U-factors shall be determined for the overall fenestration product (including the sash and frame) in accordance with ISO-15099 by an accredited independent laboratory, and labeled or certified by the manufacturer. U-factors for sloped glazing and skylights shall be determined at a slope of 20 degrees above the horizontal. For unrated products, use the default table in Appendix A.
4.2.1.2 Solar Heat Gain Coefficient
SHGC shall be determined for the overall single or multi glazed fenestration product (including the sash and frame) in accordance with ISO-15099 by an accredited independent laboratory, and labeled or certified by the manufacturer.
Exceptions to §4.2.1.2:
(a) Shading coefficient (SC) of the center of glass alone multiplied by 0.86 is an acceptable alternate for compliance with the SHGC requirements for the overall fenestration area.
(b) Solar heat gain coefficient (SHGC) of the glass alone is an acceptable alternate for compliance with the SHGC requirements for the overall fenestration product.
4.2.1.3 Visible light transmittance
Visible light transmittance (VLT) shall be determined for the fenestration product in accordance with ISO-15099 by an accredited independent laboratory, and labeled or certified by the manufacturer. For unrated products, VLT of the glass alone shall be de-rate by 10% for demonstrating compliance with the VLT requirements for the overall fenestration product.
Chapter 4Building Envelope
4.1 General
The building envelope shall comply with the mandatory provisions of §4.2, and the prescriptive criteria of §4.3. In case alternative compliance path of Building Envelope Trade-off Method is used for compliance, requirements of §4.3.5 and relevant criteria of §4.3 shall be met.
4.2.2Opaque Construction
4.2.2.1 U-Factor
U-factors shall be calculated for the opaque construction in accordance with ISO-6946. Testing shall be done in accordance with approved ISO Standard for respective insulation type by an accredited independent laboratory, and labeled or certified by the manufacturer. For unrated products, use the default tables in Appendix A.
4.2.2.2 Solar Reflectance
Solar reflectance for the external opaque roof construction shall be determined in accordance with ASTM E903-96 by an accredited independent laboratory, and labeled or certified by the manufacturer.
4.2.2.3 Emittance
Emittance for the external opaque roof construction shall be determined in accordance with ASTM E408-71 (RA 1996) by an accredited independent laboratory, and labeled or certified by the manufacturer.
4.2.3Daylighting
Above grade floor areas shall meet or exceed the useful daylight illuminance (UDI) area requirements listed in Table 4-1 for 90% of the potential daylit time in a year. Mixed-use buildings shall show compliance as per the criteria prescribed in §2.5.Compliance shall be demonstrated either through daylighting simulation method in §0 or the manual method in §4.2.3.2. Assembly buildings and other buildings where daylighting will interfere with the functions or processes of 50% (or more) of the building floor area, are exempted from meeting the requirements listed in Table 4-1.
Exceptions to §4.2.3:
Assembly buildings and other buildings where daylighting will interfere with the functions or processes of 50% (or more) of the building floor area, are exempted from meeting the requirements listed in Table 4-1.
Table 4-1Daylight Requirement
Building Category
Percentage of above grade floor area meeting the UDI requirement
ECBC
ECBC+
Super ECBC
Business, Educational
40%
50%
60%
No Star Hotel
30%
40%
50%
Star Hotel Healthcare
ENVELOPE
ENVELOPE
Building Category
Percentage of above grade floor area meeting the UDI requirement
Resort
45%
55%
65%
Shopping Complex
10%
15%
20%
Assembly
Exempted
4.2.3.1 Daylighting Simulation Method
Only BEE approved software shall be used to demonstrate compliance through the daylighting simulation method. Buildings shall achieve illuminance level between 100 lux and 2,000 lux for the minimum percentage of floor area prescribed in Table 4-1 for at least 90% of the potential daylit time. Illuminance levels for all spaces enclosed by permanent internal partitions (opaque, translucent, or transparent) with height greater or equal to 2 m from the finished floor, shall be measured as follows:
(a) Measurements shall be taken at a work plane height of 0.8 m above the finished floor.
