Step 1: Simulate a cooling load and enable the economizer by adjusting the lockout control set point. Verify and document the following:
(a) Economizer damper modulates opens to 100% outside air.
(b) Return air damper modulates closed and is completely closed when economizer damper is 100% open.
(c) Economizer damper is 100% open before mechanical cooling is enabled.
(d) Relief fan or return fan (if applicable) is operating or barometric relief dampers freely swing open.
Step 2: Continue from Step 1 and disable the economizer by adjusting the lockout control set point. Verify and document the following:
(a) Economizer damper closes to minimum ventilation position.
(b) Return air damper opens to at or near 100%.
(c) Relief fan (if applicable) shuts off or barometric relief dampers close. Return fan (if applicable) may still operate even when economizer is disabled.