- Plinth.-(1) Main Building. The plinth or any part of a building or out house shall be so located with respect to surrounding ground level that adequate drainage of the site is assured. The height of the plinth shall be not less than 45 centimeters from the surrounding ground level or reference level as the case may be.
(2) Interior courtyard. Every courtyard shall be raised to ensure satisfactory drainage.
- Habitable rooms.-(1) Height. The height of all rooms for human habitation shall not be less than 2.6 Meters measured from the surface of the floor to the lowest point of the ceiling (bottom of slab). In case of pitched roof; average height of rooms shall not be less than 2.6 meters. The minimum clear head room under a beam, folded plates or caves shall be 2.4 meters. In case of air-conditioned rooms a height of not less than 2.4 meters measured from the surface of the floor to the lowest point of air-conditioning duct or the false ceiling shall be provided.
(2) The requirements of sub-rule (1) apply to residential business and mercantile buildings. For educational and industrial building the following minimum requirements shall apply:-
(a) Educational building- Ceiling height 3.6 meters for all regions excepting cold region where it may be 3 meters.
(b) Industrial building- Ceiling height 3.6 Meters but if when air-conditioned 3 meters (Factory Act, 1948 and rules made thereunder shall govern such height where applicable).
(3) Size.
(a) The area of habitable room shall not be less than 9.5 square meters where there is only one room with a minimum width of 2.4 meters. Where there are two rooms, one of these shall not be less than 9.5 square meters and the other be not less than 7.5 square meters with a minimum width of 2.1 meters. In the case of hostels in educational institutions the minimum size of a habitable room for single person shall be 7.5 square meters.
(b) However, in the case of special housing schemes for Economically Weaker Section of Society, Low Income Group Housing, the norms for the size of the rooms shall be as provided in Appendix - J.
392 (239)
- Kitchen.- (1) Height. The height of a kitchen measured from the surface of floor to the lowest point in the ceiling (bottom slab) shall not be less than 2.6 m meters except for the portion to accommodate floor trap of the upper floor.
(2) Size. The area of a kitchen where separate dining area is provided shall not be less than 5.0 square meters and with a minimum width of 1.8 meters. Where there is a separate store, the area of kitchen may be reduced to 4.5 square meters. A kitchen, which is intended for use as a dining area also, shall have a floor area of not less than 7.5 square meters with a minimum width of 2.1 meters.
(3) Other requirements. Every room to be used as kitchen shall have,-
(a) unless separately provided in a pantry, means for the washing of kitchen utensils which shall lead directly or through a sink to a grated and trapped connection to the waste pipe;
(b) an impermeable floor;
(c) a flue, if found necessary; and
(d). a window or ventilator or opening of size not less than, as specified in note 3 of sub-rule (3) of rule 82.
- Bathroom and Water Closets.- (1) Height. The height of a bathroom or water closet measured from the surface of the floor to the lowest point in the ceiling (bottom of slab) shall not be less than 2.2 meters.
(2) Size. (a) The size of a bathroom shall not be less than 1.5 square meters. The floor area of water closet shall be 1.1 square Meters with a minimum width of 0.9 meter. If bath and water closet are combined, its floor area shall not be less than 2.4 square Meters with a minimum width of 1.2 meters. The area of Water Closet with wash basin shall not be less than 1.3 square meters;
(b) the sizes of bathrooms/water closets shall be as follows:-
(i) Independent water closet - 1.1 meter X 0.9 meter.
(ii) Independent bathroom - 1.3 meter X 1.1 meter.
(iii) combined bathroom and closet-2.0 square meters width, minimum width of 1.1 meters.
(iv) Water closet with wash basin 1.3 square meters.
