J-1. GENERAL.- (1) The planning and general building requirements in case of Low Income Housing (EWS and LIG) developed as clusters shall be as provided herein. These norms shall be applicable to all such housing projects undertaken by the Government departments and all Public/Private agencies.
(2) Such development should be as far as possible in clusters of 400 dwelling units, so distributed to maintain the overall densities of the Development Plan for the area.
J-2. PLANNING.- (1) Type of Development. The type of development for low income housing may be,-
(a) plotted development;
(b) flatted /Group Housing.
(2) Density.- The maximum density in terms of Dwelling units/hectare shall be as provided in the following table :-
Table
Maximum Densities of Economically Weaker Section and
Low Income Group Housing
[See clause J-2 (2)]
| S.No. | Density (dwelling Units/hectare) | No. of Storey's Permitted | |
| EWS | LIG | ||
| (1) | (2) | (3) | (4) |
| (i) | 130 | 85 | 1 |
| (ii) | 250 | 170 | 2 |
| (iii) | 300 | 225 | 3 |
| (iv) | 350 | 260 | 4 |
मध्यप्रदेश राजपत्र, दिनांक 13 अपैल 2012
392 (297)
Note 1. Vertical incremental housing shall be permitted in single ownership plot.
-
These densities include provision for open spaces convenient shopping, nursery and all internal roads and pathways, but do not include peripheral road around the cluster.
-
The minimum density shall be 75 per cent of the above.
-
The height of the building having four storeys as above shall not exceed 12.5 mtrs.
(3) (i) Size of Plot / built up Area. The plot area or the built up area for Economically Weaker Section and Lower Income Group houses shall be such, as may be decided by the State Government. The ground coverage may extend to a maximum of 75 per cent.
(ii) Minimum Frontage.-The minimum frontage of the plot shall be 3.6 mtrs.
(4) Height of building. The height of a building shall be as mentioned in sub-rule 2 (note-4) which shall not exceed 12.5 mtrs. In case the height has to be increased beyond 12.5 mtrs. lifts shall be provided. The density in terms of dwelling units per hectare shall be accordingly determined.
J-3. General building requirements.- The following norms shall also be adhered to :-
(1) Plinth.- The minimum height of plinth shall be 30 centimeters from the surrounding ground level.
(2) Size of room.
(a) Habitable Room-
(i) In the case of one-roomed house, the size of the multipurpose room including space for cooking shall be not less than 10 square meters with a minimum width of 2.4 meters.
(ii) In the case of two roomed house, the size of a room shall not be less than 6.5 square meters with a minimum width of 2.1 meters :
Provided that total area of both rooms is not less than 15 square-meters. In case of incremental housing to be developed as a future two roomed house, the total area of rooms to be provided in the initial and later stages shall not be less than 16 square meters.
392 (298)
(b) Water Closet/Bath Room.
(i) Size of independent water closet shall be 0.9 x 1.0 meters.
(ii) Size of independent bath shall be 1.0 x 1.2 meters.
(iii) Size of combined bath and water closet shall be 1.0 x 1.8 meters and this may be permitted in one roomed house.
(c) Kitchen. The size of cooking alcove serving as cooking space shall not be less than 2.4 square meters with minimum width of 1.2 meters. The size width of 1.2 meters. The size of individual kitchen provided in two-roomed house shall not be less than 3.3 square meters with a minimum width of 1.5 meters.
(d) Balcony - The minimum width of individual balcony, where provided, shall be 0.9 meter
(3) (a) Minimum Height -The minimum height of rooms/spaces shall be as follows:-
(i) Habitable Room - 2.6 meters.
(ii) Kitchen - 2.4 meters.
(iii) Bath/Water Closet - 2.2 meters.
(iv). Corridor - 2.1 meters.
(b) In the case of slopping roofs, the average height of roof for habitable rooms shall be 2.6 meters and the minimum height at eaves shall be 2.0 meters.
(4) Lighting and Ventilation. The openings through windows, ventilators and other for lighting and ventilation shall be as provided in sub-rule (3) of rule 82.
Note: The window and other opening shall abut on to open spaces either through areas left open within the plot or the front, side and rear spaces provided in the layouts which shall be treated as deemed to be sufficient for light and ventilation purposes.
(6) Stairs. The following criteria shall be adopted for internal individual staircase :-
(a) Minimum Width
(i) 2 storeyed - straight 0.60 meter
(ii) 2 storeyed - winding 0.75 meter
मध्यप्रदेश राजपत्र, दिनांक 13 अपैल 2012
392 (299)
(iii) 3 or more storeyed - straight 0.75 meter
(iv) 3 or more storeyed - winding 0.90 meter
(b) Riser 20 Centimeters Max.