meter per second.
(c) The car shall not move until all safety devices are in position.
(12) Every lift having winding drum machine shall be provided with a switch or device of adequate capacity which shall automatically cut off electric supply and shall stop the machine in the event the lifting ropes of the lift car become slack either due to any obstruction of the lift car in its travel in the descending direction or due to any other cause whatsoever;
(13) Emergency stop switches for short circuiting the landing door lock circuit shall be prohibited;
(14) An emergency stop switch, of manually opened and closed type, shall be provided on the top of every lift car and in the lift pit and shall be marked conspicuously;
(15) Drum drive machine shall not be used for speed exceeding 0.5 meter per second;
(16) All lift traveling at a speed of 1 meter per second and above shall be provided with floor leveling device;
(17) Signal bells or similar apparatus, which can be operated from any floor in connection with an indicator in the lift car, shall be provided on all lift operated by lift operators;
(18) The operation of the fire lift in building having more than 30 meters height, shall be a simple toggle or two button switch situated in a glass box painted with red color adjacent to the lift at entrance level on the ground floor. When the switch is 'ON, the landing call points shall become inoperative and car shall report to the ground floor and the same shall remain on car control only. When the switch is "OFF", the lift shall return to normal working;
(19) Floor position indicator shall be provided in the lift car as well as at every landing;
(20) Car top shall be provided with a suitable wire mesh guard to provide safety to persons working thereon for maintenance of lift.
- Terminal stopping and final limit switches:- (1) Every electric lift shall be provided with upper and lower normal terminal limit switches arranged to stop the car automatically within the limits of top car clearance and bottom runby (over travel) from any speed attained in normal operation. Such limit switches shall act independently of the operating device, the ultimate or final limit switch and the buffers;
(2) Normal terminal limit switch shall be fitted in the lift car or in the lift well or in the machine room, and such switches shall be brought into operation by the movement of the lift car;
(3) When terminal limit switches are situated in the machine room, they shall be mounted on and operated by stopping device mechanically connected to and driven by the lift car without friction. An automatic safety switch shall be provided to stop the machine in case of failure of tape, chain, rope or other similar device;
(4) Electric lifts shall be provided with ultimate or final limit switches arranged to stop the car automatically within the top and bottom clearances independent of the normal operating device and the terminal limit switches. The switches and the oil buffer shall be so arranged that the opening of the switch and the engagement of the buffer shall be as nearly simultaneous as possible. When spring buffers are employed, the switch shall open before the buffers are engaged;
(5) Final limit switches shall act to prevent movement of the lift car under power in both directions of travel and shall, after operation, remain open until the car has been moved by a winding to a position within the limits of normal travel;
(6) Final limit switches shall not be mounted on the lift car and shall be operated by the movement of the lift car in the lift well;
(7) Final limit switches shall not control the same switches on the controller as those controlled by the normal terminal limit switches unless two or more separate and independent switches are provided;
(8) All normal terminal stopping switches whether mounted on the lift car or in the lift well shall be of enclosed type and shall be securely mounted. The contacts of all terminal stopping devices shall be opened positively and mechanically by the movement of the lift car.
Note:-In the case of electric lift using floor controller or other similar devices for automatic stopping at the floor landing, only one set of floor stopping contacts shall be necessary for each terminal landing provided these contacts and the means of operating them comply with the requirements for terminal stopping devices;
(9) Every lift having a winding drum machine shall have two final terminal stopping devices, one being operated by the machine and the other by the movement of the lift car.