(3) Other requirements. Every bathroom or water closet shall,-
(a) be so situated that at least one of its walls shall open to external air;
392 (240)
(b) not be directly over or under any room other than another water closet, washing place, bath or terrace, unless it has a water tight floor;
(c) have the platform or seat made of watertight non-absorbent material;
(d) be enclosed by wall or partitions and the surface of every such wall or partitions shall be finished with a smooth impervious material to a height of not less than 1 meter above the floor of such a room;
(e) be provided with an impervious floor covering, sloping towards the drain with a suitable grade and not towards verandah or any other room; and
(f) have a window or ventilator, opening to a shaft or open space, of area not less than 3 square Meters with side not less than 0.3 meter.
(4). No room containing water-closet shall be used for any purpose except as a lavatory and no such room shall open directly into any kitchen or cooking space by a door, window or other opening. Every room containing water-closet shall have a door completely closing the entrance to it.
- Ledge or Tand / Loft.- (1) Height. It shall have a minimum head-room of 1.5 meters.
(2) Size. A ledge or "tand" in a habitable room shall not cover more than 25 per cent of the area of the floor on which it is constructed and shall not interfere with the ventilation of the room under any circumstances.
(3) Loft. A loft, if provided, on a kitchen shall not exceed 25 per cent of the area of kitchen and shall leave minimum height of 2.2 meters under the loft. On bathroom, water-closet and corridor, the loft may cover as much area as would allow a person to keep article there with reasonable space for body movement.
- Mezzanine (Entresol) Floor.- (1) Height. It shall have a minimum height of 2.2 meters.
(2) Size. The minimum size of the mezzanine floor, if it is to be used as a living room, shall not be less than 9.5 square meters. The aggregate area of such mezzanine floor in a building shall in no case exceed 1/3 of the plinth area of the room in which it is provided.
(3) Other requirements.. A mezzanine floor may be permitted over a room or a compartment :
Provided that,-
मध्यप्रदेश राजपत्र, दिनांक 13 अपैल 2012
392 (241)
(a) it conforms to the standards of living rooms as regards lighting and ventilation in case the size of mezzanine floor is 9.5 square meters or more;
(b) it is so constructed as not to interfere, under any circumstances, with the ventilation of the space over and under it;
(c) such mezzanine floor is not sub-divided into smaller compartments;
(d) such mezzanine floor or any part of it shall not be used as a kitchen; and
(e) in no case a mezzanine floor shall be closed so as to make it liable to be converted into unventilated compartments.
- Store room.- (1) Height. The height of a store room shall not be less than 2.2 meters.
(2) Size. The size of a store room, where provided in a residential building shall not be less than 3 square meters.
- Garage.- (1) Height. The height of a garage shall not be less than 2.2 meters.
(2) Size. The size of garage shall not be less than as below :-
(a) Private Garage- 2.5 meters X 5.0 meters.
(b) Public Garage- Based on the number of vehicles parked etc., (Refer rule 84 parking space).
- Basement.- (1) Basement shall not be used for habitable purpose except in case mentioned in sub-rule (b) of rule 2.
(2) The construction of the basement may be allowed in all the land uses subject to the following conditions, namely 2 :-
(a) basement shall not extend beyond the prescribed MOS :
Provided that where minimum MOS are more than 12 meters in front or more than 7.5 meters on all other sides, in that case basement may be allowed leaving 12 meters distance in front and 7.5 meters on other sides;
(a) the plinth level of the building in which the basement is built shall not be more than 0.45 meters above ground level, or reference level as the case may be; and
(b) in certain cases, depending on the topography of the site the part of the building below the ground or reference level could also be called the basement and if such part is habitable, then
392 (242)
मध्यप्रदेश राजपत्र, दिनांक 13 अप्रेल 2012
it may be used accordingly and shall be added in the calculation of FAR.
(3) Basement may be put to the following uses, namely :-
(a) storage of noncombustible articles;
(b) strong rooms, bank cellars, radiation room (only for medical treatment and research);
(c) air-conditioning equipment and other machine used for services and utilities of the building; and
(d) parking spaces;
(e) commercial activity only on the first basement level : Provided that,-
(i) the land use of the premises / plot is commercial;
(ii) the plot area is not less than 1.0 hectare; and
(iii) the building is detached, the basement area permitted for commercial use shall be taken into account for the purpose of calculating the FAR.