(b) The period of analysis shall be fixed for continuously 8 hours per day, anytime between 7:00 AM IST to 5:00 PM IST, resulting in 2,920 hours in total for all building types except for Schools. Schools shall be analyzed for continuously 7 hours per day, anytime between 7:00 AM IST to 3:00 PM IST.
(c) Available useful daylight across a space shall be measured based on point-by-point grid values. UDI shall be calculated for at least one point for each square meter of floor area.
(d) Fenestration shall be modeled with actual visible light transmission (VLT) as per the details provided in the material specification sheet.
(e) All surrounding natural or man-made daylight obstructions shall be modeled if the distance between the façade of the building (for which compliance is shown) and surrounding natural or man-made daylight obstructions is less than or equal to twice the height of the man-made or natural sunlight obstructers. If the reflectance of the surfaces is not known, default reflectance of 30% and 0% shall be used for all vertical surfaces of man-made and natural obstructers respectively.
(f) Interior surface reflectance shall be modeled based on the actual material specification. If material specification is not available, the default values in Table 4-2 shall be used:
Documentation requirement to demonstrate compliance are:
i. Brief description of the project with location, number of stories, space types, hours of operation and and software used.
ii. Summary describing the results of the analysis and output file from simulation tool outlining point wise compliance for the analysis grid and compliance in percentage.
iii. Explanation of any significant modelling assumptions made.
iv. Explanation of any error messages noted in the simulation program output.
v. Building floor plans, building elevations & sections, and site plan with surrounding building details (if modeled).
vi. Material reflectance, analysis grid size, total number of grid size/ resolution, total number of grid points.
Table 4-2Default Values for Surface Reflectance
Surface Type
Reflectance
Wall or Vertical Internal Surfaces
50%
Ceiling
70%
Floor
20%
Furniture (permanent)
50%
4.2.3.2 Manual Daylighting Compliance Method
This method can be used for demonstrating compliance with daylighting requirements without simulation. Daylight extent factors (DEF) mentioned in Table 4-3 shall be used for manually calculating percentage of above grade floor area meeting the UDI requirement for 90% of the potential day lit time in a year.
Table 4-3Daylight Extent Factors (DEF) for Manually Calculating Daylight Area
Shading Latitude Window VLT < 0.3 VLT ≥0.3 Type
North
South
East
West
North
South
East
West
No shading or PF < 0.4
≥15°N
All window types
2.5
2.0
0.7
0.5
2.8
2.2
1.1
0.7
< 15°N
2.4
2.0
0.8
0.6
2.7
2.2
1.5
0.8
Shading with PF≥0.4
All latitudes
All window types without light shelf*
2.8
2.3
1.5
1.1
3.0
2.5
1.8
1.5
Window with light shelf*
3.0
2.5
1.8
1.6
3.5
3.0
2.1
1.8
* To qualify as light shelf the internal projection shall meet the requirements specified under Exceptions to SHGC requirements in Table 4-10 and Table 4-11
(a) To calculate the daylit area:
i. In a direction perpendicular to the fenestration, multiply daylight extent factor (DEF) by the head height of the fenestration or till an opaque partition higher than head height of the fenestration, whichever is less.
ENVELOPE
ENVELOPE
ii. In the direction parallel to the fenestration, daylit area extends a horizontal dimension equal to the width of the fenestration plus either 1 meter on each side of the aperture, or the distance to an opaque partition of 2 m high, or one-half the distance to an adjacent fenestration, whichever is least.
iii. For skylights, calculate the horizontal dimension in each direction equal to the top aperture dimension in that direction plus either the floor-to-ceiling height (H) for skylights, or 1.5 H for monitors, or H or 2H for the sawtooth configuration, or the distance to the nearest 1 meter or higher opaque partition, or one-half the distance to an adjacent skylight or vertical glazing, whichever is least.
iv. Glazed façades, with non-cardinal orientation, shall be categorized under a particular cardinal direction if its orientation is within ± 45 degrees of that cardinal direction.
v. Daylit area overlap: For overlapping daylit areas such as windows on different orientations or in case of skylights the overlapping daylit area shall be subtracted from the sum of daylit area.
Documentation requirement:
vi. A separate architectural plan shall be prepared with all daylit areas marked on the floor plans.
vii. A summary shall be provided showing compliance as per Table 4-1.