- Electrical wiring and apparatus :- (1) The electric supply line and apparatus of the lift shall be of sufficient ratings of power, insulation and estimated fault current and of sufficient mechanical strength for the duty which they may be required to perform. Over current protection for power and control circuits, shall be provided;
(2) Each lift shall be capable of being isolated from the main supply by suitable locking arrangement;
(3) For banks of interconnected lifts, a separate sub circuit is required for the common supervisory system, in order that any one car may be shut down without isolating the supervisory control of the remainder;
(4) Machine rooms enclosing lift equipment shall be provided with adequate illumination controlled by a switch fixed adjacent to its the entrance. At least one socket outlet, suitable for lamps or tools, shall be provided in this room;
(5) The supply to the car light shall be from a separate circuit, and controlled by an independent switch located in the machine room. For multiple lifts with a common machine room a separate supply shall be provided for each car. The car lighting shall be independent of the power supply mains;
(6) Three pin sockets with switch and a light point shall be provided on each floor. The power supply for this shall be controlled by a switch provided in the lift well and accessible from the terminal floor entrance;
(7) When the alarum system is connected to a transformer or trickle charger, the supply shall be taken from the machine room lighting or when available, from the building fire alarm system;
(8) All electric supply lines and apparatus in connection with the lift installation shall be so constructed, installed, protected and maintained so that there may be no danger to persons therefrom;
(9) A battery operated telephone shall be provided in the lift car and for the purpose, a cabinet shall be fitted in the car and wiring shall be provided from car to terminal box adjacent to the lift well. Such telephone shall be receivable at the ground floor;
(10) All metal casings or metallic coverings containing or protecting any electric supply lines or apparatus shall be efficiently earthed;
(11). No bare conductor shall be used in any lift car as may cause danger to persons;
(12) A danger notice in Hindi or English and Gujarati with a sign of skull and bones shall be affixed on the i) door of the machine room, ii) lift motor and iii) lift controller.
- Testing at site :- (1) The lift shall pass the following tests when carried out at site and before it is put into normal service. The necessary test weights and instruments shall be provided by the person authorised under section 13 for erection, and the power of the declared voltage and frequency required for adjusting and testing shall be supplied by the owner.
( a) Test to determine that the modulation resistance between power and control lines and earth is not less than 0.5 megohms when measured with a DC voltage of 500 volts shall be carried out with the conductors so connected together as to ensure that all parts of every circuit are simultaneously tested;
(b) Test to determine that the earthing of all conduit, switch, casings and similar metal work is continuous and of low resistance. Tests shall be made from all terminal points by means of a substantial current to ensure that the resistance of earth path is sufficiently low to enable fuses or circuits to operate under faulty conditions;
(c) Test to determine that the motor, brake, control equipment and door locking devices and limit switches function correctly. Brake to be tested at 125 percent of the rated load;
(d) Test to determine that the lift car raises and lowers at rated load;
(e) Test to determine that the lift car achieves the rated speed;
(f) The car safety gear shall be tested as under;
(i) The rope driving the over speed governor shall be removed;
(ii) The governor shall then be connected with separate rubber belt or other flexible connection to the off load over speed governor testing kit specially designed for the purpose. The testing set up shall be capable of increasing or decreasing the speed of the governor manually and shall be capable of measuring the speed of the over speed governor to which it is connected.
(iii) Calibration of the over-speed governor shall then be checked. The tripping speed shall be confirm with that specified in rule 41;
NOTE :- The safety gear of a lift having an AC motor driven machine shall be tested by manually tripping the governor with the speed attained by a loaded lift car descending, with brake released, is insufficient to operate the governor.
(2) A lift is designed to operate and transport the rated load at the required duty cycle, and shall not, by intention, or habitually, be used to carry overloads. During test, as a safeguard to cover variable supply and temperature conditions, a lift shall be checked for the car to complete one round trip with rated load plus 10 percent at nominal supply voltage and nominal ambient temperature;
(3) No new lift shall be brought into use unless the lift has been tested to determine whether its safety gear, brakes, terminal stopping devices, buffers, over-speed governor, etc. operate satisfactorily;
(4) The person authorised under section 13 for erection of a lift shall certify in writing that all the tests specified in these rules are carried out by him to determine the suitability of the lift for normal and regular service, and if required by the Inspector, such tests may also be carried out by him.
- Other precautions :- (1) Adequate precaution shall be taken to guard against any possibility of a lift being operated by unauthorized persons. Precautions shall also be taken to prevent a lift from being operated by any person when it is not intended for use;
(2) No person shall remain in the pit while the lift is working Adequate precautions shall be taken to protect persons working in the pit from accidental contact with counterweight;
(3) While a lift is under examination or repairs, suitable steps shall be taken to ensure that the lift is not operated inadvertently by any person working in the lift;
(4) No explosive or other inflammable material shall be carried in the lift car as may cause danger to the safety of persons.