(1) The courtyard shall have a minimum area, throughout its height, of not less than the square of one-fifth the height of the highest wall abutting the courtyard. Provided that when any room (excluding staircase bay, bathroom and watercloset) is dependent for its light and ventilation on an inner courtyard, the dimension shall be such as is required for each wing of the building.
(2) Provided that such courtyard shall not be less than square metres in area and the minimum width of every such courtyard in any direction shall not be less than 3.0 metres. In determining the said aggregate, floor area of the rooms and verandah abutting on the courtyard, following shall be considered:-
(i) Only one half of the floor area of such rooms and verandahs as abut on another courtyard or an open space or road not less than 6 metres in width shall be taken in account;
(ii) The area of the courtyard for the purposes of this Code shall be the area open to sky, clear of all projections.
Chapter 7Building Design Norms
7.1 Parking
(1) In plots situated in plotted colony, minimum 1.5 Equivalent Car Space (ECS) for each dwelling unit shall be required.
(2) In Group Housing minimum 1.5 Equivalent Car Space (ECS) for each dwelling unit shall be required. Further minimum 5% of the total car parking area shall be made available to the EWS category flats.
(3) In Integrated/ Multi Storey Commercial Building, Big Box Retail Stores and shopping mall 1.0 ECS for every 50 square metres of covered area shall be required.
(4) In offices, Cyber Park/ IT Park/ Cyber Cities, 1.0 ECS for every 40 square metres of covered area shall be required.
(5) In shopping area and designated shopping markets being developed by competent authority, 65% of total site area shall be kept for parking purpose.
(6) In hospital, parking is to be provided as 1.0 ECS for every 2 beds and visitors parking as 1 ECS for every 4 beds.
(7) For industries and institutions, 1.0 ECS for every 100 square metres of permissible FAR of plot.
(8) For restaurant, parking shall be provided as 1.0 ECS for every 2 seats and for multiplex/ cinema/ theatre 1 ECS for every 4 seats.
(9) For hotels and Motels:
Type
Minimum Guests parking requirement
Minimum employees and visitors' parking requirement
4 Star and above
One ECS for each guest room
One ECS for every three guest rooms
3 Star
Two ECS for every three guest rooms
One ECS for every four guest rooms
2 Star
Two ECS for every five guest rooms
One ECS for every five guest rooms
Motels
One ECS for each guest room
25% of the site area
(10) The covered parking in the basement or in the form of multi-level parking above ground level or stilt shall not be counted towards Floor Area Ratio (FAR). However, the footprint of separate parking building blocks shall be counted towards ground coverage.
(11) In case of provision of mechanical parking in the basement floor/ upper stories, the floor to ceiling clear height of the basement/ floor may be maximum of 4.75 metres.
(12) No storage and commercial activities shall be permitted in the covered parking areas.
(13) The misuse of the covered parking space shall immediately attract levy of three times the penalty of the composition fee prescribed for the excess covered area in the respective category.
Note:
For sites other than residential plots, 1ECS = 23 square metres for open parking, 28 square metres for parking on stilts and 32 square metres for basement parking.
7.3Plinth
(1) The plinth of the main building shall be so located with respect to surrounding ground level that proper drainage of the site is assured. The height of the plinth shall not be less than 450 mm and more than 1.5 metres.
(2) The plinth of court-yard shall be at least 150 mm above the level of the street from where entry to plot has been taken and shall be satisfactorily drained.
(3) In no case, any part of the ramp/ steps connecting building plinth to street/ road shall lie on street/ road and obstruct traffic movement. However, the ramp/ step from the plot boundary to the entry of house building, if required shall be provided.
7.4Minimum area, size, height and light and ventilation of different components of Residential premises
(1) Minimum area for a habitable room, kitchen and water closet shall be followed in accordance to tablet given as under:
Sr. no.
Room type
Minimum area (in square metres
Size (minimum width) (in metres)
Minimum Height (in metres)
Light and Ventilation (area of open-able windows, ventilators)
1
Habitable room
9.5
2.4
2.75
Total area not less than 1/8th of the total floor area of the room.
2
Kitchen
5.5
1.8
2.75 (except for the portion accommodate floor trap of above floor)
Total area not less than 1/8th of the total floor area of the room.
3
Pantry
3.00
1.40
2.75
Not applicable
4
Bathroom
1.80
1.20
2.45
5
Water Closet
1.1
0.90
2.45
6
Combined Bath and Water Closet
2.8
1.2
2.45
0.3 square metres on wall not less than 0.3 metres wide.
7
Store
No restriction
No restriction
2.10
Not applicable
10
Garage
14.85
2.75 x 5.40
2.40
11
Doorways Habitable room
Not applicable
0.90
2.10
12
Doorways for kitchen, bath, W.C
Not applicable
0.75
2.00
(2) Habitable room
(i) In case of Group Housing Scheme the dwelling unit having more than one room may have one of the rooms with a clear floor area not less than 7.5 sq. metres with one side not less than 2.4 metres.
(ii) In case of air conditioned rooms, the height shall not be less than 2.4 metres measured from the surface of the floor to the lowest point of air conditioning duct or false ceiling; and
(iii) All doors and windows shall open directly or through a verandah or to a permanent open space or an open space abutting the building not less than 1.8 metres in width. No portion of a room shall be assumed to be lighted, if it is more than 3 metres or as stated in National Building Code 2005, away from the opening provided for lighting that portion.
(3) Kitchen
(i) In case there is a separate store, the floor area of the kitchen shall be reduced to 4.5 square metres.
(ii) In case of houses constructed on plots up to 100 square metres, the size of the kitchen shall be reduced to 3.8 square metres.
(iii) The kitchen which is intended for use as a dining space also shall have a floor area of not less than 9.5 square metres with a minimum width of 2.45 metres.
(iv) For the purpose of this regulation, a kitchen shall be deemed to be a habitable room and all the aforementioned requirements regarding ventilation shall apply to it provided that the minimum area of the kitchen shall not be less than 5.5 square metres with a minimum width of 1.8 metres.
(v) In case of Group Housing Scheme the minimum area of the kitchen shall not be less than 5.5 square metres with a minimum width of 1.8 metres.
(4) Bathroom and Water Closet (W.C):
(i) Every bathroom and water closet shall:-
(a) preferably be so situated that at least one of its walls shall have opening for circulation of external air, with provision of exhaust fan.
(b) not be directly over any room other than another W.C, washing place, bath or terrace unless it has a water-tight floor;
(c) have a platform or seat made of water tight non-absorbent materials;
(d) preferably be enclosed by walls and partitions and the surface of every such walls or partition, shall be finished with a smooth impervious material to a height not less than 1.5 metres above the floor of such room; and
(e) be provided with impervious floor covering sloping towards the drain with a suitable gradient and not towards verandah or any other room.
(ii) Where the water-closet room in a building is not connected to exterior, it shall be ventilated by mechanical means or through a vertical shaft open to sky of a minimum size of 1.25 metre X 1.50 metre for ventilation to toilet, bath and water closet, but it shall be counted towards covered area.
(iii) No room containing water-closet shall be used for any other purposes except as lavatory and no such room shall open directly into any kitchen or cooking space by a door/ window or another opening. Every room containing watercloset shall have a door completely closing the entrance to it.
(iv) Soil or ventilating pipes shall not be allowed on the exterior face of any building, provided these shall either be embedded in the walls or pipe ducts to be provided to accommodate them.
(5) Security rooms each measuring maximum area of 3.0 square metres is permitted only at the entry and exit gates of premises.