4.2.4Building Envelope Sealing
Following areas of the building envelope, of all except naturally ventilated buildings or spaces, shall be sealed, caulked, gasketed, or weather-stripped:
(a) Joints around fenestration, skylights, and door frames
(b) Openings between walls and foundations, and between walls and roof, and wall panels
(c) Openings at penetrations of utility services through roofs, walls, and floors
(d) Site-built fenestration and doors
(e) Building assemblies used as ducts or plenums
(f) All other openings in the building envelope
(g) Exhaust fans shall be fitted with a sealing device such as a self-closing damper
(h) Operable fenestration should be constructed to eliminate air leakages from fenestration frame and shutter frame
Note 4-1 Daylight Extent Factor and Useful Daylight Illuminance
Useful Daylight Illuminance (UDI) is defined as the annual occurrence of daylight between 100 lux to 2,000 lux on a work plane. This daylight is most useful to occupants, glare free and when available, eliminates the need for artificial lighting. Daylight extent factor provides a ratio of window sizes to floor area receiving UDI in accordance to window orientation.
Calculating Useful Daylight Illuminance (UDI)
An office building located in New Delhi, India is pursuing ECBC compliance. Table 4-1 lists the minimum daylight area requirements for compliance. The table specifies that for office buildings, minimum 40% of its floor area shall receive daylight in range of 100 – 2,000 lux for at least 90% of the year.
This typical floor has a rectangular layout (33 m x 38 m) of 1,254 m2. Visible light transmission (VLT) of glazing in all orientations is 0.39. Windows have light shelves and external shading devices with Projection Factor (PF) ≥ 0.4. Head height of fenestrations is 3.0 m.
For compliance at least 502 m2 (40% of 1,254 m2) of floor area shall fulfil the UDI requirements. Daylit area should be indicated in floor plans submitted to code enforcement authorities. Design guidelines on daylighting stated in NBC (Part 8: Building Services, Section 1: Lighting and Natural Ventilation, Subsection 4.2: Daylighting) should also be referred to achieve the ECBC, ECBC+, or Super ECBC requirement. Compliance with 4.2.3 Daylight Requirements can be checked for through two approaches.
(a) Analysis through software
If the whole building performance approach is used, compliance for daylighting requirements can be checked by analysing the façade and floor plate design in an analytical software approved by BEE (3.4). The image below, developed through an approved software, specifies the lux levels and time-period of a year during which lighting levels would be available. With this information, designers can check if the required minimum area as per 4.2.3 has the required daylight levels
UDI Analysis with a Daylighting Analysis Software
(b) Manual calculation method
For projects adopting the prescriptive compliance approach, manual calculation method can be used for UDI compliance.
From Table 4-3 determine the daylight extent factor (DEF) for each orientation. For a building located in Delhi (latitude > 15 degrees), with glazing of VLT ≥ 0.39, shading PF ≥0.4 and light shelves in windows, DEFs for windows in North = 3.5, in South = 3.0, in East = 2.1, and in West = 1.8. Head height is 3.0 m.
For fenestration clear of any opaque obstructions calculate daylit floor area (AxB).
A: In the direction perpendicular to the fenestration, daylit area extends to head height of the fenestration multiplied by the daylight extent factor (DEF) or distance till an opaque partition higher than head height of the fenestration, whichever is less.
B: In the direction parallel to the fenestration daylit area extends a horizontal dimension equal to the width of the fenestration plus either one meter on each side of the aperture or the distance to an opaque partition, or one-half the distance to an adjacent fenestration, whichever is least.
For overlapping daylit areas such as corner windows. Subtract the overlapping daylit area from the sum of daylit area.
UDI Analysis with manual calculations
As per the calculations 616.5 m2 of floor area will meet the UDI requirements during 90% of the year. This is 49.2 % of the total above grade floor area of 1,254 m2. Thus, the building floor will comply with UDI requirement. Following Tables shows calculated Daylight Area Meeting UDI Requirement.
