75 Definitions.—
In this Chapter, unless the context otherwise requires,—
(a) “exit” means an escape route which includes passage, channel or means of access from any buildings, storeys or floor area to a street or other open space of safety and includes a vertical exit or a horizontal exit or an outside exit;
Explanation.—In this clause,—
(i) “vertical exit” means an exit used for ascension or descension between two or more levels including stairways, smoke proof towers, ramps, lifts, escalators and fire escapes,
(ii) “horizontal exit” means a protected opening through or around a fire wall or a bridge connecting two buildings,
(iii) “outside exit” means an exit from the building to a street or to an open area leading to a street or to an enclosed fire resistive passage leading to a street;
(b) “travel distance” means the distance from the exit of a tenement of any premises on a floor of a building to a place of safety, be it a vertical exit, a horizontal exit or an outside exit, measured along the line of travel.
76 Fire protection.—
Every building for residential and educational uses of more than fourteen meters and a half in height, and all buildings of other uses and buildings with basement shall be provided with adequate means of exit and all arrangement for protection in case of fire.
77 General exit requirements.—
(1) The following general requirements shall apply to exit:—
(a) all vertical exits or horizontal exits shall be free from obstructions;
(b) no building shall be altered so as to reduce the number, width or protection of exits to less than what is required under these rules;
(c) exits shall be clearly visible and routes to reach each exit shall be clearly marked;
(d) all exits shall be properly illuminated;
(e) fire-fighting equipment shall, where provided along exits, be suitably located and clearly marked so as not to obstruct the exit way and there shall be clear indication about its location from either side of the exit;
(f) alarm devices shall be installed to ensure prompt evacuation through exits;
(g) all exits shall provide continuous means of access to the exterior of a building or to an exterior open space leading to a street or means of access;
(h) exits shall be so arranged that may be reached without passing through another occupied unit, except in the case of a building for residential and educational uses.
(2) An exit may be a door-way, corridor, passage-way to staircase, ramp or a varandah or terrace which has access to the street or to the roof of a building. An exit may also include a horizontal exit leading to an adjoining building at the same level.
(3) Lifts and escalators shall not be considered as exits:
Provided that if the lift, lobby and shaft is provided as per requirement of West Bengal Fire and Emergency Services, it shall be considered as fire escape route.
(4) All basements shall have a minimum of two exits.
Explanation.—Ramps to the basement shall be considered as exits.
78 Arrangements of exits.—
(1) Exits shall be so located that the distance between two exits on the floor shall not exceed,—
(a) 22.5 meters, in the case of a residential building or an educational building or an institutional building or a hazardous building; and
[P AR T I
(b) 30 meters, in the case of an assembly building or a business building or a mercantile building or an industrial building or a storage building.
(2) For floors with sprinklers, which are not part of requirements for that floor and occupancy, the distance in subrule (1) may be increased by 50 per cent.
(3) The distance to an exit from the dead end of a corridor shall not exceed half the distance specified in sub-rule (1), except in an educational building or an assembly building or an institutional building in which case it shall not exceed 6 meters.
(4) Whenever more than one exit is required for any room, space or floor of a building, exits shall be placed as remote from each other as possible and shall be arranged to provide direct access in separate directions from any point in the area served.
79 Requirements regarding staircase.—
All buildings referred to in rule 76 shall be provided with such number of staircases as the Board of Councillors may require. Under no circumstances, the number of staircases shall be less than two in the case of a building of more than fourteen meters and a half in height and one of them shall be on the external face of the building and shall be enclosed or pressurised type as per requirements of West Bengal Fire Services. In case the staircase or staircases are not facing external surface of the building or not having ventilation shaft, mechanical ventilation is required.
80 Minimum Width Provisions.—
(1) The following provisions for minimum width of stairways shall be made:—
TABLE I
| Category of Building | Height of the Building (in meters). | Width of the Stairway (in meters). | No. of Staircase. |
|---|---|---|---|
| Residential | Up to 8.00 | 1.00 | 1 |
| Above 8.00 & Up to 11.00 | 1.2 | 1 | |
| Above 11.00 & Up to 14.50 | 1.35 | 1 | |
| Above 14.50 & Up to 18.00 | 1.25 | 2 | |
| Above 18.00 & Up to 24.00 | 1.25 | 2 | |
| Above 24.00 & Up to 36.00 | 1.25 | 2 | |
| Above 36.00 | 1.50 | 2 |
(2) For residential buildings of height above 14.5 m and upto a height of 24.00 m with not more than three tenements or 500 sqm. per floor (whichever is less), one staircase of 1.50 mtrs. of width may be permitted. If by any case the floor area or the number of tenements exceed the above value, the number of staircase should be increased as per the prescribed norms in table given below:—
43
TABLE II
| Category of building. | Area per floor. | Width of the Stairway (Mtr.). | Minimum Number Staircase of (Height upto ll.OMtrs.). | Minimum Number of Staircase (Height above ll.OMtrs.). |
| Educational | Upt o 500 sqm. | 1.35 | 2 | 2 |
| Above 500 sqm. | 2.0 | 2 | 2 | |
| Assembly | Up to 500 sqm. | 1.50 | 1 | 2 |
| Above 500 sqm. | 2.0 | 2 | 2 | |
| Institutional | Up to 500 sqm. | 1.50 | 1 | 2 |
| Above 500 sqm. | 2.0 | 2 | 2 | |
| Business | Up to 500 sqm. | 1.50 | 1 | 2 |
| Above 500 sqm. | 1.50 | 2 | 2 | |
| Mercantile | Up to 500 sqm. | 1.80 | 2 | 2 |
| (Retail) | Above 500 sqm. | 2.00 |
81 Provision for doors for an assembly room or hall.—
The doors of a room or a hall, where groups of people congregate or gather in any building, shall be made to open outwards and no locks or bolts for closing the same from outside shall be affixed thereto. There shall be at least two such doors in every such room or hall if not more than 300 persons are intended to be accommodated therein and an additional door shall be provided for every 100 persons or part thereof in excess of 300 persons. The width of every such door shall not less than 1.80 meters.
82 Other requirements.—
In respect of matters relating to fire prevention and fire protection, for which provisions have not been made in this part, the provisions of the latest edition of the National Building Code and the latest edition of the National Electrical Code shall apply.
83 Consultation with the Director of Fire Services before granting permission to erect a building.—
No permission for the erection, addition to, or alteration of, any building other than a residential building or an educational building of less than fourteen meters and a half in height shall be granted unless the Board of Councillors in consultation with the Director of Fire Services of the Government of West Bengal or any Officer specially empowered by the Director for the purpose, is satisfied about the provision of means of exits and about the arrangements for protection against fire proposed for the building.
84 Power to Municipal Authority to ask for sufficient means of exits.—
Where on the basis of the report of the Director of Fire Services of the Government or any other officer specially empowered by him, the Municipal Authority is of opinion that the means of exit from any building is insufficient to allow safe exit in the event of fire, or the in-built fire protection measures are inadequate, he may by written notice require the owner or occupier of the building to alter or reconstruct any existing staircase in such manner, or to provide such additional or emergency staircases as he may determine, or such fire protection measures, as he may, in consultation with the Director of Fire Services of the Government or any other officer specially empowered by him, determine.
85 Requirements of special occupancies under any other law in force.—
Notwithstanding anything contained in these rules, a building shall comply with the special requirements, if any, laid down in the Factories Act, 1948 (63 of 1948) or in any other law for the time being in force in relation to such building.