Annexure IXGeneral Building Requirements (See clause (vii) and (viii) of Rule 43)
(1) Doorways:
(i) Every doorway shall open into an enclosed stairway, a horizontal exit, on a corridor or passageway providing continuous and protected means of egress.
(ii) No exit doorway shall be less than 1 meter in width. Doorways shall be not less than 2 meter in height. Doorways for bathrooms, water closet and stores shall be not less than 0.75 meter wide.
(iii) Exit doorways shall open outwards, that is, away from the room but shall not obstruct the travel along any exit. No door, when opened, shall reduce the require width of stairway or landing to less than 0.9 meter, overhead or sliding doors shall not be installed.
(iv) Exit door shall not open immediately upon a flight or stairs, a landing equal to at least the width of the door shall be provided in the stairway at each doorway, level of landing shall be the same as that of the floor which it serves.
(v) Exit doorways shall be openable from the side which they serve without the use of a key.
(vi) Mirrors shall not be placed in exit ways or exit doors to avoid confusion regarding the direction of exit.
(vii) Revolving doors shall not be provided as a means of fire exit
(2) Stairways:
(i) A staircase shall not be arranged round a lift shaft.
(ii) The natural ventilation requirement of the staircase shall be, achieved through opening at each landing, of an area 0.5 square meters in the external wall. A cross ventilated staircase shall have 2 (two) such openings in opposite/adjacent walls or the same shall be cross-ventilated through the corridor. The National Building Code of India, Chapter 4 Fire and Life Safety, Clause 4.4.2.5 Smoke Control of exits shall be followed for requirement of Pressurized staircase in various building components.
(iii) The minimum width of staircase shall be as in Table 1 herein contained—
Table No. 1: Type of Building and Staircase Width
Sl.No.
Type of Building
Width (m)
(a)
(b)
(c)
1
Residential buildings (dwellings)
1.0
2
Residential Hotel Buildings
1.5
3
Assembly buildings e.g. auditorium, theatres and cinemas
2.0
4
Educational buildings up to 30 meter in height
1.5
5
Institutional buildings like hospitals
2.0
6
All other buildings
1.5
(iv) The minimum width of treads without nosing shall be 0.25 meter for staircase of residential buildings. In the case of other buildings the minimum tread shall be 0.3 meter. The treads shall be constructed and maintained in a manner to prevent
slipping. The maximum height of riser shall be 0.19 meter in the case of residential buildings and 0.15 meter in the case of other buildings and the number of riser shall be limited to 12 per flight.
(v) Handrails shall be provided with a minimum height of 0.9 meter from the center of the tread.
(vi) Handrail shall be provided on both sides of the staircase, if the width of staircase is 1.5 meter or more.
(vii) The minimum headroom in a passage under the landing of a staircase and under the staircase shall be 2.2 meter.
(viii) Access to exit staircase shall be through a fire door of a minimum 120 min fire resistance rating. It shall be a swing type door opening in the direction of the escape.
(ix) No living space, store or other fire risk shall open directly into staircases.
(x) External exit door of staircase enclosure at ground level shall open directly to the open spaces or can be reached without passing through any door other than a door provided to form a draught lobby.
(xi) The exit sign with arrow indicating the way to the escape route shall be provided at a height of 0.5 meter from the floor level on the wall and shall be illuminated by electric light connected to corridor circuits. All exit way marking signs shall be flushed with the wall and so designed that no mechanical damage shall occur to them due to moving of furniture or other heavy equipment's. Further all landings of floor shall have floor indication boards indicating the number of floor. The floor indication board shall be placed on the wall immediately facing the flight of stairs and nearest to the landing. It shall be of size not less than 0.5 meter × 0.5 meter and it shall be prominently on the wall facing the staircase.
(xii) In case of single staircase it shall terminate at the ground floor level and the access to the basement shall be by a separate staircase. The second staircase may lead to basement levels provided the same is separated at ground level by either a ventilated lobby with discharge points at two different ends or through enclosures with fire resistance rating door (Table 1, Part IV of the National Building Code of India revised time to time) or through a fire protected corridor.
(3) Lifts: General requirements of lifts shall be as follows:
(i) All the floors shall be accessible for 24 hours by the lifts. The lifts provided in the buildings shall not be considered as a means of escape in case of emergency. In a dual line arrangement (lifts opposite to each other) the lobby may be between 1.5 times to 2.5 times the depth of one car. For in-line (single line) arrangements the lobby may be typically half of the above recommendations.
(ii) Grounding switch, at ground floor level, to enable the fire service to ground the lift shall also be provided.
(iii) The lift machine room shall be separate and no other machinery shall be installed there in.
(iv) Walls of lift enclosures and lift lobby shall have fire rating of 2 hour; (National Building Code of India); lifts shall have a vent at the top of area not less than 0.2 square meter.
(v) Lift car door shall have a fire resistance rating of 1 hour.
(vi) Lift lobby doors in lift enclosures shall have fire resistance as per relevant provision of the National Building Code of India.
(vii) Collapsible gates shall not be permitted for lifts and shall have solid doors with fire resistance of at least 1 hour.
(viii) Lifts if communicating with the basement, the lift lobby of the basements shall be pressurized as suggested in Annexure-III (Fire Protection and Fire Safety Requirements) with self-closing door with fire resistance rating. Telephone or other communication facilities shall be provided in lift cars and to be connected to fire control room for the building.
(ix) Suitable arrangements such as providing slope in the floor of lift lobby shall be made to prevent water used during firefighting etc., at any landing from entering the lift shafts.
(x) A sign shall be posted and maintained on every floor at or near the lift indicating that in case of fire, occupants shall use the stairs unless instructed otherwise. The sign shall also contain a plan for each floor showing the locations of the stairways. Alternate source of power supply shall be provided for all the lifts through a manually operated changeover switch.
(xi) The National Building Code of India, Chapter 4 Fire and Life Safety, Clause 4.4.2.5 Smoke Control of exits may be followed for requirement of Pressurized lifts in various building components.