(4) The basement shall have the following requirement, namely :-
(a) basement in every part shall have a clear height of at least 2.4 meters as measured from the floor to the underside of the beam, in case of clause 3(e) above, the minimum clear height as calculated above shall be 3.6 meters;
(b) adequate ventilation shall be provided for the basement, the ventilation requirements shall be the same as required by the particular occupancy according to these rules. Any deficiency may be met by providing adequate mechanical ventilation in the form of blowers, exhaust fans, air-conditioning systems or the like;
(c) the maximum height of the ceiling of any basement shall be 0.45 meter above the average surrounding ground level in such a fashion that vehicular movement in the MOS or around the buildings are not obstructed;
(d) adequate arrangements shall be made as such that the surface drainage does not enter the basement;
मध्यादेश राजपत्र, दिनांक 13 अपैल 2012
392 (243)
(e) the walls and floors of the basement shall be watertight and be so designed that the effect of the surrounding soil and moisture are taken into account in design and adequate damp proofing treatment done;
(f) the access to the basement shall be separate from the main entrance and in addition another staircase/ramp shall be provided for. access to and exit from various floors of the basement where the staircase/ramp is continuous the same shall be of enclosed type serving as a fire separation from the basement floor and higher floors; and
(g) open ramps as means of access to the basement may be permitted :
Provided that such ramp do not obstruct the MOS in any manner.
(5) A maximum of three levels may be allowed in the construction of multi-level basements. Such multi-level basement may be allowed only if,-
(a) The minimum frontage of the plot is 21 meters and the minimum average depth 30 Meters and the plots abuts a road of width 18 meters or more; and
(b) the building is detached.
(6) If the built form below the ground or reference level is used as habitable accommodation because of the existing topography such area may be permitted as habitable area and shall be counted in the Floor Area Ratio.
-
Parapet.- Parapet walls and handrails provided on the edges of roofs terraces, balcony, corridors/ lobbies/ foyers or verandah shall not be less than 1.05 meters in height from the finished floor level.
-
Boundary Wall.- The requirements of boundary wall are given below:-
(a) The maximum height of the compound wall shall be 1.5 meters above the center line of the front street unless the Authority permits a higher wall.
(b) The rear and side compound walls shall not have a height more than 3 meters above the central line of the service road in case it exists otherwise it shall be 2 meters. It shall be measured above the central line of the front street. In case of
392 (244)
मध्यादेश राजपत्र, दिनांक 13 अपैल 2012
a corner plot the height of the boundary wall abutting on the side road shall also not be more than 1.5 meters
(c) the provisions of (a) and (b) are not applicable to boundary walls of jails, electric sub-stations, transformer stations, institutional buildings, like sanatoria, hospitals, industrial buildings like work-shops, factories and educational buildings like schools, colleges, including the hostels and other uses of public utility undertaking, where height as required, may be permitted by the Authority.
- Septic Tanks.- Where a septic tank is used for sewage disposal, the location, design and construction of the septic tank shall conform to the following requirements :-
(1) Location of Septic Tanks and Sub-Surface absorption systems. A sub-soil dispersion system shall not be located within 18 meters from any source of drinking water. It shall also be as removed from the nearest habitable building as economically feasible but not within 2 meters thereof so that there is no damage to the structures.
(2) Other Requirements.