Table 4-1-1Manual calculation for Daylight Area Meeting UDI Requirement
Orientation-NORTH, DEF-3.5, Fenestration Head Height H - 3m
Window without opaque obstructions
Fenestration Width W (m)
A= H x DEF (m)
B = L₁ + W + L₂ (m) L₁ = L₂ = 1m
Area meeting the UDI requirements = AxB (m²)
N7
2.0
10.5
4.0
42.0
N6
2.0
10.5
4.0
42.0
N2
2.0
10.5
4.0
42.0
Window with opaque obstructions
Fenestration Width W (m)
A= Distance till parallel Obstruction (m)
B = L₁ + W + L₂ (m) L₁ = L₂ = Distance to perpendicular Obstructions
Area meeting the UDI requirements = AxB (m²)
N1
2.0
10.5
0.3+2+0.3=2.6
27.3
N3
2.0.
4.0
0.4+2+0.4=2.8
11.2
N4
2.0
4.0
0.4+2+0.4=2.8
11.2
N5
2.0
4.0
0.4+2+0.4=2.8
11.2
N8
1.5
10.5
0+1.5+1.0=2.5
26.3
Daylit area meeting UDI requirement
213.2
Orientation-SOUTH, DEF-3, Fenestration Head Height H - 3m
Window without opaque obstructions
Fenestration Width W (m)
A= H x DEF (m)
B= L₁ +W+ L₂ (m) L₁ = L₂ =1m
Area meeting the UDI requirements = AxB( m² )
S1
1.2
6.2
1.0+1.2+1.0=3.3
20.1
S2
1.7
6.2
1.0+1.7+0.3=3.0
18.6
S3
21.0
9.0
1.0+21.0+1.0=24
216.0
Daylit area meeting UDI requirement
254.7
Orientation-EAST, DEF-2.1, Fenestration Head Height H - 3m
Window without opaque obstructions
Fenestration Width W (m)
A= H x DEF (m)
B = L₁ + W + L₂( m) L₁ = L₂ = 1m
Area meeting the UDI requirements = AxB(m²)
E1
1.5
6.3
1.0 + 1.5 + 1.0 = 3.5
22.1
E5
5.5
6.3
1.0 + 5.5 + 1.0 = 7.5
47.3
Adjacent fenestration less than two meter apart
Fenestration Width W (m)
A= H x DEF (m)
B = L₁ + W + L₂( m) L₁,L₂ = one half of distance to adjacent fenestration
Area meeting the UDI requirements = AxB(m²)
E2
2
6.3
1.0 + 2.0 + 0.2 = 3.2
20.2
E3
2
6.3
0.2 + 2 + 0.2 = 2.4
15.1
E4
2
6.3
0.2 + 2 + 1 = 3.2
20.2
Daylit area meeting UDI requirement
124.9
Orientation-WEST, DEF-1.8, Fenestration Head Height H - 3m
Window without opaque obstructions
Fenestration Width W (m)
A= H x DEF (m)
B = L₁ + W + L₂ (m) L₁ = L₂ = 1m
Area meeting the UDI requirements = AxB (m²)
W3
2.0
5.4
1.0+2.0+1.0=4.0
21.6
W4
1.4
5.4
1.0+1.2+1.0=3.2
17.3
Window with opaque obstructions in daylit area
Fenestration Width W (m)
A= H x DEF (m)
B = L₁ + W + L₂ (m) L₁ = L₂ = Distance to perpendicular Obstructions
Area meeting the UDI requirements = AxB (m²)
W1
1.0
5.4
0.3+1+0.3=1.6
8.6
W2
1.0
5.4
0.3+1+0.3=1.6
8.6
Daylit area meeting UDI requirement
56.1
Overlapping area calculations
Window with overlap areas
Width (m)
Depth (m)
Area ( m² )
N4 and S1
3.3
3.3
10.9
S3 and E5
3.3
6.5
21.5
Overlapping daylight area (b)
32.4
Total Daylit area
ORIENTATION
Daylit area (m2)
NORTH
213.2
SOUTH
254.7
EAST
124.9
WEST
56.1
Total daylight area (a)
648.9
Total Overlapping daylit area (b)
32.4
Total daylit area meeting UDI requirement during 90% of the year (a-b)