Buildings of the listed occupancy types or spaces in Mixed-use Buildings with the listed occupancy types.
-
Where attributes make a building eligible for more than one system type; use the predominant condition to determine the Standard Design system type provided the non-predominant conditions apply to less than 1,000m2of conditioned floor area. Use additional system type for non-predominant conditions if those conditions apply to more than 1,000 m2 of conditioned floor area.
Use additional system type for any space which has a substantial difference in peak loads and/or operational hours compared to the predominant space type. Such spaces may include but are not limited to computer/server rooms, retail areas in residential, or office buildings.
- One AHU per floor at a minimum.
WHOLE BUILDING METHOD
WHOLE BUILDING METHOD
| Hotel/Motel, Hospital Patient Rooms, Hotel Guest Rooms, Resorts, Villas, Sleeping Quarters in Mixed-use Buildings, Schools, Classrooms/Lecture Rooms¹ | Buildings with Less than or Equal to 12,500 m² of Conditioned Area | Buildings with More than 12,500 m² of Conditioned Area | Data Centre/ Server/ Computer Rooms | |
| Name | System A | System B | System C | System D |
| System Type² | Split AC | VRF: Variable Refrigerant Flow | VAV: Central cooling plant with variable volume AHU³ | Computer Room air conditioners |
| Fan Control | Constant Volume | Constant volume | Variable volume | Constant volume |
| Cooling Type | Direct expansion with air cooled condenser | Direct expansion with air cooled condenser | Chilled Water with water cooled condenser | Direct expansion with air cooled condenser |
| Heating Type | 1. Heat Pump: Where no heating system has been specified or where an electric heating system has been specified in the Proposed Design | 1. Heat Pump: Where no heating system has been specified or where an electric heating system has been specified in the Proposed Design | 1. Electric resistance: Where no heating system has been specified or where an electric heating system has been specified in the Proposed Design | NA |
| 2. Fossil Fuel Boiler, Fossil/Electric Hybrid: Where a heating system exists and a fossil fuel hot water boiler has been specified in the Proposed Design | 2. Fossil Fuel Boiler Fossil/Electric Hybrid: Where a heating system exists and a fossil fuel hot water boiler has been specified in the Proposed Design | 2. Fossil Fuel Boiler Fossil/Electric Hybrid: Where a heating system exists and a fossil fuel hot water boiler has been specified in the Proposed Design |
Notes:
-
Buildings of the listed occupancy types or spaces in Mixed-use Buildings with the listed occupancy types.
-
Where attributes make a building eligible for more than one system type; use the predominant condition to determine the Standard Design system type provided the non-predominant conditions apply to less than 1,000m2 of conditioned floor area. Use additional system type for non-predominant conditions if those conditions apply to more than 1,000 m2 of conditioned floor area.
Use additional system type for any space which has a substantial difference in peak loads and/or operational hours compared to the predominant space type. Such spaces may include but are not limited to computer/server rooms, retail areas in residential, or office buildings.
- One AHU per floor at a minimum.
| Automatic Control Device | Daytime occ and area <30 | upancy All Others 0 m<sup>2</sup> |
|---|---|---|
| Programmable Timing Control | 10% | 0% |
| Occupancy Sensor | 10% | 10% |
| Occupancy Sensor and Programmable Timi | ng Control 15% | 10% |