5.2.2.1 Chillers
(a) Chillers shall meet or exceed the minimum efficiency requirements under BEE Standards and Labelling Program for chillers as and when updated by BEE.
(b) For ECBC compliance, minimum 1 star rated chillier shall be installed.
(c) The application of air-cooled chiller is allowed in all buildings with cooling load less than 530 kW. For buildings with cooling load equal to or greater than 530 kW, the capacity of air-cooled chiller shall be restricted to 33% of the total installed chilled water capacity unless the authority having jurisdiction mandates the application of air-cooled chillers.
5.2.2.2 Unitary, Split, Packaged Air-Conditioners
Unitary air-conditioners shall meet or exceed the efficiency requirements given in Table 5-1. Window and split air conditioners shall be certified under BEE’s Star Labeling Program. EER shall be as per IS 8148 for all unitary, split, packaged air conditioners greater than 10 kWr.
| Cooling Capacity (kWr) | Water Cooled | Air Cooled |
|---|---|---|
| ≤ 10.5 | NA | BEE 3 Star |
| >10.5 | 3.3 EER | 2.8 EER |
5.2.2.3 Variable Refrigerant Flow
Variable Refrigerant Flow (VRF) systems shall meet or exceed the efficiency requirements specified in Table 5-2 as per the ANSI/AHRI Standard 1230 while the Indian Standard on VRF is being developed. BEE Standards and Labeling requirements for VRF shall take precedence over the current minimum requirement.
COMFORT SYSTEMS
COMFORT SYSTEMS
| For Heatin | g or cooling or both | ||
|---|---|---|---|
| Type | Size category (kWr) | EER(W/W) | IEER(W/W) |
| VRF Air | < 40 | 3.28 | 4.36 |
| Conditioners, | >= 40 and < 70 | 3.26 | 4.34 |
| Air cooled | >= 70 | 3.02 | 4.07 |
* The revised EER and IEER values as per Indian Standard for VRF corresponding to values in this table will supersede as and when the revised standards are published.
5.2.2.4 Air Conditioning and Condensing Units Serving Computer Rooms
Air conditioning and condensing units serving computer rooms shall meet or exceed the energy efficiency requirements listed in Table 5-3.
| Equipment type | Net Sensible Cooling Capacitya | Minimum SCOP-127b | |
| Downflow | Upflow | ||
| All types of computer room ACsAir/ Water/ Glycol | All capacity | 2.5 | 2.5 |
a. Net Sensible cooling capacity = Total gross cooling capacity - latent cooling capacity – Fan power
b. Sensible Coefficient of Performance (SCOP-127): A ratio calculated by dividing the net sensible cooling capacity in watts by the total power input in watts (excluding reheater and dehumidifier) at conditions defined in ASHRAE Standard 127-2012 Method of Testing for Rating Computer and Data Processing Room Unitary Air Conditioners)
5.2.2.5 Boilers
Gas and oil-fired boilers shall meet or exceed the minimum efficiency requirements specified in Table 5-4.
| Equipment Type | Sub Category | Size Category | Minimum FUE |
| Boilers, Hot Water | Gas or oil fired | All capacity | 80% |
| FUE - fuel utilization efficiency | |||