All heating, ventilation, air conditioning equipment and systems, and their controls shall comply with the mandatory provisions of §5.2 and the prescriptive criteria of §5.3 for the respective building energy efficiency level. In case alternative compliance path of Total System Efficiency or Low Energy Systems is used for compliance, respective requirements of §5.3.13 or §5.3.14 and relevant criteria of §5.3 shall be met.
5.2MandatoryRequirements
5.2.1 Ventilation
(a) All habitable spaces shall be ventilated with outdoor air in accordance with the requirements of §5.2.1 and guidelines specified in the National Building Code2016 (Part 8: Building Services, Section 1: Lighting and Natural Ventilation, Subsection 5: Ventilation).
(b) Ventilated spaces shall be provided with outdoor air using one of the following:
i. Natural ventilation
ii. Mechanical ventilation
5.2.1.1 Natural Ventilation Design Requirements
Naturally ventilated buildings shall:
(a) Comply with guidelines provided for natural ventilation in NBC.
(b) Have minimum BEE 3-star rated ceiling fans, if provided with ceiling fans.
(c) Have exhaust fans complying with minimum efficiency requirements of fans in §5.3, if provided.
5.2.1.2 Mechanical Ventilation Air Quantity Design Requirements
Buildings that are ventilated using a mechanical ventilation system that are ventilated with a mechanical system, either completely or in conjunction with natural ventilation systems, shall:
(a) Install mechanical systems that provide outdoor air change rate as per NBC.
(b) Have a ventilation system controlled by CO sensors for basement car park spaces with total car park space greater than or equal to 600 m2.
5.2.1.3 Demand Control Ventilation
Mechanical ventilation systems shall have demand control ventilation if they provide outdoor air greater than 1,500 liters per second, to a space greater than 50 m2, with occupant density exceeding 40 people per 1 0 0 m 2 of the space, and are served by one or more of the following systems:
i. An air side economizer
ii. Automatic outdoor modulating control of the outdoor air damper
Exceptions to §5.2.1.3:
(a) Classrooms in Schools, call centers category under Business
(b) Spaces that have processes or operations that generate dust, fumes, mists, vapors, or gases and are provided with exhaust ventilation, such as indoor operation of internal combustion engines or areas designated for unvented food service preparation, or beauty salons
(c) Systems with exhaust air energy recovering system
5.2.2Minimum Space Conditioning Equipment Efficiencies
5.2.2.1 Chillers
(a) Chillers shall meet or exceed the minimum efficiency requirements under BEE Standards and Labelling Program for chillers as and when updated by BEE.
(b) For ECBC compliance, minimum 1 star rated chillier shall be installed.
(c) The application of air-cooled chiller is allowed in all buildings with cooling load less than 530 kW. For buildings with cooling load equal to or greater than 530 kW, the capacity of air-cooled chiller shall be restricted to 33% of the total installed chilled water capacity unless the authority having jurisdiction mandates the application of air-cooled chillers.
5.2.2.2 Unitary, Split, Packaged Air-Conditioners
Unitary air-conditioners shall meet or exceed the efficiency requirements given in Table 5-1. Window and split air conditioners shall be certified under BEE’s Star Labeling Program. EER shall be as per IS 8148 for all unitary, split, packaged air conditioners greater than 10 kWr.
Table 5-1Minimum Requirements for Unitary, Split, Packaged Air Conditioners in ECBC Building
Cooling Capacity (kWr)
Water Cooled
Air Cooled
≤ 10.5
NA
BEE 3 Star
>10.5
3.3 EER
2.8 EER
5.2.2.3 Variable Refrigerant Flow
Variable Refrigerant Flow (VRF) systems shall meet or exceed the efficiency requirements specified in Table 5-2 as per the ANSI/AHRI Standard 1230 while the Indian Standard on VRF is being developed. BEE Standards and Labeling requirements for VRF shall take precedence over the current minimum requirement.
COMFORT SYSTEMS
COMFORT SYSTEMS
Table 5-2Minimum Efficiency Requirements for VRF Air conditioners for ECBC Building*
For Heatin
g or cooling or both
Type
Size category (kWr)
EER(W/W)
IEER(W/W)
VRF Air
< 40
3.28
4.36
Conditioners,
>= 40 and < 70
3.26
4.34
Air cooled
>= 70
3.02
4.07
* The revised EER and IEER values as per Indian Standard for VRF corresponding to values in this table will supersede as and when the revised standards are published.
5.2.2.4 Air Conditioning and Condensing Units Serving Computer Rooms
Air conditioning and condensing units serving computer rooms shall meet or exceed the energy efficiency requirements listed in Table 5-3.
Table 5-3Minimum Efficiency Requirements for Computer Room Air Conditioners
Equipment type
Net Sensible Cooling Capacitya
Minimum SCOP-127b
Downflow
Upflow
All types of computer room ACsAir/ Water/ Glycol
All capacity
2.5
2.5
a. Net Sensible cooling capacity = Total gross cooling capacity - latent cooling capacity – Fan power
b. Sensible Coefficient of Performance (SCOP-127): A ratio calculated by dividing the net sensible cooling capacity in watts by the total power input in watts (excluding reheater and dehumidifier) at conditions defined in ASHRAE Standard 127-2012 Method of Testing for Rating Computer and Data Processing Room Unitary Air Conditioners)
5.2.2.5 Boilers
Gas and oil-fired boilers shall meet or exceed the minimum efficiency requirements specified in Table 5-4.