Additional Provisions for providing barrier-free environment in the public buildings for persons with disabilities
33 Definitions
(i) Non-ambulatory disabilities : Impairments that regardless of cause or manifestation, for all practical purposes, confine individuals to wheelchairs.
(ii) Semi-ambulatory disabilities : Impairments that cause individual to walk with difficulty or insecurity. Individuals using braces or crutches, amputees, arthritis, spastics and those with pulmonary and cardiac ills may be semi-ambulatory.
(iii) Hearing disabilities : Deafness or hearing handicaps that make an individual insecure in public areas because he is unable to communicate or hear warning signals.
(iv) Sight disabilities : Total blindness or impairment affecting sight to the extent that the individual functioning in public areas is insecure or exposed to danger.
(v) Wheel Chair : Chair used by disabled people for mobility.
a) Size of Small Wheel Chair : 750 x 1050 mm
b) Size of Large Wheel Chair : 800 x 1500 mm
34 Provision of Facilities in Public Buildings for Disabled Per-sons
(A). Scope : These byelaws are applicable to all building, recreation areas & facilities used by public. It does not apply to private domestic residences.
i) Site planning: Level of the roads, access paths & parking areas shall be described in the plan along with specification of materials. Every building should have at least one access to main entrance/exit to the disabled which shall be indicated by proper signage. This entrance shall be approached through a ramp together with stepped entry. The ramp should have a landing after every 9 Metre run and in front of the doorway. Minimum size of landing shall be 1000 x 2000 mm.
ii) Access path/walk way: Access path from plot entry and surface parking to building entrance shall be minimum of 1800 mm wide having even surface without any step. Slope, if any, shall not have gradient greater than 5%. Selection of floor material shall be made suitably to attract or to guide visually impaired persons (limited to floor material whose colour texture is conspicuously different from that of the surrounding floor material or the material that emit different sound to guide visually impaired persons). Finishes shall have a non-slip surface with texture traversable by a wheel chair. Curbs wherever provided should blend to common level.
iii) Parking: For parking of vehicles of disabled people, the following provisions shall be made.
(a) Surface parking for two Equivalent Car Spaces (ECS) shall be provided near entrance for the physically handicapped persons with maximum travel distance of 30 metre from building entrance.
(b) The width of parking bay shall be minimum 3.6 metre.
(c) The information stating that the space is reserved for wheel chair users shall be conspicuously displayed.
(d) Guiding floor materials shall be provided or a device which guides visually impaired persons with audible signals or other devices which serves the same purpose shall be provided.
(B). Building requirements: The specified facilities for the buildings for disabled persons which shall be provided with Braille signage shall be as follows:
i) Approach to Plinth Level: Ramp shall be provided with non-slip material to enter the building. Minimum clear width of ramp shall be 1800 mm with maximum gradient 1:12 between top and bottom of the ramp. Length of ramp shall not exceed 9.00 metres having 800 mm high handrail on both sides extending 300 mm beyond the ramp. Minimum gap from the adjacent wall to the handrail shall be 50 mm. Minimum clear opening for the entrance door shall be 1000 mm. Threshold shall not be raised more than 12 mm. For stepped approach, size of tread shall not be less than 300 mm and maximum riser shall be 150 mm. Provision of 800 mm high handrails on both sides of the stepped approach similar to the ramped approach shall be made.
ii) Corridor connecting the entrance/exit for the handicapped: The corridor connecting the entrance/exit for the handicapped leading directly outdoors to a place
where information concerning the overall use of the specified building can be provided to visually impaired person either by a person or by signs, shall be provided as follows.
a) Guiding floor materials shall be provided or devices that emit sound to guide visually impaired persons.
b) The minimum width shall be 1500 mm.
c) In case there is a difference of level, slope ways shall be provided with a slope of 1:12
d) Handrails shall be provided for ramps/slope ways.
iii) Stair-ways: Stairways with open riser and provision of nosing are not permitted in such building.
iv) Lift: Whenever lift is required as per byelaws, provisions of at least one lift shall be made for the wheel chair user with the following car dimensions of lift recommended for passenger lift of 13 persons capacity by Bureau of Indian Standard.
Clear internal depth 1100 mm
Clear internal width 2000 mm
Entrance door width 910 mm
a) A handrail not less than 600 mm long at 900 mm above the floor level shall be fixed adjacent to the control panel.
b) The lift lobby shall be of an inside measurement of 1800 mm x 2000 mm or more.
c) The Braille signage will be posted outside the lifts.
d) Operational details of lifts shall confirm to the National Building Code (NBC) and will be the responsibility of designer as well as manufacturer.
v) Toilets: One special WC in a set of toilet shall be provided for the use of the handicapped with essential provision of washbasin near the entrance for the handicapped.
a) The minimum size shall be 1500 mm x 1750 mm.
b) Minimum clear opening of the door shall be 900 mm and the door shall swing out/sliding type.
c) Suitable arrangement for vertical/horizontal handrails with 50 mm clearance from wall shall be made in the toilet.
d) The WC seat shall be 500 mm from the floor.
vi) Drinking water: Drinking water facilities shall be made accessible for the disabled
(C). Refuge: An alternative to immediate evacuation of a building via staircases and/or lifts is the movement of disabled persons to areas of safety within a building. If possible, they could remain there until the fire is controlled and extinguished or until rescued by fire fighters. It is useful to have the provision of a refuge area, usually at the fire protected stair landing on each floor that can safely hold one or two wheel chairs.
(i) Have doorways with clear opening width of 900 mm
(ii) Have an alarm switch installed between 900 mm and1200 mm from the floor level.