Restriction on construction of high-rise building.— (1) Construction of high-rise buildings shall not be permitted in villages, as notified by the Authority, from time to time.
The Authority may, with prior approval of the State Government, restrict construction of high-rise buildings in any peri-urban or rural area within its jurisdiction on the basis of assessment of the available utilities or infrastructure such as drainage, solid waste management, transport, water management required for urban settlements or habitats.
Where conditional permissions have been granted before commencement of these rules, development shall be controlled as per regulations under which such permission were given:
Provided that this relaxation shall not be allowed where such development was made in violation of heritage zone condition.
Main Entrance.— (1) The main entrance to the premises shall not be less than 6 (six) meters in width in order to allow easy access to fire engine and the gate shall fold back against the compound wall of the premises, thus leaving the exterior access way, within the plot, free for the movement of fire service vehicles:
Provided that if archway is provided over the main entrances, the height of the archway shall not be less than 5 (five) meters.
For high-rise Housing Projects on one plot, the access way within the premises shall not be less than 7.5 (seven and half) meters in width and the open space between buildings
shall be as specified under rule 34.
The space set apart for providing access within the premises shall in no case be included in the calculation of requirements pertaining to parking spaces and other amenities required to be provided for the building.
Every access way shall be properly drained and lighted to the satisfaction of the Authority and manhole covers or any other fittings laid within the right of way of the access way shall be flushed with the finished surface level of it so as not to obstruct safe movement of men and vehicles.
Reconstruction, addition or alteration to any high-rise building shall not be taken in a manner which shall reduce the width of the access way to a level below the minimum prescribed limit under these rules.
Exit.— (1) Every high rise building meant for human occupation or assembly, shall be provided with exit sufficient to permit safe escape of the occupants in case of fire or other emergencies.
An exit may be a door-way, corridor, passage way to an internal or external staircase or to a verandah or roof or terrace having access to a street.
Exits shall be so arranged as to provide continuous means of access to the exterior of a building or exterior open space leading to a street without passing through any occupied unit.
Exits shall be so located that the travel distance on the floor shall not exceed 20 (twenty) meters in case of residential, educational, institutional and hazardous occupancies and 30 (thirty) metres in the case of assembly, business, mercantile, industrial and storage occupancies.
If the provision specified at clause 4.4.2.4 of Part-IV of National Building Code of India 2016 regarding travel distance based on occupancy and construction type (fire resistance rating) is completely adhered to, then such travel distance shall be considered as compliance towards provisions of sub-rule (4).
Wherever more than one exit is required for a floor of a building, exits shall be placed at a reasonable distance from each other as possible.
All the exits shall be accessible from the entire floor area at all floor levels.
There shall be at least two exits serving every floor and at least one of them shall lead to a staircase.
The width of every exit shall not be less than one metre and shall be provided as specified in Table No.18 below:
| Table No. 18: Number of Occupants as per type of Occupancy | |||
| Sl. No. | Type of occupancy | Number of occupants per unit exit width | |
| Staircase | Terrace | ||
| (a) | (b) | (c) | (d) |
| 1 | Residential | 25 | 75 |
| 2 | Mixed and other uses | 50 | 75 |
Explanation:—
(a) Lifts and escalators shall not be considered as an exit.
(b) 'Travel distance' means the distance from any point in the floor area to any exit measured along the path or egress except that when the floor areas are sub-divided into rooms, used singly or of rooms and served by suite corridors and passage, the travel distance may be measured from the corridor entrance of such rooms or suites to the nearest staircase or verandah having access to the street.
(c) The definition of travel distance shall be as specified in NBCI 2016, in case the same is provided in complete compliance of Clause 4.4.2.4 of Part-VI of NBCI.
(d) The unit of exit width, used to measure the capacity of any exit, shall be 500 mm. A clear width of 250 mm shall be counted as an additional half unit. Clear widths less than 250 mm shall not be counted for exit width.
Structural Safety Design, Standards and other requirements.— (1) The structural design of foundation, masonry, timber, plain concrete, reinforced concrete, pre-stressed concrete and structural steel shall be carried out in accordance with provisions related to structural design, loads, foundation, wood, masonry, concrete and steel of the National Building Code of India taking into consideration all relevant Indian Standards prescribed by Bureau of Indian Standards for general structural safety, for cyclone or wind or storm protection, for earthquake protection and for protection of landslide hazard. (Refer to Annexure-VII for list of relevant Indian Standards)
All material and workmanship shall be of good quality conforming generally to the accepted standards of Public Works Department and Indian standard specification and codes as included under Building Materials and Construction practices and safety of the National Building Code of India.
The provisions of these rules are not intended to prevent the use of any material or method of design or construction not specifically prescribed in these rules provided any such alternative has been approved as part of specification provided under clause (x) of sub-rule (2) of rule 5.
The building materials approved by Bureau of Indian Standards (B.I.S.) or any statutory body will form part of the approved building material and technology as part of the rules.
The Planning design and installation of electrical installations, air conditioning installation of lifts and escalators can be carried out in accordance with provisions prescribed for Building Services, Lighting and Ventilation, electrical and Allied installation, air conditioning and heating, acoustics, sound insulation and noise control, installation of lifts and escalators in the National Building Code of India.
The requirements of electric sub-station and the provisions of electric sub-station
shall also require approval from the concerned Authority.
The planning, design, construction and installation of water supply, drainage and sanitation and gas supply system shall be in accordance with relevant provisions of the National Building Code of India.