(1) Plinth area shall be considered from Plot boundary Centerline sharing the approach road. The plinth of the main building shall be sited with respect to surrounding ground level for proper drainage of the plot. The height of the plinth shall not be less than 450 mm and more than 1.5 meters in the case of independent building not sharing party wall. If the party wall is shared the plinth level shall be the same as already laid for the party wall.
(2) The plinth of courtyard shall be at least 150 mm above the level of the street from where entry to plot has been taken and shall be satisfactorily drained.
(3) In no case, any part of the ramp/steps connecting building plinth to street/road shall lie on street/road and obstruct traffic movement.
Chapter 8Parking v/s Building
8.1 Parking Car Space norms for buildings land-use-wise shall be as follows:
(1) Car space Norms for residential plots:
Sr. No.
Size of plot (square meters)
No of ECS
1
Above 500
1 ECS for each dwelling unit.
2
Above 250 to 500
0.75 ECS for each dwelling unit.
3
Above 150 to 250
0.5 ECS for each dwelling unit.
4
Up to 150
Not required
Note-One ECS=12.5 sq. m. to be indicated in car bay size of 2.5 m X 5 m in residential plots. No on street parking where the right of way of road/street is less than 12 meters shall be permissible
(2) For Group Housing minimum 1.5 Equivalent Car Space (ECS) for each dwelling unit,
(3) For integrated/multi storied commercial building, big retail stores, restaurant, multiplex/ cinema/ theatre, and shopping mall 1.0 ECS for every 50 square meters of covered area,
(4) For offices, cyber park/IT park/ cyber cities, 1.0 ECS for every 75 square meters of covered,
(5) For shopping area and designated shopping markets being developed by competent authority, 65% of total site area shall be kept for parking purpose,
(6) For hospitals/1.0 ECS for every 2 beds and for visitors 1 ECS for every 4 beds,
(7) For industries, 1.0 ECS for every 300 square meters of covered area,
(8) For assembly buildings (i.e., standalone theatres, cinema houses, concert halls, auditoria, and assembly halls), 1 ECS for every 40 square meters of covered area,
(9) For primary and secondary schools, 15% of total site area for parking purpose,
(10) For college, parking at rate of 1 ECS for every 200 square meters of covered area,
(11) For government or semi-public offices including civil/High Court, 1 ECS for every 75 square meters of covered area,
(12) For hotels and Motels, 1.0 ECS for every 75 square meters of covered area,
(13) For institutional/ educational/ assembly buildings with parking areas, designate space in parking lots for on-site snow storage in areas that maximize sunlight and melting, while being mindful of drainage considerations
(14) Covered parking in the basement or in the form of multi-level parking above ground level or stilt shall not be counted towards FAR. However, the footprint of separate parking building block(s) shall be counted towards ground coverage. For existing properties, separate parking area shall not be counted towards FAR.
(15) Parking facilities need to include no-parking zones as per DCRs and Master Plans
of the respective Local bodies
(16) Necessary changes may be made in the parking as per subsequent Development Plans and requirement of the time for which the changes are being provided. Furthermore, Code 3.3 of Model Building Bye Laws 2016 needs to be referred, wherever not mentioned in these Bye-Laws.
(17) In case of provision of mechanical parking in the basement floor/upper stories, the floor to ceiling clear height of the basement/floor shall be maximum of 4.75 meters.
(18) No storage and commercial activities shall be permissible in the covered parking areas,
(19) The misuse of the covered parking space shall immediately attract levy of three times the penalty of the composition fee prescribed (i.e., applicable collector rates for the locality) for the excess covered area in the respective category.
(20) Fast charging facilities need to be incorporated at feasible locations for high volume of vehicles
8.2 Applicable Car Space norms for sub-code 8.1 (1) to (19) above shall be as under:
i. 1 ECS = 23 square meters for open parking,
ii. 28 square meters for parking on stilts and
iii. 32 square meters for basement parking.
8.3 Party Wall
(1) In case the plot holder intends to construct a common boundary wall with minimum width of 230mm, shall be required to submit consent of owners of adjacent plots with which plot shares a common boundary i.e., the plot on both sides and at the rear.
(2) Wherever the plot owner opts for independent boundary wall within the plot boundary:
(i) shall be allowed independent boundary wall only where adjacent plots are vacant, and,
(ii) the owner shall ensure that no part of foundation and boundary wall is constructed on the adjoining plot.
8.4 Courtyard
Interior courtyard for light and ventilation of habitable rooms shall not be less than 12.0 square meters in area and the minimum width of every such courtyard in any direction shall not be less than 3.0 meters.
8.6Minimum area, size, height, light and ventilation required for different components of Residential buildings
(1) Minimum area of a habitable room, kitchen and water closet shall be followed in accordance with tablet given as under:
Sr. No.
Room type
Minimum area (in square meters
Minimum width (in meters)
Minimum clear Height (in meters)
Light and Ventilation (area of openable windows, ventilators)
1
Habitable room
9.5
2.4
2.40
Not less than 1/8th of the total floor area of the room.
2
Kitchen
5.5
1.8
2.40
Not less than 1/8th of the total floor area of the room.
3
Pantry
3.00
1.40
2.10
Not applicable
4
Bathroom
1.80
1.20
2.10
5
Water Closet
1.1
0.90
2.10
6
Combined Bath and Water Closet
2.8
1.2
2.10
0.3 square meters on wall not less than 0.3 meters wide.
7
Store
No restriction
No restriction
2.10
Not applicable
8
Garage
14.85
2.75 x 5.40
2.40
9
Doorways Habitable room
Not applicable
0.90
1.95
10
Doorways for kitchen, bath, W.C
Not applicable
0.75
2.10
(2) Habitable room Size and height
(i) In case of Group Housing scheme, the dwelling unit having more than one room may have one of the rooms with a clear floor area not less than 7.5 sq. meters with one side not less than 2.4 meters,
(ii) in case of air-conditioned rooms, the height shall not be less than 2.4 meters measured from the surface of the floor to the lowest point of air conditioning duct or false ceiling; and,
(iii) all doors and windows shall open directly or through a verandah or to a permanent open space or an open space abutting the building not less than 1.8 meters in width.
(3) Bathroom and Water Closet (W.C)
(i) Every bathroom and water closet shall:
(a) preferably be so situated that at least one of its walls shall have opening for circulation of external air, with provision of exhaust fan, and,
(b) toilet be provided with impervious floor covering sloping towards the drain with a suitable gradient.
(ii) where the water-closet in a building is not connected to exterior, it shall be
ventilated by mechanical means or through a vertical shaft open to sky of a minimum size stated in the Model Building Bye Laws 2016, for ventilation to toilet, bath, and water closet, and shall be counted in covered area,
(iii) no room containing water-closet shall be used for any other purposes except as lavatory and no such room shall open directly into any kitchen or cooking space by a door/ window or another opening, and every room containing water- closet shall have a door completely closing its entrance.
(iv) soil or ventilating pipes shall not be allowed on the exterior face of any building, provided these shall either be embedded in the walls or pipe ducts to be provided to accommodate them.
(v) Security rooms each measuring maximum area of 3.0 square meters is permitted only at the entry-exit gates of premises.
(vi) All commercial buildings should necessarily design a public toilet with winter friendly technology and universal design. Buildings with plinth areas more than 75 sqm shall be accessible from outside of main building block.