(a) Dimensions of septic tanks. Septic tanks shall have minimum width of 75 centimeters and minimum depth of one meter below the surface level and a minimum liquid capacity of one cubic meter. Length of tanks shall be 2 to 4 times the width;
(b) septic tanks may be constructed of brick work /stone masonry/ concrete or other suitable materials as approved by the Authority;
(c) under no circumstances should effluent from a septic tank be allowed into an open channel drain or body of water without adequate treatment;
(d) minimum nominal diameter of pipe used shall be 100 millimeters. Further at junctions of pipes in manholes, direction of flow from a branch connection should not make an angle exceeding 45 degrees with the direction of flow in the main pipe;
(e) the gradients of land drains, under-drainage as well as the bottom of dispersion trenches and soak ways should be between 1:300 and 1:400;
(g)
मध्यप्रदेश राजपत्र, दिनांक 13 अपैल 2012
392 (245)
every septic tank shall be provided with ventilating pipe of at least 50 millimeters diameter. The top of the pipe shall be provided with a suitable case of mosquito proof wire mesh. The ventilating pipe shall extend to a height, which would cause no smell nuisance to any building in the area. Generally, the ventilating pipe may extend to a height of about 2 meters when the septic tank is at least 15 meters away from the nearest building and to a height of 2 meters above the top of the building when it is located closer than 15 meters;
when the disposal of septic tank effluent is to seepage pit, the seepage pit may be of any suitable shape with the least cross-section dimension of 90 centimeters and not less than 100 centimeters in depth below the invert level of the inlet pipe. The pit may be lined with stone, brick or concrete blocks with dry open joints which should be backed with at least 7.5 centimeters of clean coarse aggregate. The lining above the inlet level should be finished with mortar. In the case of pits of large dimensions, the top portion may be narrowed to reduce the size of the reinforced cement concrete cover slabs. Where no lining is used, specially near trees, the entire pit should be filled with loose stones. A masonry ring may be constructed at the top of the pit to prevent damage by flooding of the pit by surface run off. The inlet pipe may be taken down to a depth of 90 centimeters from the top as an anti-mosquito measures; and
(h) when the disposal of septic tank effluent is to a dispersion trench, the dispersion trench shall be 50 to 100 centimeters deep and 30 to 100 centimeters wide excavated to gradient and shall be provided with 10 to 25 centimeters of washed gravel or crushed stone. Open joints placed inside the trench shall be made of unglazed earthenware pipes clay or concretes and shall have minimum internal diameter of 75 to 100 millimeters. Each dispersion trench should not be longer than 30 meters and trenches should not be placed closer than 1.8 meters.
- Staircase.- (1) The minimum clear width and maximum riser of staircases for buildings shall be as given in sub-rule (2) to (4).
392 (246)
(2) Minimum Width. The minimum width of staircase shall be as follows:-
(i) Residential buildings (Dwellings) 0.85 meters
(ii) hotel buildings. 1.5 meters
(iii) Assembly buildings like auditorium, 1.5 meters theatres and cinemas
(iv) Educational buildings-
(a) up to 24 m in height 1.5 meters
(b) more than 24 m in height 2.0 meters
(a) up to 10 beds 1.5 meters
(b) more than 10 beds 2.0 meters
(vi) All other buildings 1.5 meters
(3) The landing width shall be a minimum of twice the staircase width plus 15 centimeters.
(4) Minimum Tread. The minimum width of tread without nosing shall be 25 centimeters for residential buildings. The minimum width of tread for other buildings shall be 30 centimeter.
(5) Maximum Riser-The maximum height of risers shall be 17 centimeters for residential buildings and 15 centimeters for other buildings and these shall be limited to 15 numbers per flight.
(6) Head Room. The minimum head-room in a passage under the landing of a staircase shall be 2.2 meters. The minimum clear head-room in any staircase shall be 2.2 meters.
- Roofs.- (1) The roof of a building shall be so constructed or framed as to permit effective drainage of the rain water therefrom by means 0f sufficient rain-water pipes of adequate size, whenever required, so arranged, Jointed and fixed as to ensure that the rain-water is carried away from the building without causing dampness in any part of the walls or foundations of the building or those of an adjacent building.
(2) The Authority may require rain-water pipes to be connected to a drain or sewer or a covered channel beneath the public footpath or in any other approved manner.
(3) Rain-water pipes shall be affixed to the outside of the external walls of the building or in recesses or chases cut or formed in such external walls or in such other manner as may be approved by the Authority.
392 (247)
(4) Rain/Roof water harvesting method shall have to be provided on all type of buildings having plot size more than 140 Square meter as per the options mentioned in APPENDIX – H-1, H-2 and H-3.